Insulation Resistance in tamil || Megohm Value || Megger || IR Value || 500V - 5000V Megger

แชร์
ฝัง
  • เผยแพร่เมื่อ 11 ก.ย. 2024
  • Description
    Minimum insulation resistance value
    At a pressure of 1000 V applied between each live conductor and earth for a period of one minute the insulation resistances of HV installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian Standards. Medium and Low Voltage Installations- At a pressure of 500 V applied between each live conductor and earth for a period of one minute, the insulation resistance of medium and low voltage installations shall be at least 1 Mega ohm or as specified by the Bureau of Indian Standards] from time to time. 1. IR (Min) = kV+1 For most windings made before about 1970, all field windings, and others not described below 2. IR (Min) = 100 MΩFor most dc armature and ac windings built after about 1970 (form wound coils) 3. IR (Min) = 5 MΩFor most machines with random -wound stator coils and form-wound coils rated below 1kV