  • Harbor Freight Predator 9500w Inverter generator runs my whole house including central A/C!!!! Using a soft start system on my 3.5 ton A/C system.

ความคิดเห็น • 251

  • @frontxxrunner
    @frontxxrunner 3 ปีที่แล้ว +10

    Is there any kind of conversation kit for this to run it on natural gas?

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว +6

      Yes, PNGtechnologies.com has one for this generator.

    • @4life409
      @4life409 3 ปีที่แล้ว +14

      I don't think it talks, maybe a conversion kit?

    • @frontxxrunner
      @frontxxrunner 3 ปีที่แล้ว +1

      @@4life409 LOL slide type screw up

    • @MrThumper1440
      @MrThumper1440 3 ปีที่แล้ว +8

      Remember when you switch to natural gas, it will lose a lot of the wattage. I’ve been looking at some different generators that produce around 10k watts with gas and may go as low as 7.5k watts for natural gas.

    • @frontxxrunner
      @frontxxrunner 3 ปีที่แล้ว +1

      @@MrThumper1440 yeah gasoline makes the most power, followed by LPG, and finally natural gas. Your power loss estimate sounds about right

  • @BestKaylee
    @BestKaylee ปีที่แล้ว +4

    Thank you for the video. There are two issues that should be covered. There needs to be a generator interlock kit in the service panel. to prevent the line power and the generator from being on at the same time. Secondly it is not recommended to leave the generator power cord coiled. The cord could overheat and be damaged.

  • @sarabear1238
    @sarabear1238 ปีที่แล้ว +42

    We have used the th-cam.com/users/postUgkxOTeIs0vv4_9B5hsmnLsk9r930uDQLu_Y for probably 30 hours with our camper and it’s been great! The noise level is really only noticeable when running the AC and other appliances like the microwave, hair dryer, or coffee pot. It’s not huge like other ones and it has wheels so even at 90lbs, I can move it!

  • @joeyv9688
    @joeyv9688 2 ปีที่แล้ว +6

    Just an outstanding video man. Out frickin standing!! I haven’t even unboxed my Predator 9500. I am looking to do the exact same thing. You couldn’t have covered it any better. Review on everything and nothing at all missed!! 👏 Thank you 🤘Great info on all the AC stuff to.
    Joey V

  • @RobertL78
    @RobertL78 3 ปีที่แล้ว +47

    Square D makes an interlock kit that will make sure you can’t have the generator and main breaker on at the same time. It’ll be up to code for most areas then.

    • @AP-514
      @AP-514 3 ปีที่แล้ว +6

      yup your going to HELL if you do not install that $50 Interlock kit...:)..No really install it ! !

    • @DieselRamcharger
      @DieselRamcharger 2 ปีที่แล้ว +3

      @@AP-514 you might end up their quicker than expected if ya dont have it! lol

  • @marknichols7861
    @marknichols7861 3 ปีที่แล้ว +44

    I would recommend installing a Generator Interlock Kit on your panel. It may be a legal requirement depending on your local codes. It will also prevent killing a lineman working on the grid if you should happen to forget to disconnect your main breaker while running the generator.

    • @glock19gen3
      @glock19gen3 3 ปีที่แล้ว +3

      Funny how he has replied to every other reply but the ones asking him to not kill others lol

    • @kustomaf7606
      @kustomaf7606 3 ปีที่แล้ว +4

      @@glock19gen3 he replied to @Bob O
      A couple weeks ago about back feeding the utility. He should have an interlock but if I get lit up from backfeed, that means I broke some rules too. I am a JL

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว +12

      I going to get a kit for my panel soon and will put a video up on installing it. Thanks for your input!

    • @olemissjim
      @olemissjim 3 ปีที่แล้ว +6

      Won’t “kill a lineman” they are always supposed to ground the line before working it. An ATS or interlock is important tho, and without it you are back feeding your neighbors, so your generator will fail trying to power THIER houses.

    • @frontxxrunner
      @frontxxrunner 3 ปีที่แล้ว

      Yeah it's code in NJ. Illegal without it. I feel better having it on there for the safety.

  • @TheBry_Guy
    @TheBry_Guy ปีที่แล้ว +1

    I have the Honda 7000 (5500 sustained) and it works for me the same way. My A/C is only a 2 ton but I have the same soft starter (smaller model). Mine has the same starting amps, but draws about 6 amps continuous when running. With the inverter power everything is rock solid in the house unless we turn on the electric stove. you can see a faint flicker in the lights every time the element (3500W!!!) kicks on. but I can cook with the A/C running without fear of overloads!

  • @Ruquick1
    @Ruquick1 3 ปีที่แล้ว +15

    Micro-Air Easy Start makes a world of difference with the crazy reduction of inrush current. Game changer for backup generator use.

    • @Ruquick1
      @Ruquick1 3 ปีที่แล้ว +2

      @@ver151set My unit pulled 95.8 amps before installing a Micro-Air Easy Start. Now it only pulls 13.7 amps so I'm happy with the results. I'm also a fan of the Harbor Freight Predator generators. I use one to run my 2,000 watt fishing lights and its actually quieter than my Yamaha inverter generator.

    • @chris-n-melissahawks2809
      @chris-n-melissahawks2809 3 ปีที่แล้ว

      @@ver151set Emerson doesn't actally make the securestart. It's made by hyper engineering and then labeled for Emerson and several other companies. Hyper Engineering was started by an ex microair employee from what I've read. The hyper engineering units currently being sold under their brand and other labels are more like the original microair. The current microair soft starts are more advanced.

  • @paulmcclure7794
    @paulmcclure7794 3 ปีที่แล้ว +6

    I use similar setup wiring wise with a different ~7500 watt continuous gen, wired into my whole house breaker through an interlocked breaker... Think I also may have same Garmin as you, love the Fenix 6X, it is amazing!
    I also bolted on a ~$30 propane conversion kit onto my gen, so I can run 2 story home central AC from a propane tank in power outage, and it also still runs on gas...just flip a valve open (I keep fuel stabilizer in full gen fuel tank).

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      Haha good eye! I love my Garmin!!! It sounds like your good to go with your setup.

    • @paulmcclure7794
      @paulmcclure7794 3 ปีที่แล้ว

      @@JayMaxWrench Thanks, yeah I try to get about 20miles a week runs in...take care

  • @Mark-zz9rt
    @Mark-zz9rt ปีที่แล้ว +1

    Great video thanks from Michigan. $1,100 for that generator. For a generac home generator $8000

  • @Cenlalowell
    @Cenlalowell 3 ปีที่แล้ว +3

    You can use a hard start kit as well. I have one on mine.

    • @vmsr1969
      @vmsr1969 3 ปีที่แล้ว

      I have a 3 ton unit with the same predator generator....do u know if the heat pump can also be used in case of need.?
      Thank you🙋🏻‍♂️

  • @jeffconley819
    @jeffconley819 2 ปีที่แล้ว +4

    One important thing to do is never coil your electric extension.
    When the cord is in a coil it will heat up the higher the amp draw is.
    Make a dedicated cable to go from the generator to the house input.
    I learned this lesson first hand when my coiled cable melted.

    • @JayMaxWrench
      @JayMaxWrench  2 ปีที่แล้ว

      Thanks for the tip!

    • @MikeyJEveryday
      @MikeyJEveryday 2 ปีที่แล้ว +2

      That's cause your wire gauge was to small or had broken strands in the extention itself. Has nothing to do with coiling the cable. Dedicated wire is always the best option.

    • @jcyork1767
      @jcyork1767 2 ปีที่แล้ว

      #metoo

    • @jeffconley819
      @jeffconley819 2 ปีที่แล้ว +1

      @@MikeyJEveryday yes the gauge was to small for sure. But the coiling of such a long piece of cable added to the problem .
      You can research on your own if you what the technical aspects.
      Our electrical engineer at work explained the how’s and whys to me but frankly I don’t remember what he said. I just know to never do that again .

  • @eddierodriguez419
    @eddierodriguez419 3 ปีที่แล้ว +6

    Wow i just saw your other video of this generator.. FROM THIS VIDEO FOR THE PRICE IS A FRIGGIN BEAST 💪🏼💪🏼 TY BUD

    • @shaunsmuder3880
      @shaunsmuder3880 3 ปีที่แล้ว +1

      They're junk I've had 4 of them I've taken them all back they're junk don't waste your time

    • @eddierodriguez419
      @eddierodriguez419 3 ปีที่แล้ว

      @@shaunsmuder3880 oh really from the looks of it seems legit but thanx for the input

  • @daved6569
    @daved6569 3 ปีที่แล้ว +6

    That motor sounds like my Honda 7000. Wow. I want a predator

    • @FullSendPrecision
      @FullSendPrecision 3 ปีที่แล้ว +4

      They're honda clones and are great engines.

    • @rebellucy5610
      @rebellucy5610 3 ปีที่แล้ว +4

      Stick with your Honda 7000.

    • @earllittle6591
      @earllittle6591 2 ปีที่แล้ว +1

      @@rebellucy5610 it have them both 1A & 1B. So I'm really for whatever.........

  • @gene2200
    @gene2200 3 ปีที่แล้ว +2

    Break in on these is crucial, check some video if need be, after that use Lucas 20-50 syn oil or 10-40 in below 30 temps. Rung one out using conventional oil, I'd be black in 3 days where syn is clear for 3 wks. Now to get a piston and rings, should be easy rebuild.

    • @gene2200
      @gene2200 3 ปีที่แล้ว

      Recently just came across a Westinghouse with 9000 watts, pretty much built the same as predator 9000, meaning it would fit my genny shed, with 2yr warranty not 90days. Comes with battery, wheels and remote on/ off. Was $850, much better or couldn't be worse then predators. The remote it's self is a great option

  • @SkypowerwithKarl
    @SkypowerwithKarl 3 ปีที่แล้ว +2

    When I turn on my 15 year old 2 ton AC, no soft start, it barely makes the 9500 grunt in Eco mode. The Predator is a beast. Could probably run the dryer at the same time LOl.

  • @terraGaliciaXXIV
    @terraGaliciaXXIV 3 ปีที่แล้ว +2

    The Costco Firman unit is hard to hear at $899 though and more power. Also a tri fuel generator in case of emergency use

    • @SkypowerwithKarl
      @SkypowerwithKarl 3 ปีที่แล้ว

      That’s a nice unit too, but you have to be very careful with some electronics. Don’t start or stop it or let it run out of gas with the load connected. Your equipment may see the run up voltage and frequency. Some thing don’t like that. Inverter types generally don’t output till the juice is right.

  • @shanwar9844
    @shanwar9844 3 ปีที่แล้ว +8

    Looks like a nice setup.

  • @winniethepooh1931
    @winniethepooh1931 3 ปีที่แล้ว +5

    Install an interlock so it will only allow either main or generator.

  • @Shonschannel
    @Shonschannel 2 ปีที่แล้ว

    I just put a 1 ton mini split in my master bedroom to run off my generator. Noe of these store bought gens can handle my 5 ton main unit. Plus the mini split also has a heat pump so we are good during any summer outages as well as winter outages.

  • @danray9744
    @danray9744 2 ปีที่แล้ว +1

    Whole House includes Water Heater 40 amps & Stove 50amps ! which NO 9500 surge 7600 run watt Generator will Handle !

  • @franklin051579
    @franklin051579 3 ปีที่แล้ว +7

    The price just increased to $1,999.99!!! So Glad I got mine when it was released, I am sure you feel the same! lol

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว +1

      Absolutely!!

    • @franksanna217
      @franksanna217 3 ปีที่แล้ว

      What was the price before?

    • @jaredairhart2818
      @jaredairhart2818 3 ปีที่แล้ว +2

      @@franksanna217 1799.99

    • @freedomranch6094
      @freedomranch6094 3 ปีที่แล้ว

      Still $1799 with the HF CC and 36 month no interest. 10% off

    • @bubbatime
      @bubbatime 3 ปีที่แล้ว +2

      Price is up to $2200 today 11/23/21

  • @RadioReprised
    @RadioReprised 2 ปีที่แล้ว +2

    I can't believe the A/C unit is drawing 8 amps...something is wrong. Should be around 20 or higher. Soft start doesn't change running amps. My new 4 Ton draws 26 continuous....

  • @uainttheone
    @uainttheone 2 ปีที่แล้ว +4

    5 days straight! ? Holly shyte! Hope you got the protection plan and 30 bucks a day for gas... Let's go Brandon!

  • @jimmytate7587
    @jimmytate7587 3 ปีที่แล้ว +9

    important to remember....this generator is NOT a 9500 watt running generator. it is a 9500 watt starting current generator. if you try to run a continuous load of more than 7500 watts you will quickly kill the generator

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว +3

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

    • @ShowMeWhatINeedToKnow
      @ShowMeWhatINeedToKnow 3 ปีที่แล้ว

      Will it trip something on the generator or will it actually fry the generator? This generator doesn't even tell you how many watts are being used -- so not sure how you are supposed to know.

    • @TheBry_Guy
      @TheBry_Guy ปีที่แล้ว

      @@ShowMeWhatINeedToKnow Yes, every outlet on a generator has a breaker that will trip. Also the generator has an internal overload. Inverters are smart about it and can let you pull 9500-ish (or whatever your peak power is) watts for a short time and flash a warning (like 10 seconds) before shutting off.

    • @ShowMeWhatINeedToKnow
      @ShowMeWhatINeedToKnow ปีที่แล้ว

      @@TheBry_Guy Thanks!

  • @yvonneagundez1994
    @yvonneagundez1994 5 หลายเดือนก่อน

    Hey man I appreciate that video of the 9500 predator I did have a question about the outside panel I see the 200 and I see the double pole 30 where are the other smaller loads breakers connected to how does the predator power the other loads breakers

  • @cuz129
    @cuz129 ปีที่แล้ว

    I have the same generator but I've got a total electric house including the water heater. I could run the AC if I added a soft start to it. I'm thinking about doing that. That's not a recommended set up you've got, by the way. You have to have an interlock so you can't back feed to the grid. That could kill a lineman if you flipped one of the breakers the wrong way.

  • @thelast1900
    @thelast1900 3 ปีที่แล้ว +4

    Hyper engineering also makes one. Emerson who builds most ac compressors actually rebrands the hyper engineering unit as their own. The box also lessons the stress on the compressor bearings on start. Excellent addition with a generator. Most generator installation companies never heard of the units.

  • @jpenn727
    @jpenn727 3 ปีที่แล้ว +1

    I have almost the same setup. My micro air took my 3.5 ton AC from 50Amp to 27Amp. Today I Just got the Westinghouse 9500DF generator. I hope to get it plugged in this weekend for break in and testing.

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @hondaredrdr
    @hondaredrdr 3 ปีที่แล้ว +3

    Thanks for the video, thinking about doing the same thing

  • @phbrinsden
    @phbrinsden ปีที่แล้ว +1

    Be safe ! Put the interlock plate on.

    • @ACommenterOnYouTube
      @ACommenterOnYouTube 3 หลายเดือนก่อน +1

      Oh no ... the arm chair interlock police just spoke up

  • @flowrob6861
    @flowrob6861 3 ปีที่แล้ว +2

    If you would Ambient temperature , house temp setting , house square footage as a comparison

  • @scoot77777
    @scoot77777 ปีที่แล้ว

    Wow! Very nicely done! Straight forward to the point great presentation 5 ⭐️ ⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️⭐️ excited to get my system on line. I have a 4 ton unit and just installed the easy start Module working on getting a power plug installed Thank you 😊 for your time and efforts to share your information 🎉

  • @KuntalGhosh
    @KuntalGhosh 3 ปีที่แล้ว +3

    That's why i use inverter ac. There is no surge of power .

    • @HFJCHS123
      @HFJCHS123 3 ปีที่แล้ว +2

      Agree inverter AC and higher SEER are more cost up front but will pay back over the years of use. My 3 ton 20 SEER inverter replaced a 21 year old 10 SEER. Loving the elect savings. Today checked the compressor at 6.7 amps running g and 0.94 amps for the outside outside condenser blower ecm motor. Only other draw is for inside air handler blower ecm motor. Likely total draw for 3 ton central ac is under 9 amps running.

  • @robfrischkorn9405
    @robfrischkorn9405 2 ปีที่แล้ว +1

    You mentioned this is a 3.5 (42k Btu’s) condenser. I see that your Micro Air Easystart is rated for
    49-72K BTU, the internal capacitor with this model is 270-324MFD. Shouldn’t you have gone with X48 model instead of the X72 model for this application?
    Or replace the 270-324MFD capacitor with the 189-227MFD since it’s rated for 37-48K BTU?
    Thanks

  • @KA-nd7od
    @KA-nd7od 3 ปีที่แล้ว

    Am I going to be able to run the house furnace in the winter,also I got one freezer,one refrigerator,sump pump, electric laundry machine and water heater.?! am about to get the last Predator 9500 in the store ..

  • @payloadperformance9706
    @payloadperformance9706 3 ปีที่แล้ว +5

    Friggin awesome generator!!

  • @DieselRamcharger
    @DieselRamcharger 2 ปีที่แล้ว +2

    put an interlock kit on that panel my man!

  • @zappos49
    @zappos49 2 ปีที่แล้ว

    What’s the best way to get the power from the generator into the home? I want to run 3-4 1,500 watt electric ⚡️ heaters this winter.

  • @markhunt6573
    @markhunt6573 3 หลายเดือนก่อน

    Do they make a wattage output meter for this model?

  • @diytypeofguy6502
    @diytypeofguy6502 3 ปีที่แล้ว +7

    Thing is a beast

  • @hitmanhite
    @hitmanhite 3 ปีที่แล้ว +1

    Be interesting to see what kind of amps it would pull without the soft start on the meter for your specific unit.

    • @vitin6039
      @vitin6039 2 ปีที่แล้ว

      I got a 2.2 Ton AC and it pull 72.5 amps to start 13.5 amps running impossible to start without the easystart kit

  • @navyretired230
    @navyretired230 3 ปีที่แล้ว +1

    Did you turn off some appliances?

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว +1

      Everything was connected. But you must be mindful of not running high draw appliances like the stove/oven,clothes drier and, the central A/C at the same.

  • @Nickyboy343
    @Nickyboy343 8 หลายเดือนก่อน

    So that thing will run your ac and your whole house at the same Time?

  • @keithesteen1356
    @keithesteen1356 7 หลายเดือนก่อน

    Is it best to turn central air on last after turning on other breakers

  • @ammogiant824
    @ammogiant824 3 ปีที่แล้ว +3

    Wouldn't a hard start capacity do the same? That's what I'm using.

    • @MichaelGraves3304
      @MichaelGraves3304 3 ปีที่แล้ว

      No. I actually just tried this this past weekend.
      A hard start capacitor is about adding extra startup current to help overcome an aged, inefficient compressor. A hard start kit delivers more current to help get it moving. It does not significantly/specifically reduce initial inrush current.

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @wentbrokestayingmiddleclas4907
    @wentbrokestayingmiddleclas4907 3 ปีที่แล้ว +2

    Thanks for the video! I heard air conditioner noise can bother the neighbors, but the generator certainly will. Is there a way to put it in the garage and vent it outside ? also for security so it is still there in the morning 😀

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      I wouldn’t do that. Carbon monoxide isn’t called the silent killer for no reason. Unfortunately theft is something we can’t avoid. Maybe chaining the unit to a eye that has been set in concrete would give some added deterrence. I heard a story about a thief that came with a lawn mower and swapped it in place of the generator so that no one would hear the generator turn off and wake the people sleeping in the house…… Pretty clever, I think that when security comes to mind you gotta think how a thief would steal your unit with limited time and tools. Thanks for the comment.

    • @314Tazo
      @314Tazo 3 ปีที่แล้ว +2

      @@JayMaxWrench Doesn't the manufacturer say to place the generator 15 - 20 ft. from home and windows.

    • @joeross952
      @joeross952 ปีที่แล้ว

      Every year on the gulf coast they say never put a generator in the garage. I always ask myself who is that dumb.

  • @harryinoklahoma1866
    @harryinoklahoma1866 3 ปีที่แล้ว +2

    HF is suppose to come out with a parallel cable so you can hook up two of those 9500 Inverters. How awsome is that?

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      I’am excited for it! One of these units is great I can only imagine two!

    • @johnprice6212
      @johnprice6212 3 ปีที่แล้ว +1

      Has anyone heard what the max amps might be on the parallel kit?

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      @@johnprice6212 I haven’t seen any spec’s yet…….

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      @@johnprice6212 I used the EasyStart Micro-Air 368 3-6 ton capacity

    • @dalepatterson1748
      @dalepatterson1748 3 ปีที่แล้ว +1

      50 amps

  • @nshrestha5673
    @nshrestha5673 ปีที่แล้ว

    Did you put the ESC throttle button OFF or ON position while running the whole house including A/C?

  • @stevereason6931
    @stevereason6931 ปีที่แล้ว

    Were you running your A/C with a Micro Air Soft Start connected to it?

  • @nadermazari3334
    @nadermazari3334 2 ปีที่แล้ว

    I'm sorry but I did not understand the function of the Micro Air switch on your condenser. Also, can you use a 60 amp input and wire? Thx.

  • @uainttheone
    @uainttheone 2 ปีที่แล้ว

    What if you were spinning an alternator with a small electric motor powered by the gen

  • @monoralph1375
    @monoralph1375 3 ปีที่แล้ว +6

    Be sure not to point the engine exhaust at the condensing unit

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      Yeah absolutely. It Would really hurt the performance of the condenser and translate to poor to no cooling inside the house. Thanks for the input!

  • @SgtRudySmith31bRet
    @SgtRudySmith31bRet 3 ปีที่แล้ว +15

    Have you hooked up the generator legally yet?

    • @fattysgarage1754
      @fattysgarage1754 2 ปีที่แล้ว +1

      What is the statute for this illegal hook up?

  • @JavierRivera
    @JavierRivera 3 ปีที่แล้ว +2

    Hey, I am planning to do the same. Did you know that the Predator 9500 can do 63.3 amps? You would need a 1 Y Adapter Cord 50Amp (L14-50r) receiver to Two 30 Amp plugs, Cut the Y adapter and re-wire 2 new plugs L5-30P and L14-30P.; you can find them at amazon. You would need to change your brake for a 50-60 amps breaker.

    • @raybees72
      @raybees72 3 ปีที่แล้ว

      You're going to burn your house down.

    • @Davidsnet1
      @Davidsnet1 3 ปีที่แล้ว

      So a 9500 watt generator can put out 63.3 amp X 220V =13,926 Watts.... The math dosen't add up buddy.

    • @raybees72
      @raybees72 3 ปีที่แล้ว

      @@Davidsnet1 I'm not really sure what he is trying to do. You should only load a breaker to 80%, so on his 30A that's 24A. now on 240V, both legs you can do 48A but not with this unit. this unit running is 7600W so (P/I) 7600/240 = 31.6. and yes it can do 9500W but that's for a very short time.
      Now the Y adapter thing. WHY? You have one L5-30P 120V and one L14-30P 240V on the unit. So you going to pull only 120V from the L14-30P??
      You are still going to end up with 240V on a 30A breaker. and you better hope you grab the opposite leg than the L5-30P.
      "You would need to change your brake for a 50-60 amps breaker." WTF!!!! why? so you make sure it never trips?

  • @duganfr
    @duganfr 3 ปีที่แล้ว

    It has enough power to start and run your condensing unit which is what that is. Does it have enough to run your air handle at the same time?

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว +1

      Yes they run in sync with each other the handler has a delay of about 2 seconds when it comes on

  • @jidic1845
    @jidic1845 6 หลายเดือนก่อน

    This generator does not produce enough Amps to run a whole house. With the soft start, the generator may handle the A/C and the fridge compressor. Adding the draw from everything else will shut that unit down.

  • @clutester
    @clutester 2 ปีที่แล้ว

    I'm looking into this setup myself. Is there a reason you went with the 30A plug over the 50A?

    • @atvjam9626
      @atvjam9626 2 ปีที่แล้ว

      30amp = 7500 watts which is this generators max running out put

  • @Lloydski
    @Lloydski 3 ปีที่แล้ว +1

    Whats the locked rotor amps ( LRA ) on the ac compressor with out that soft start connected.

  • @MrSkunks
    @MrSkunks ปีที่แล้ว

    What 5 ton is that? It only runs 8 amps? Mine runs at like 20!

  • @percyfaith11
    @percyfaith11 ปีที่แล้ว

    Is this Predator Inverter generator still operational?

  • @johnyee7323
    @johnyee7323 3 ปีที่แล้ว +1

    Did you modify your generator to floating neutral?

  • @djgilblake
    @djgilblake 3 หลายเดือนก่อน

    ❤👏🏼👍🏼 Nice job

  • @Thanosisnotreal
    @Thanosisnotreal 2 ปีที่แล้ว

    What size is your ac ? Mine is a 2.5 ton, I’m hoping the Predator 9500 works well to power my home.

  • @brandonjay_gotem
    @brandonjay_gotem 2 ปีที่แล้ว

    man what a game changer

  • @terraGaliciaXXIV
    @terraGaliciaXXIV 3 ปีที่แล้ว

    Is there a difference with this soft start brand vs the Hyper Engineering offering?

  • @greginfla_1
    @greginfla_1 3 ปีที่แล้ว

    Do you have before micro air amp draw numbers? I just went out and checked my AC it’s starting amps is 25 it’s running amps are 10..... i was surprised how little it drawed; wonder what a micro air can do

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว +1

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps

  • @smunro851
    @smunro851 ปีที่แล้ว

    Can u tell me what model the micro air easystart is

  • @StandingOnScriptures
    @StandingOnScriptures 10 หลายเดือนก่อน

    Great vid!

  • @dogman807
    @dogman807 3 ปีที่แล้ว +1

    How long will it run on a heavy load?

  • @gasser2348
    @gasser2348 3 ปีที่แล้ว +1

    Wow, way to go, thanks.

  • @asj9793
    @asj9793 3 ปีที่แล้ว

    I was wondering which MICRO- AIR 368 model did you choose and why? Does it makes any difference weather it's the up to 48 thousand btu version or the 48 thru 72 thousand btu model

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @dhansel4835
    @dhansel4835 3 ปีที่แล้ว

    The generator is not enclosed so how would it do in a driving rainstorm with everything getting wet?

    • @blackmacgyver9965
      @blackmacgyver9965 3 ปีที่แล้ว +1

      Just build a small
      Shed for it

    • @dhansel4835
      @dhansel4835 3 ปีที่แล้ว

      @@blackmacgyver9965 My experience with small sheds is that they reflect the noise of the generator and sound much louder than they are.
      You can build a bigger one, insulate it with sound dreading material and put powered exhaust fans in it to keep it cool.
      I have seen some enclosures already made for a little over $ 1,800.
      With that expense I would just go and buy a Generac Generator which will auto-switch to the generator and has it's own weather proof cabinet.

  • @raybees72
    @raybees72 3 ปีที่แล้ว

    On a 30A plug, you can only load it to 80% so that's 24A. so the only thing you can run is the A/C.

    • @ShowMeWhatINeedToKnow
      @ShowMeWhatINeedToKnow 3 ปีที่แล้ว

      Can you explain what you mean please? I was thinking of getting one of these. If it matters, I was going to convert the Predator 9500 30amp output to a 50amp connection / cord -- using an adapter.

    • @raybees72
      @raybees72 3 ปีที่แล้ว

      @@ShowMeWhatINeedToKnow There is no point in going to a 50A plug. Explain what?

    • @raybees72
      @raybees72 3 ปีที่แล้ว

      You should only load a breaker to 80%, so on his 30A that's 24A. now on 240V, both legs you can do 48A but not with this unit. this unit running is 7600W so (P/I) 7600/240 = 31.6. and yes it can do 9500W but that's for a very short time.

    • @ShowMeWhatINeedToKnow
      @ShowMeWhatINeedToKnow 3 ปีที่แล้ว

      @@raybees72 -- Awesome; thanks. So plan on running 24 amps, which would be about 5760 watts, right?

    • @ShowMeWhatINeedToKnow
      @ShowMeWhatINeedToKnow 3 ปีที่แล้ว

      @@raybees72 -- think I got it; thanks.

  • @felaxchow207
    @felaxchow207 3 ปีที่แล้ว +3

    For a 7500 running watt inverter generator that is capable of 120/240 volts is pretty good bang for the buck in the $2k range. I was fortunate to qualify on their financing to break it down to 3 years same as cash helping to take the sting out of the cash flow, but it is worth it. I can start up my 2.5 ton hvac unit at full rpm mode and once it is up to speed, I can put in economy mode. The Micro-air soft start units are a great add-on if you're replacing the outside unit anyway or if it is less than 5 years old. In my case, I really can't justify the $400 price tag on a 16+ year old outside condensing unit; I might as well put that cost towards installing a single or multi-head mini-split heat pump.
    For the time being I just need to manually prioritize my energy usage which not too bad for a single person. I got by for the past 8 years on the 3500 inverter generator; got lights, a cold fridge/freezer, and a fan. This definitely a major upgrade; now I got lights, a cold fridge/freezer, hvac, and electric hot water!

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      Don’t forget about the generator safety rules: anyone who uses portable gas generators really needs to see this safety reminder. All generator safety rules should be followed carefully. This advice is just to make sure that everyone is aware of all the warnings and it’s just to remind people to be careful using portable generators. Generators can be dangerous if not used carefully. Every year, hundreds of people die or get injured when using portable generators due to carbon monoxide poisoning and electrocution. Make sure you are using your generator carefully and keeping others safe as well. There is something very serious that everyone should always be aware of when using generators. Some people do run their generator indoors which is not safe and that increases the risk of carbon monoxide poisoning which can cause death of family and you. Some people run their generator in wet conditions which can electrocute them. Please remember that you should never run your generator indoors. Remember that carbon monoxide is an odorless and colorless gas that you cannot see or smell. Carbon monoxide is a silent killer. Keep that in mind. Make sure your generator is 15-20 feet away from your house and away from doors, windows, and vents. Never use your generator in your porch too. Having a carbon monoxide detector is very important against generator safety. Some people also allow children to go near the portable generator which could pose risks. We need to keep an eye on our children making sure that they are not near the portable generator so they won’t get electrocuted or burned by the generator which is dangerous. A locking enclosure also keeps kids safe. A generator shed might look like a tempting place to explore, or take cover during a game of hide and seek, but a generator is a dangerous piece of equipment that can cause injury. It says on the manual that we should also keep children away at all times from the portable generator to avoid injuries. Please do not allow a child or unqualified people to operate the portable generator. Just because some manuals missed what should be listed doesn’t mean it’s safe to do. Always follow the generator safety rules when using portable generators. Generators pose electrical risks. If you need to use your generator during wet weather, you need a generator tent to protect your generator from getting wet. Don’t let your generator get wet. Keep your generator dry and before using your generator, please make sure your hands and your generator is dry. Do not wear loose clothing when operating the generator. Everything that is said on the generator’s operating manual should not be ignored. Never smoke cigarettes near the generator. Please keep flammable things away from the generator. Never overload your generator too. Your generator can catch fire. Never ever try to plug a generator cord into a wall outlet to avoid back feeding. Back feeding your generator is dangerous. Always turn on your generator first before plugging in appliances and shut off the appliances before turning your generator off. Use a heavy duty cord for your generator and the cord should not be worn out. All the instructions should be followed carefully. Never refuel your generator while it’s running. It can cause fire if fuel spills while your generator is hot. You should turn off your generator and let it cool off before refueling it. Having a fire extinguisher next to the generator is also important. This is only a reminder for everyone’s safety of using generators. Make sure your generator is properly grounded. Having a fire extinguisher next to the generator is also important against the safety rules. th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators and also about our family’s safety. Hope this helps. Thank you.

    • @felaxchow207
      @felaxchow207 3 ปีที่แล้ว +1

      @@The_Happy_Aviation_Enthusiast grounding your generator on a home that has an generator input with an interlocked transfer switch actually will potentially cause a hazardous condition due to it being a non-seperately derived system where the neutral on a 120/240 split phase system is floating. The point where the grounding electrode conductor terminates at the neutral bus bar is at the first point of the utility disconnect. On a locking 30 amp 3-pole 4-wire generator cord carries the required isolated neutral and required equipment grounding conductor to bond the generator to neutral/grounding bus bars in the main service panel. If you ground your generator in that type of situation and there is a fault with the bonding with the grounding electrode; you will have stray current looping between them causing a pretty nasty shock if you complete the circuit unintentionally.
      If it is a standalone operation with a spaghetti model of extension cords running inside your house then grounding your generator is definitely needed. The other option is to install a separately derived system transfer switch where both neutral and grounds are bonded independently one for the utility and one for the generator. The only equipment bonding is common with both utility and generator and the neutrals are isolated from each other. This commonly done mostly in health care facilities and industrial applications. These types of transfer switches start around $2k USD, plus labor to install it.

    • @stevereason6931
      @stevereason6931 ปีที่แล้ว

      So you were able to run your A/C with your inverter generator without the Micro Air Soft Start?

    • @felaxchow207
      @felaxchow207 ปีที่แล้ว +1

      @@stevereason6931 short answer is yes, but you have to run the generator at full rpm and shed any loads that is currently running with the exception of a LED light or a small fan. 54 amps locked rotor is right on the very edge of tripping out the overload protection or stalling out your generator.
      I just recently replaced my heat pump unit and added the Micro Air soft start at the time of installation; the locked rotor amps is now below 20 and running is around 6. Well within the generator's operating specifications , now I can run it on ESC mode not skipping a beat when the compressor kicks in.
      A more budget friendly version has come along in the market by ICM controls. Their version is the ICM870 in the

    • @stevereason6931
      @stevereason6931 ปีที่แล้ว

      @@felaxchow207 Thanks for the quick and thorough response. I just bought a 6500 running watt inverter generator and will be using a 50 amp 6 gauge cord. I will attempt to run only the house 3 ton A/C with it and if it works I will then turn on individual breakers to see how much it can handle. If the A/C is too much without the Micro Air Soft Start, I will at least be able to run most everything else for the time being and I can always add the Micro Air Soft Start later. Another option would be to later add another inverter generator, with less wattage, in parallel.

  • @mrfunkington
    @mrfunkington 3 ปีที่แล้ว +1

    Question isn't valid.
    The generator can run an 8000w load. Does your house pull more than 8000w of power? If no, then no problem. If yes then it can not.

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @littlerascal2753
    @littlerascal2753 3 ปีที่แล้ว +1

    how big is your house???

    • @CL-gq3no
      @CL-gq3no 3 ปีที่แล้ว +1

      In South FL that size AC would typically go into about a 2500 sqft home.

  • @victorm7274
    @victorm7274 3 ปีที่แล้ว +5

    You really should install a lock out. You could potentially kill some one working on the electrical wire down stream.

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️That is why the generator safety tips should be followed carefully and not be ignored as well:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @demoll78
    @demoll78 3 ปีที่แล้ว

    What soft start kit you bought

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      It’s a Micro-Air Easy start

  • @luismedina2029
    @luismedina2029 3 ปีที่แล้ว +1

    How many tons is your a.c unit

  • @sanjuanpr25
    @sanjuanpr25 3 ปีที่แล้ว

    What’s the square footage of the house this generator is running and what’s the size of the generator?

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @johnwalker890
    @johnwalker890 3 ปีที่แล้ว

    Good luck.

  • @gm1300r
    @gm1300r 3 ปีที่แล้ว +1

    What model # is your Rheem 3.5 unit, I have a 3.5 Rheem too. But my amps went from 100 at start up to 43 amps, with the soft start, still a big drop, but not sure the predator will run it
    Thanks for any help

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      I would have to look at model number. It’s a 6 year old unit. At 43 amps it would exceed what the 30amp rating of the single 220v outlet on the generator. In my opinion it most likely would trip the breaker that protects that outlet.

    • @gm1300r
      @gm1300r 3 ปีที่แล้ว

      Thanks for the reply, living on the coast just trying to get ready for hurricane season, I was
      Hoping to use the predator generator, may have to wait till Predator comes out with a parallel system, my model # is RA1442BJ1NA , thanks again

    • @gm1300r
      @gm1300r 3 ปีที่แล้ว

      looking at the video again, looks like your unit is a RA1642AJ1NA, that makes yours a 16 SEER vs mine is a 14 SEER, but it shows to have the same Lock Rotor AMPS @ 109, not sure why my amps are still so high. What wire did you use to get your first amp reading before the soft start. Thanks for any help!

    • @mhr7962
      @mhr7962 3 ปีที่แล้ว

      The soft start kit takes five on/off cycles to learn in order to work best. Test again and maybe the start amps are down. I put one on a new 3 ton Carrier unit and my start amps went from 92 down to 17. Maybe because my unit is new and we let it cycle five times.

    • @gm1300r
      @gm1300r 3 ปีที่แล้ว +1

      I let it run for 24 hours and checked it again, same reading at 46 amp @ LRA, I picked up the inverter the other day anyway , and ran the 30amp /240 side converted to my 50amp plug on my electrical panel, it ran the whole house in the ECS mode. The math isn’t adding up somewhere, but it works, will be ordering my natural gas kit soon, I know I’ll lose some amp output using natural gas, crossing my fingers that it will work. Super happy with it so far.

  • @TheNoviceAquarist
    @TheNoviceAquarist 3 ปีที่แล้ว

    Great vid good info

  • @mega-hb4re
    @mega-hb4re 3 ปีที่แล้ว

    Good to know but I have a 5 ton unit so I don’t think that it will do it.

    • @MM-yv1ny
      @MM-yv1ny 3 ปีที่แล้ว

      Micro-Air makes a soft start for a 5-ton unit, but go with a genset that has 50amp capabilities/ 50 amp recep. I just bought one for my 4-ton unit.

  • @rickcormier9160
    @rickcormier9160 3 ปีที่แล้ว +1

    Did you need to ground the generator to connect it to your breaker box? I had an electrician install a 50amp connection into my breaker box. I am planning to buy a 7000 or more running watt generator. I have noticed some are grounded to the frame, but this one and the almost identical Duromax inverter have a ground connection on the panel.
    (Also, I am not sure about this, but have been told it is bad to coil your extension cords when in use because it can create issues??)

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว

      I didn’t in the video but will when I am normally using it. It’s highly recommend for the safety of the operator especially when it wet and rainy.

    • @SkypowerwithKarl
      @SkypowerwithKarl 3 ปีที่แล้ว

      If your electrician was halfway competent, you should have a ground through the cord when you connect. If you run the Predator 9500 or Duramax version, you will have to change the plug on the cord at one end or the other since you have a 50 outlet and those generators use 30 amp 240. A 50 amp cord has very little power loss but it’ll be creative stuffing the #6 wire into a nice Eaton 30 amp plug. I’ve done it with smart dremel work because I’m stubborn and didn’t want to cut strands Lol. Forget the 30amp plug that comes in the tool kit for 6/3+8/1 50amp cable.

  • @area51flyby
    @area51flyby 3 ปีที่แล้ว +2

    A generator with that level of output should have a 50 amp plug! HF screwed up big time on that! Also, wish it was dual fuel capable -- gasoline or propane. If it had those two features, I would buy it, but it does not, so I'll have to buy a different brand unit.

    • @crazymk6
      @crazymk6 3 ปีที่แล้ว +5

      Well, the running watts for this generator is 7,600. So really it would only utilize a 32 Amp plug. (7,600 watts/240 volts). So the 9500 watts it puts out, is only for a few seconds. So the 50 amp outlet would be overkill anyway, since the generators breaker would pop at anything over 32 amps.

    • @josedaniel4725
      @josedaniel4725 3 ปีที่แล้ว

      @@crazymk6 👍🏼👍🏼

    • @jimmytate7587
      @jimmytate7587 3 ปีที่แล้ว +2

      that is a 30 amp generator.

  • @js-wq6zy
    @js-wq6zy 2 ปีที่แล้ว

    No permit, improper device and improperly wired = no home insurance
    Your water heater is probably around 2.5- 4KW all by itself, obviously it shouldbe switched off.

  • @robertlamb3053
    @robertlamb3053 3 ปีที่แล้ว

    Does the predator have a 50amp hook up?

    • @JayMaxWrench
      @JayMaxWrench  3 ปีที่แล้ว +1

      Unfortunately it’s 30 amp

    • @shanew7361
      @shanew7361 3 ปีที่แล้ว

      @@JayMaxWrench That sucks

    • @crazymk6
      @crazymk6 3 ปีที่แล้ว +1

      @@shanew7361 Well, the running watts for this generator is 7,600. So really it would only utilize a 32 Amp plug. (7,600 watts/240 volts). So the 9500 watts it puts out, is only for a few seconds. So the 50 amp outlet would be overkill anyway, since the generators breaker would pop at anything over 32 amps.

    • @shanew7361
      @shanew7361 3 ปีที่แล้ว +1

      @@crazymk6 Good to know, ty sir 🙏🇺🇲

    • @joemeyer2726
      @joemeyer2726 2 ปีที่แล้ว

      Pharrell kit for 50 amp 240 volt

  • @LeaderOfPlanets
    @LeaderOfPlanets 3 ปีที่แล้ว

    Has your predictor generator ever been rained on?

  • @TelecasterRon
    @TelecasterRon 3 ปีที่แล้ว +1

    I do understand how people that don't understand Electrical get suckered into misleading claims. At best your Generator Inverter will be equel to about 3 15 amp circuits or 2.5 20 amp ones. If you can run a house on 9.5 kw you must live in a camper. Sorry but that is misleading 40 amps and you inverter is toast before long under even that condition. Maybe you honestly think you can run a home on a 40 amp circuit. Nope. sorry but some people think you are serious. E/IR for DC will get you close. voltage x current gives wattage. hello.

    • @CL-gq3no
      @CL-gq3no 3 ปีที่แล้ว +1

      I live in a 2000 sqft home in central FL and my home almost never uses more than 10kW at any given time. So other than startup currents from the HVAC system (which he addressed with the MicroAir), I would have to be pretty careless with energy consumption to overload that generator even with my normal routine. During a power outage I wouldn't be firing up the spa heater, dishwasher, dryer, etc. without shutting other loads down first. I think in the context of running your home on a generator, it goes without saying that we are talking critical loads and energy conservation. In FL during the summertime it could be argued that HVAC is a critical load so this video can serve as a good reference point for a lot of people.

    • @TelecasterRon
      @TelecasterRon 3 ปีที่แล้ว

      Under a 10kw load it wont last long. I spent much time in Cocoa Beach and the Cape. You can do it with Solar There for sure if they are ridged mounts and redundant systems. Most people are so disappointed when they find how feeble it really is.

    • @CL-gq3no
      @CL-gq3no 3 ปีที่แล้ว +1

      ​@@TelecasterRon, this is for emergencies like power outages caused by hurricanes. People run their homes on smaller generators than this in those circumstances. He only needs lighting, refrigerator, and the HVAC to be in good shape during an emergency. Nowhere near 10kW.

    • @TelecasterRon
      @TelecasterRon 3 ปีที่แล้ว

      YES BUT IT IMPLIES RUNS HIS WHOLE HOUSE. I BROUGHT BACK RESORTS AFTER GENE, FRANCIS, IVIN so I am very much aware of a need for power. Just you cannot mislead people about power as the SOLAR and Generac people do. OK it is equel to a wall receptacle. Just say it don't mislead people.

    • @dmdx86
      @dmdx86 2 หลายเดือนก่อน

      Sorry but I missed the part where he was trying to sell you on anything. You seem excessively butthurt about this for no reason.

  • @2507gs
    @2507gs 2 ปีที่แล้ว

    This is an illegal install though. You need to have an Interlock!

    • @fattysgarage1754
      @fattysgarage1754 2 ปีที่แล้ว

      Under what statute exactly and who will arrest him for this illegal install?

    • @davidegan3280
      @davidegan3280 2 ปีที่แล้ว

      What's going to happen if you accidentally leave the main on and the power comes back on, I guess that's why you get the harbor freight extended warranty

  • @elcaballoloco7288
    @elcaballoloco7288 3 ปีที่แล้ว

    Is dangerous don,t put a Interlock or a manual transfer switch. You could suffer a short circuit

  • @JohnDoe-es5xh
    @JohnDoe-es5xh 3 ปีที่แล้ว

    nice generator, but the excessive noise is inacceptable

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @donabele1243
    @donabele1243 2 ปีที่แล้ว +1

    Great information about the Easy-Start and the Predator. BUT, your video shows exactly how to kill a lineman! You should NEVER have a generator wired into your panel this way. If you (or someone else) does not cut the mains first, your generator will push electricity back through the lines supplying your house and down the lines. A generator interlock isn't expensive and is easy to install. In most (if not all) locations, it is REQUIRED.

  • @SkyHawk2729
    @SkyHawk2729 3 ปีที่แล้ว

    My gen doesnt rev higher when i flip the switch? Any idea why?

    • @The_Happy_Aviation_Enthusiast
      @The_Happy_Aviation_Enthusiast 3 ปีที่แล้ว

      ⚠️Please don’t forget to follow the generator safety tips:
      All generator safety rules need to be followed carefully whenever you use your portable generator. This is a reminder.
      1) KEEPING OTHERS SAFE: Please do not allow an unqualified person or your children to operate and service the portable generator. Just because some manuals don’t say that doesn’t mean it’s safe. That is important against the generator safety rules. We also need to be keeping an eye on our children too. You need to make sure that your children are not playing near the portable generator especially when it’s running so they won’t get electrocuted. Generators pose electrical risks and they can be hot during an operation. Please keep your children away from the portable generator at all times. It is important to keep our children safe especially our little ones. Be aware of all the hazards.
      2) WHERE TO RUN YOUR GENERATOR: Some people use their portable generators indoors which increases the risk of carbon monoxide poisoning. It’s important to have a carbon monoxide if you have a gas generator. Never ever use your generator indoors even if your doors and windows are open and even in the garage is not safe to use a portable generator. Not even at your porch and your deck. It is never safe to use your generator indoors and in enclosed areas of your home. Your generator needs to be 15-20 feet away from your house.
      3)🔥FIRE HAZARDS: Never refuel your generator while it’s running. You need to let your generator cool off before refueling it and before storing your generator. Never overload your generator too. Never ever back feed your generator. You should never plug your generator into a wall outlet. Also never store propane tanks indoors. Please keep flammable things away from the generator as well and please don’t smoke cigarettes near the generator. Having a fire extinguisher next to the generator is also important against the generator safety rules.
      4) GENERATOR OPERATION: make sure your hands are dry before touching the generator. Never use your generator in wet conditions. Don’t let your generator get wet. You need a generator tent if you need to use your generator during wet weather. Please don’t wear loose clothes when operating the generator. Turn on your generator before plugging in appliances. Use the right cord for your generator. Please do not use worn out cords.
      th-cam.com/video/I1jT3ANENvI/w-d-xo.html and here is a video more about keeping others safe when using generators
      Hope this helps. Everything that is said about generator safety should not be ignored to avoid hazards.

  • @franklin051579
    @franklin051579 3 ปีที่แล้ว

    🙌🏻🙌🏻🙌🏻

  • @apglass2154
    @apglass2154 3 ปีที่แล้ว +1

    Please ground your generator. It's a safety Plath.

    • @bubbatime
      @bubbatime 3 ปีที่แล้ว

      The 4 prong cord has a ground in it. It grounds the generator.

    • @johnclyne6350
      @johnclyne6350 3 ปีที่แล้ว +1

      Actually Ap Glass is referring to a separate ground from your case to a ground wire running to a driven ground nearest your generator. You’d be surprised if your generator was running a while how much static the case will build up. It might be enough to shock someone? Your relying on a house ground that will have several connections to it. The house ground may not work as well now with the additional load you have added since the house was built? Always get in the habit of checking your grounds every so often. Other utilities namely CATV/ phone tie their ground into yours instead of installing their own ground rod. They may have weakened your ground or overloaded the wire size or connection?

    • @apglass2154
      @apglass2154 3 ปีที่แล้ว

      John is correct grounding the case is very important most generators have a post to attach a ground to that has three lines running horizontal top one being the longest the bottom one being the shortest that is a schematic symbol for an earth ground.

  • @thefruitshowstheroot7844
    @thefruitshowstheroot7844 3 ปีที่แล้ว

    It's too loud. Couldn't hear what you were saying 😣

  • @mikedavid7168
    @mikedavid7168 6 หลายเดือนก่อน

    Get 50amp generator