Transformer Differential Protection | Differential Relay| Hindi

แชร์
ฝัง
  • เผยแพร่เมื่อ 22 ธ.ค. 2024

ความคิดเห็น • 187

  • @kameshwarmehta5507
    @kameshwarmehta5507 2 ปีที่แล้ว +2

    aapka batane ka tarika bilkul hi lajwab hai,thank you very much

  • @ruchitprajapati
    @ruchitprajapati 2 ปีที่แล้ว +1

    Superb video. And your knowledge is great. This video is best explanation in TH-cam

  • @Ajay_Aj386
    @Ajay_Aj386 9 หลายเดือนก่อน

    Best video for understanding differential relay... thank you Abhishek ji

  • @Best_Parts102
    @Best_Parts102 ปีที่แล้ว +1

    Agor delta delta and star star xmer ho toh CT ka kaya connection hoga???? Plz reply

  • @tejaskhalasi1009
    @tejaskhalasi1009 3 ปีที่แล้ว +4

    Sir IR test in transform kese karte hai...it's value?

  • @hemantkumar9345
    @hemantkumar9345 ปีที่แล้ว

    Sir aaap bahot achhe se explain krte ho ......

  • @dasaraja1976
    @dasaraja1976 10 หลายเดือนก่อน

    Ur style i like bcoz crystal clear idea given by u

  • @manoharborvadkar2107
    @manoharborvadkar2107 3 ปีที่แล้ว +2

    Thanks sir for consideration of my request and well explained of transformer differential protection, Now I am waiting for transformer testing videos

  • @shivenduanand9657
    @shivenduanand9657 11 หลายเดือนก่อน +1

    Amazing Experience watching your well described video

  • @basicelectrical3655
    @basicelectrical3655 3 ปีที่แล้ว

    Veer ji Jrck load kya hota h

  • @k.p.prajapati3063
    @k.p.prajapati3063 3 ปีที่แล้ว +2

    Very informative video sir

  • @navalkishore9845
    @navalkishore9845 3 ปีที่แล้ว +2

    Are Restraining coil & tripping coil inbuilt in advance numerical relay or relay itself manage all function? Kindly explain sir

  • @ateeqkhan09
    @ateeqkhan09 ปีที่แล้ว +1

    according to the transformation ratio current will be different on of windings in power transformer ..how do you select CT for it?

  • @suvendusahoo7905
    @suvendusahoo7905 ปีที่แล้ว

    Sir transformer ko hum static divice bolte hai to phir tap changer Kay hai ?
    Please sir explained me.

  • @princechauhan6872
    @princechauhan6872 5 หลายเดือนก่อน

    ek question ye h ki jb hmra transformer ka kaam hi yhi hai HT to LT convert yani jb volatge dono side alg alg hoti hai toh current b dono side alg alg hoga toh isme diffrence toh rhega hi fir dono side k bich diffrence toh rhega toh ye work kaise krega

  • @ganeshmalakar14
    @ganeshmalakar14 3 ปีที่แล้ว +3

    Sir Transformer ki primary aur Secondary me normal conditions me Voltage Different hone par Current bhi different hogi to operating Coil me Zero Current kaise flow hogi??

    • @mohibbullahniaz5349
      @mohibbullahniaz5349 3 ปีที่แล้ว

      Bcz CT connection also changed..

    • @dinabandhukhuntia9077
      @dinabandhukhuntia9077 2 ปีที่แล้ว

      Aux ct lagate hai for balancing current.
      Also you should know about spill currently

  • @pavankumar-ey3bw
    @pavankumar-ey3bw 3 ปีที่แล้ว +1

    33kv manual trip ckt what is the uv blocking.....? Please give me replay

  • @awadithya87
    @awadithya87 2 ปีที่แล้ว +1

    Hai sir I have a dought in restraining coil.
    When fault occurs, fault current surpasses through restraining coil as u said.
    Can I assume, restraining coil opposes sudden change in current for few sec then after it allows that current to flow in relay operating coil

  • @haldharchouhan007
    @haldharchouhan007 3 ปีที่แล้ว +1

    Please explain why use opposite ct use

  • @arbinkafley9168
    @arbinkafley9168 3 ปีที่แล้ว +1

    Sir.
    If there is short circuit in one feeder panel is there chances of getting trip of other panel in a company.

  • @ayushpandey7187
    @ayushpandey7187 2 ปีที่แล้ว

    sir Transfomer normal operation me bhi to primary and secondary me current different hota hi power constant rakhne ke lie.....tab operating coil me current kyu ni flow hota

  • @dars_hit4917
    @dars_hit4917 ปีที่แล้ว

    Sir agar hamara connection Y-Y or ∆ - Y hoga to hamara operating & restarting coil hai usme koi change aayega kya ???
    Or circuit diagram me koi change ho sakta hai kya ???

  • @bhaveshprajapati5377
    @bhaveshprajapati5377 3 ปีที่แล้ว

    Sir Transformer me normal condition me HV LV ka current equal hota to nahi hai.
    To bhi relay kaise work karta hai....?

  • @gamingworldofAbdullah_8787
    @gamingworldofAbdullah_8787 ปีที่แล้ว

    Where this restating coil installed. In transformer or in relay. Plz confirm.

  • @zainulkhan881
    @zainulkhan881 3 ปีที่แล้ว +6

    Pls. describe "Distance Protn.relay" & different b/w switched/Non switched distance relay.

  • @muhammadkhalid7129
    @muhammadkhalid7129 ปีที่แล้ว

    Sir. Do u have any video on Percent Differential Relay???

  • @Ali__tahir
    @Ali__tahir ปีที่แล้ว

    u said restraining coil will stop inrash current or change in voltage/current due tap change ……..wont it stop the difference of current from CTs as well ? explain

  • @gulfamhasmi
    @gulfamhasmi 10 หลายเดือนก่อน

    superb Yaar super se bhi upper very nice conclusion

  • @maheshnadgire
    @maheshnadgire ปีที่แล้ว +1

    Nice explanation

  • @shaikkhaja2821
    @shaikkhaja2821 2 ปีที่แล้ว

    Tq so much sir given good information. Sir I have doubt ht motor my differential relay lagate hy our us ke saat our ak relay bi lagaya jaata a donu my kya difference hy baatya na sir please.

  • @prasadprs7501
    @prasadprs7501 2 ปีที่แล้ว

    bro i have a dout transforer output means primary voltage is diffrent from secondary voltage but diffrential relay works on diffrence of magnitude so please explain if u know?

  • @victorhigh7896
    @victorhigh7896 2 ปีที่แล้ว +1

    Very well explained, thank you so much dear friend 😊🙏🙏👌👌👌

  • @k.p.prajapati3063
    @k.p.prajapati3063 3 ปีที่แล้ว +1

    Ir, Isc, Im, means kya hai jo realy timer and contactor leka hota hai

  • @Rajeshkumar-ds3sb
    @Rajeshkumar-ds3sb 3 ปีที่แล้ว

    Sir kya ye connection sabi relay par ho sakte h

  • @sgtechnicalm1322
    @sgtechnicalm1322 3 ปีที่แล้ว +2

    sir, why smps posetive terminal is ground? (plese make a video).

  • @amp_001
    @amp_001 2 ปีที่แล้ว

    what is the ratings of transformer in your example

  • @ajitroy1990
    @ajitroy1990 3 ปีที่แล้ว

    Sir apne video me kaha CT ratio same rakhna hai it means secondary same rahega par ye to jaruri nahi hai na ki primary wala v same rahe?

  • @ayushpandey7187
    @ayushpandey7187 2 ปีที่แล้ว

    sir normal transformer operation me bhi to primary and secondary me current different hota hi power ko constant rakhne ke lie.....tab differential relay ki operating coil me current kyu ni flow hota

  • @sumantsharma7815
    @sumantsharma7815 2 ปีที่แล้ว

    What happens when i use 300/1 CT in primary side and 800/5 CT in secondary side in 15 MVA X'MER then how diffrntial protection works. Pls. ans

  • @mrs.mukesh1938
    @mrs.mukesh1938 7 หลายเดือนก่อน

    Sir genrator differential protection me circulating current kya h

  • @srijansingh9834
    @srijansingh9834 2 ปีที่แล้ว

    Sir jb dono side star configuration ho to ct ko kaise connect kre

  • @sinodchauhan2464
    @sinodchauhan2464 2 ปีที่แล้ว

    Sir my question delta side star ct and star side delta ct connection kiya gya hai resion phase shifting and tap changing ke karan current flow hota usko avid karne ke liye
    Sir uske liye to resitring coil lga hai to usko avid kar sakta hai.
    Please reply

  • @hemantshukla2314
    @hemantshukla2314 3 ปีที่แล้ว +3

    Settings kaise krte hai differential relay ki

  • @learnelectrical7031
    @learnelectrical7031 3 ปีที่แล้ว +1

    Sir plz make a video on phase shift ,phase angle ,phase squence and sooo on plz

  • @mrityunjayshrivastav9832
    @mrityunjayshrivastav9832 21 วันที่ผ่านมา

    Sir pilot Wires kya Hota Hai??

  • @06.amitkumar17
    @06.amitkumar17 3 ปีที่แล้ว

    Sir transformer me incoming current and outgoing current same kaise ho Sakta hai ..

  • @jaleshwarsingh2032
    @jaleshwarsingh2032 3 ปีที่แล้ว +1

    Sir plz make video on directional relay

  • @dharampalsingh-sr3hs
    @dharampalsingh-sr3hs 2 ปีที่แล้ว

    Distance protection relay fault ka distance ko kasea sense krti h

  • @indronildey7753
    @indronildey7753 2 ปีที่แล้ว +1

    How the restraining coil differentiate between high inrush current and fault current.

    • @itsbarki3656
      @itsbarki3656 7 หลายเดือนก่อน

      fault current has very high magnitude , restraining coil may opppose , but its magnitude is very , some current pass to operating coil, and differential relay operate

  • @soumitra943
    @soumitra943 3 ปีที่แล้ว +1

    Sir please make a video on different types of power grid connection

  • @mudasirshahid3839
    @mudasirshahid3839 5 หลายเดือนก่อน

    Please clear
    You use 100/1 CT
    When 1000 amp flow then CT , Saturate , ct output only 1 amp

  • @arvindkumarrajput8909
    @arvindkumarrajput8909 3 ปีที่แล้ว +3

    Up to how much KVA differential relay used in transformer

  • @akshaypatel9997
    @akshaypatel9997 3 ปีที่แล้ว +4

    Sir,
    My question is how to select CT ratio for primary and secondary side for differential relay..

    • @electricalwithabhishekjoshi
      @electricalwithabhishekjoshi  3 ปีที่แล้ว +1

      Watch my video on how to select CT.

    • @shrikantsathe371
      @shrikantsathe371 3 ปีที่แล้ว +3

      First consider full load current of HV winding of transformer. Keeping 20% as spare current value, next rounded off CT ratio to be selected. Say 80 ampere is current of transformer then select 100 ampere as primary current of the CT. Secondary CT current to be selected as per input current of the differential protection relay. Suppose relay input current as per manufacturer of the relay is 1 ampere, then CT ratio for HV Side CT would be 100 / 1. Now finalise LV side CT ratio as per corresponding current of HV and LV winding of the transformer. Suppose for example LV transformer current is 800 ampere, then select 1000 ampere as primary CT current of LV side. Now, we have to decide secondary current of this CT. First understand connections of HV & LV winding of the transformer. If both are either Star or Delta connected i.e. HV winding & LV winding both are Star connected (Star - Star) then 1000/1 ratio for LV winding is suitable. Considering connections of differential relay wires which are called pilot wires; during normal operation of the transformer from 0 load to full load, current shall be equal from both the CT's at any point of loading is the fundamental requirement. Moreover, in case of differential protection CT's, the class of CT's shall be class PS, where CT magnetising current saturation is studied and knee point voltage is taken into consideration. (If someone is using Microprocessor based differential protection relay, then class of CT requirement is derived from the relay input requirement as per catalogue of the relay. sathe1963@gmail.com Thanks!

  • @farazkhan7176
    @farazkhan7176 3 ปีที่แล้ว

    Now CT star mea hoti han or compensation relay apne software mea karti ha

  • @vishalprakashthakur8494
    @vishalprakashthakur8494 3 ปีที่แล้ว

    Sir my question please clearify me two generator running in parallel one of the generator KW fluctuating what may be the reason

  • @omkarkannaujiya9037
    @omkarkannaujiya9037 7 หลายเดือนก่อน

    Hello sir
    As you said for CT secondary the current flow is opposite to the CT primary current... please make any video what's the logic behind it or reply in text .
    Hoping you will respond

  • @Indiabhanu
    @Indiabhanu ปีที่แล้ว +1

    In normal scenarios also current flows from both CTs. Why then differential relays don't act? Pls answer the query.

  • @VikasKumar-dl8wk
    @VikasKumar-dl8wk 7 หลายเดือนก่อน

    Sir HT me CT ratio kaise choose kare

  • @nitino8
    @nitino8 2 ปีที่แล้ว

    Dear sir
    If fault is happen outside the transformer I.e CT than what happen ....
    Due to CT saturate relay is operated or Not?

  • @umakantjadhav3110
    @umakantjadhav3110 3 ปีที่แล้ว +14

    In case of distribution transformer, current in the primary (high voltage) winding is always less than the current in the secondary winding. CT raio of primary & secondary winding always differ. In your explanation, you have shown same CT ratio for both windings. Besides, even in healthy condition also current in primary CT shall always be less than the current in secondary CT. Then the difference current will flow through the relay coil & shall trip the transformer. This is what I have predicted. Please throw more light on this matter to make me understand function of this relay correctly.

    • @yubrajchimoriya2761
      @yubrajchimoriya2761 3 ปีที่แล้ว

      ..

    • @muhammadashhad2146
      @muhammadashhad2146 2 ปีที่แล้ว

      Relay setting is always kept higher then the normal Spill Current which is due to Differnce in CT Ratios and Lead Leangths.

    • @pramodpgc
      @pramodpgc 2 ปีที่แล้ว

      In conventional relay there is provision of matching CT in both side. And now a days in numerical relay no need of matching CT, there can be feed setting.

    • @sm-ph8uf
      @sm-ph8uf ปีที่แล้ว

      thanks

    • @pawankumar-nb5ce
      @pawankumar-nb5ce ปีที่แล้ว

      @Umakant yeh doubt mujhe bhi pareshan kar Rahi hai. Agar kuch clear ho to please reply

  • @omprakashsingh-cl4jl
    @omprakashsingh-cl4jl 3 ปีที่แล้ว +2

    Plz. vector surge relay per video banaye..

  • @digambarkhokalepatil1945
    @digambarkhokalepatil1945 3 ปีที่แล้ว +1

    Sir,
    Please Make video on 2 nd ,3rd ,4th harmonic filter bank in SVC.

  • @PareshRS-h7e
    @PareshRS-h7e 2 หลายเดือนก่อน

    Kya bolu ab. Tranformer hV aur LV side ka current thodi hi match hota he. Lv side me current high rhta he distribution tf me aur hv side me kam rahta he. Aur dono side same current rating ki CT kaise lg sakti he

  • @asifuzzamanhridayhriday1400
    @asifuzzamanhridayhriday1400 ปีที่แล้ว

    Thank you sir , i have a question to you . here you showing that delta side senodary point star connection and star side secondary point delta connection , why you use this system...? but our companies transformer are winding is majority percent transformer are HT side Delta and LT side Star connection . and we HT or LT bushing CT s both are secodary point connected always star. it fully different your drawing. and you showing HT n LT side CT ratio same is it possible...? plz plz plz plz sir explain me my question .

  • @A70B07
    @A70B07 ปีที่แล้ว

    Agar normal condition meh sirf ct se current flow hoga to kab transformer meh current jayega. Aur kiu normal meh primary and secondary meh cureent same ata hain? Voltage level to different ayega to fir cureent same kiu

  • @aashishaikh4867
    @aashishaikh4867 3 ปีที่แล้ว +1

    Nicely explained sir, Thank You sir

  • @shreemadbhagvadgeeta9671
    @shreemadbhagvadgeeta9671 2 ปีที่แล้ว

    Really very useful video.

  • @deepaksisodiya9474
    @deepaksisodiya9474 3 ปีที่แล้ว +1

    Good afternoon sir,
    Sir please describe my doubtful question, i am stand centre of Transmission line distance how will be identify the direction of the power generation substation and any incoming substation?

  • @surendrakverma555
    @surendrakverma555 2 ปีที่แล้ว

    Very good. Thanks 🙏🙏🙏🙏

  • @shahbazrehman7211
    @shahbazrehman7211 2 ปีที่แล้ว

    App ki new video kab aye ge

  • @satyaranjanbarik5702
    @satyaranjanbarik5702 2 ปีที่แล้ว

    Please make a video on 2 phase lighting transformers

  • @mallikarjunreddy5063
    @mallikarjunreddy5063 3 ปีที่แล้ว +1

    Please explain about phase shift concept

  • @haldharchouhan007
    @haldharchouhan007 3 ปีที่แล้ว +1

    Superb sir

  • @rajendrapaliwal239
    @rajendrapaliwal239 2 ปีที่แล้ว

    Sir Please make vidios on transformer testing ,IR values

  • @vinodshah5120
    @vinodshah5120 2 ปีที่แล้ว

    Superb explanation sir

  • @tarakparai4058
    @tarakparai4058 9 หลายเดือนก่อน

    Thanks 🙏🙏🙏🙏👍👍👍👍 Hamara side me tap chang time same problem hua thaa.

  • @tejaskhalasi1009
    @tejaskhalasi1009 3 ปีที่แล้ว +3

    Sir, tap Changer kaha lagate hai...why? Kis Transformers me lagta hai?

  • @mayurramdham3051
    @mayurramdham3051 2 ปีที่แล้ว

    Best ever explained

  • @sagargalani5945
    @sagargalani5945 2 ปีที่แล้ว

    How many CT are being used in Differential relay protection of transformer?

  • @gajadharkushwaha886
    @gajadharkushwaha886 2 ปีที่แล้ว

    Sir 11kv/690v converter transformers ke bare bataye

  • @shilwantsingh89
    @shilwantsingh89 3 ปีที่แล้ว +1

    Doubt clear .thanks

  • @arunjoshi2089
    @arunjoshi2089 3 ปีที่แล้ว +2

    Well explained.

  • @mitubarik3361
    @mitubarik3361 3 ปีที่แล้ว +1

    Well explained sir

  • @sandeepsandy709
    @sandeepsandy709 3 ปีที่แล้ว +1

    Sir speed control of a motor both AC & DC

  • @SitaramSamota-n6j
    @SitaramSamota-n6j ปีที่แล้ว

    sir,
    Electrical saving per bhi video banvo

  • @vidyasagaryadav3881
    @vidyasagaryadav3881 2 ปีที่แล้ว

    Sir please explain transformer stability test..

  • @krishnaRajput-mf4dq
    @krishnaRajput-mf4dq 3 ปีที่แล้ว

    Sir please make a vedio how to measured transformer winding temperature

  • @anmolpawar3149
    @anmolpawar3149 2 ปีที่แล้ว

    Fabulous and fantastic sir 🙏🙏

  • @sanjeetgupta3997
    @sanjeetgupta3997 2 ปีที่แล้ว

    No word sir 🙏🙏🙏

  • @digvijaymohite63
    @digvijaymohite63 ปีที่แล้ว

    nice explanation of Diffrential protection of tramsformar

  • @dhetolangthasa169
    @dhetolangthasa169 ปีที่แล้ว

    Awesome 👍👍👍

  • @ajaysinhzala9624
    @ajaysinhzala9624 3 ปีที่แล้ว +1

    In normal condition both side of transformer same magnitude of current is not flowing because HT side and LT side current are not same in transformer.

  • @surekhagaikwad5195
    @surekhagaikwad5195 2 ปีที่แล้ว +1

    Hello Brother kindly use blank white paper and bold pen/ dark pen. Thankyou so much..

  • @davetejas3728
    @davetejas3728 3 ปีที่แล้ว

    Please make video of oltc control diagram

  • @arpitdhiman4021
    @arpitdhiman4021 2 ปีที่แล้ว +1

    Sir please aap , trip circuit supervision relay & restricted earth fault relay per video bnaye.

    • @electricalwithabhishekjoshi
      @electricalwithabhishekjoshi  2 ปีที่แล้ว +1

      Arpit, restricted earth fault relay pe video banaya hai. Drawing ke sath explain kiya hai

  • @ShauryaInvincible
    @ShauryaInvincible 2 หลายเดือนก่อน

    Are current kaise same rhga transformer me step up or step down krne m

  • @himanshutiwari3219
    @himanshutiwari3219 3 ปีที่แล้ว

    Very good explanation

  • @vivekkadam1992
    @vivekkadam1992 3 ปีที่แล้ว

    Hello sir, please make video on summation CT

  • @Hemanth2787
    @Hemanth2787 3 ปีที่แล้ว

    Wich class of CT used fr REF and differential relay

  • @navalkishore9845
    @navalkishore9845 3 ปีที่แล้ว

    Sir make a video on distance protection relay in our line protection.