How to diagnose, replace diverted, valve pressure sensor, auto air vent on Vaillant boiler
ฝัง
- เผยแพร่เมื่อ 21 พ.ย. 2024
- How to diagnose / replace /diverted valve / pressure sensor (F75) / auto air vent/ on a single boiler, Vaillant Eco tec boiler step by step
This video is for GAS SAFE ENGINEERS only, always follow manufacturer instructions.
Before to start any work on gas appliance isolate the power, turn off the gas and the waters.
Diverted valve is leaking, it's built up limescale on auto air vent and pressure sensor
Download manual
www.vaillant.c...
2. Remove front cover
3. Isolate the flow and return valves
4. Drain the boiler
5. Leave open the drain point
6. Remove air inlet pipe
7. Remove pressure sensor and replace for new one
8. Remove and replace auto air vent
9. Remove and replace pressure sensor
10. Close the drain valve and open the flow and return valves
11. Re-pressurise the heating system till 1 - 1.5 bar.
If you need more information you can find on my channel each part replacement individual.
Very nice
Brilliant
Brilliant video 🎉🎉
Excellent video, big help. Thanks mate . I was wondering if you need to purge with P. 00 program after working on the boiler?
You're welcome. The heating will purge by auto air vent, but you can run the program.
@@bheating thanks mate ,really appreciate that
appreciate for sharing your experience
Brilliant video thanks
Would a leaking aav cause pressure drop ? Thanks in advance
Yes
Nice one.