    Great video, but what if you do not have air mixing, no fresh air intake and all recirculated air are all the three sensible heat factor would be the same to get the ADP?, since I'm using Fan coil unit not a air handling unit.

    • @saurabhaggarwal2776
      @saurabhaggarwal2776  8 หลายเดือนก่อน

      Nice thought, but if only recirculated air is used and room inlet point 3 remains same you need to humidify the air to reach point 3(as it is desired room entry condition) this will lead to different Sensible heat factor lines. Also keep in mind 100% recirculated air will decrease Oxygen content in air per circulation and if conditioned space have humans or living organisms they will be suffocated.

  • @krishnachaitanya1969
    @krishnachaitanya1969 2 ปีที่แล้ว

    Sir, @13:33 - i) Heater is for controlling the Rh in Monsoon; ii) to help us in finding out ADP.. add some sensible heat in worst scenario.

  • @krishnachaitanya1969
    @krishnachaitanya1969 2 ปีที่แล้ว

    Very nice explanation Sir.. Please mention the above are valid for which areas. For India we have one more season.

  • @srinivasmittapally258
    @srinivasmittapally258 3 ปีที่แล้ว

    Nice explaination sir...