PROBLEM ON COOLING LOAD ESTIMATION | DESIGN OF AIR CONDITIONING SYSTEM | CONCEPT OF RSHF GSHF ADP

แชร์
ฝัง
  • เผยแพร่เมื่อ 1 ต.ค. 2024
  • An air-conditioned auditorium is to be maintained at 27°C dry bulb temperature and 60% relative humidity. The ambient condition is 40°C dry bulb temperature and 30°C wet bulb temperature. The total sensible heat load is 100000 KJ/hr. and total latent heat load is 40000 KJ/hr. 60% of the return air is recirculated and mixed with 40% of make up air after the cooling coil. The condition of air leaving the cooling coil is at 18°C.
    Determine a) Room sensible heat factor
    b) The condition of air entering the auditorium c) The amount of makeup air
    d) Apparatus dew point e) By pass factor of the cooling coil. (DEC 2023)
    VIDEOS ON PSYCHROMETRY PROCESSES
    1. • NUMERICALS ON PSYCHROM...
    2. • NUMERICALS ON PSYCHROM...
    3. • NUMERICAL ON ADIABATIC...
    4. • NUMERICAL ON PSYCHROME...
    5. • PROBLEM ON COOLING LOA...
    VIDEOS ON VCR CYCLE
    1. • A NUMERICAL ON VCR CYC...

ความคิดเห็น • 6

  • @chouite2010
    @chouite2010 หลายเดือนก่อน

    RSH=100000/3600=27.78kW

  • @ShubhamBhardwaj00001
    @ShubhamBhardwaj00001 4 หลายเดือนก่อน +1

    Best sirji

  • @zunaidalam5971
    @zunaidalam5971 28 วันที่ผ่านมา +1

    Return air and outside air mix before the coil not after the coil

    • @bhaujaude374
      @bhaujaude374 19 วันที่ผ่านมา

      No, as per the Numerical return air mixes with Fresh air after the coil

  • @DMERaushanRaj
    @DMERaushanRaj 5 หลายเดือนก่อน

    Nice...❤