25 NEC Electrical Exam Prep Questions with Full Explanations Volume 4

แชร์
ฝัง
  • เผยแพร่เมื่อ 12 พ.ย. 2024

ความคิดเห็น • 26

  • @okusitinotahitua1020
    @okusitinotahitua1020 9 หลายเดือนก่อน +3

    the best of all... thank you very much may God help u and bless you for your sharing your knowlegde

    • @ElectricalCodeCoach
      @ElectricalCodeCoach  9 หลายเดือนก่อน +1

      You are very welcome. Thank you for the comment. God is good!

  • @blazero2169
    @blazero2169 ปีที่แล้ว +2

    I love your style thank you 🙏🏽

  • @robainad
    @robainad 2 ปีที่แล้ว +5

    What size copper GEC would you select for a 400A service with 500kcmil main AL service conductors? You said 1/0. I think it should be #2. Did I miss something?

  • @liveelectric2413
    @liveelectric2413 ปีที่แล้ว +2

    Why didn’t you do the 125% motor increase before the short circuit ground fault protection questions?? Multiple by 1.25, then multiply protective device demand factors?

    • @liveelectric2413
      @liveelectric2413 ปีที่แล้ว

      All love brother! I just wanna make sure I’m doing this right
      But from me to you, f that question! Because your 10 week program was ridiculously helpful!! And when I pass my test, you are to blame. I’m gonna schedule it in a month

    • @ElectricalCodeCoach
      @ElectricalCodeCoach  ปีที่แล้ว

      Great question! you will only do the 1.25 for motor conductors! Go get em!!!

  • @mr.fix-all
    @mr.fix-all ปีที่แล้ว +3

    what happened to that motor short circuit/ground fault 7.5 HP 230v single phase motor question? that thing got botched. the writing was on point but you were telling about a 3 ph motor at 208...

    • @FENATECH
      @FENATECH 29 วันที่ผ่านมา

      I just came across this myself and was confused and thinking I missed something. Following the text on the screen as you said seems to check out though.

  • @davidinscore1612
    @davidinscore1612 หลายเดือนก่อน

    Very helpful, thanks Coach.

  • @josueayalallanas7142
    @josueayalallanas7142 2 ปีที่แล้ว +1

    250 that 52 A4 requires ground rings to be not smaller than number two therefore the grounding electrode conductor shall not be smaller than the size used for the ground ring

    • @josueayalallanas7142
      @josueayalallanas7142 2 ปีที่แล้ว +1

      Thanks for all the info that you share, i have watched so many of your videos and helped me a lot in the field!

    • @ElectricalCodeCoach
      @ElectricalCodeCoach  2 ปีที่แล้ว +1

      You are very welcome! Let's get to it!!

  • @FENATECH
    @FENATECH 29 วันที่ผ่านมา

    Coach, the question around 30minute mark with the ground ring seems misleading. 250.52(4) states a ground ring is to be a bare copper conductor not smaller than 2 AWG, which is not a possible choice.
    Is this an incorrect question then?

  • @kendread
    @kendread 10 หลายเดือนก่อน

    Coach, 13:36 you start the question off as a Single Phase Motor 7.5 hp at 230v, but you solve the question with table 430.250 which is 3 phase and at 208 voltage.
    Is our FLC not supposed to be 40v according to 430.248? Or am I confused?
    Let's get to it.

  • @VinceBeltrami
    @VinceBeltrami ปีที่แล้ว +2

    Looking at HVAC calc, 220.82 (C) says 100% of the nameplate rating of the heat pump, but you bumped it up to 125%. Is that because of 430.22? Didn't think that was necessary for the load calc

    • @ElectricalCodeCoach
      @ElectricalCodeCoach  ปีที่แล้ว

      Disregard that 125%

    • @joseverges1955
      @joseverges1955 ปีที่แล้ว

      I was asking myself the same question. So just to be clear, according to his reply, we do not multiply by 125% and this example it’s wrong. I spent 30 minutes looking for an answer till I found this comment.

  • @deeluton86
    @deeluton86 ปีที่แล้ว

    Is this equivalent to the Florida exam?

  • @mikescott6247
    @mikescott6247 2 ปีที่แล้ว +1

    Are these LLE for Tennessee??

    • @ElectricalCodeCoach
      @ElectricalCodeCoach  2 ปีที่แล้ว

      Yes ide take this first#1 FREE Electrician Exam PREP VIDEO SERIES Electrical exam prep: th-cam.com/play/PLJokxpBhbuUc6LTyszEzt-FR7k8Tz4eMG.html

  • @mildaudiophile3879
    @mildaudiophile3879 2 ปีที่แล้ว +2

    You said round down 146.09 and the answer was 150. Did you mean round up?

    • @ElectricalCodeCoach
      @ElectricalCodeCoach  2 ปีที่แล้ว

      Good eye, its just habit, you would round down to 146 on the calculation part, but would choose the next standard size

    • @mildaudiophile3879
      @mildaudiophile3879 2 ปีที่แล้ว

      @@ElectricalCodeCoach thank you.