Ji hamne already actuator ki vidio upload ki hui hai aor use by pass aap manuel kar sakte hai ya phir agar apke pass BMS system hai to waha se 100%open ki commond de dijiye sukriya
Check the vidio Chiller oprater ko kya karna padta hai ... Link diya hai hamne aap dekh lijiye Baaki 3 vidio dekh lijiye jo maine upload ki hui hai interview ki 1. Top 10 interview questions and answers 2.top 9 interview questions and answers for dubai 3. Ahu top 7 questions and answers Ye dekh lijiye aap i hope agar apme intrest rahega to apka interview sure clear ho jayega
Set point apka around 40 to 43 digri celcius rahta hai isse kam ho jayega to chiller start nahi hoga low temp. Alarm ayega .. aor jab chiller running condition pe aa jata hai to 50 to 60 digri celcius pe chalta rahta hai ।। Sukriya
Sir Good evening Sir hm jaha job krte hai vha Chiller 1000 Tr ki hai sir ,6 Chiller hai, Aaj use start krne ke badh uska Condenser Temperature or Condenser pressure Dono high Jaa rha hai sir , Cooling tower vhi ok Condison tha , please sir kya problem ho shakta hai btaye mujhe please sir 🙏🏻🙏🏻
1. Cooling tower se air रिलीज करो ठीक से 2. Cooling tower fan check 3. Chiller ke hisab se ahu ka load kitna hai wo check karo 4. Chiller ko 80% load pe start karo pahle
👉Daily cleaning 👉 Weekly checking equipment and cleaning and all leakege 👉Month check all इलेक्ट्रिक terminal 👉 6 month oil testing and filter checking 👉1year filter change all electrick terminal check and oil level chcek proper all leakege check If Condenser approch going high so descaling the condenser Sukriya
Sir low lube oil pressure ka alam jo iss chiller pe jo aaya tha woh kis wajeh se aaya tha aur sir Chiller over load aur chiller under load ka kya matlab hota hai ??
1. Chiller ka load check karo 2. Primery pump ka pressure check karo 3. Set point temperature check karo 4. Gas ka pressure Kya hai 👉 isi me apko reason mil jayega ..ye pahle check karo aap
My brother...here is many brothers that's don't know proper English...that's why I making vidio in Hindi language... If you have any doubt or question so it's my Instagram I'd come and here and ask your question..I'd 👉 kgufran195
Good day bro this chiller direct drive k h ya gaer box drive h ap k pass mara pass jo chiller h Trane k wo gaer drive h or ois main bhot sound ho Raha h abnormal 33000 running hours ho gai h chiller k ap ois bara main Koi advice dain
Sir please help me all questions answers 🙏🙏 R134a refrigerant ka.. Superheating Temperature? Saturation Temperature? Subcooling Temperature? R134a refrigerant Expansion valve ke bat temperature kitna hota he? & R134a refrigerant evaporator se out hone ke temperature kitna hota he? Chiller normal working condition me Suction and Discharge pressure kitna hota he? Meroko interview me pucha tha .. Mene answer nehi de paya.. Please bata dijiye sir🙏
R134a data 👉Discharge temp. 40 digri celcius 👉Condenser me temp. 30 to 35 digri celcius 👉And evaporater temp.3 to 6 digri celcius 👉Subcooling 3 to 5 digri celcius Chiller normal conditions pressure 👉Suction 37 to 40 psig 👉Discharge 110 to 120 psi Yaad rahe jab bhi koi cheej load pe jaata hai to uske parameters bhi kam jyada ho jate hai।।।। ye jo maine bataya hai ye lagbhag standard hai sukriya 🙏
Bahut khub bhai bahut kam time me bahut achchha flowers ho gaya apka iska resion apki awaj or samjhane ki idea
Ji bahoot sukriya apka ... Ye sab aplogo ka प्यार 🤲💐 aor ap logo ki duay hai ... 💐💐
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Great sir❤
Thank guru ji
Mast knoledge
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Nice 👍 sir
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Sir VGD ka work kya hai yk chiller me
🌹🌹❤️❤️❤️🌹🌹
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Excellent
Thank you 💐
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Wah guru ji
Thank you 🙏💐
Sir aap jaunpur se hai kya
रायबरेली 🤗
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
✋✋✋✋✋👌👌👌👌👌
Sukriya
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Sir Trane ka ya carrier chiller ya koi or water cooled chiller ke parameters same hon gi York ki tarah
Ji ha bilkul any chiiler parameter to same in water cooled typ chiller 👍
Sir ..plz help 🇦🇪....trance chiller rtac400 model low refrigerant temprature aane se kiya problem ho sakti ..or kiya check krne pdenge
First check the ... Set point temp..
Second chcek primery pump pressure
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Sir aap apna name bataye pls sir
Aap to hum logo ka markdarshn hai
Aap ko hum logo ki dua lagi gi sir
Inshallah
Aap bahut achha revise karwa rahae hai
Ji bahoot sukriya apka ....
Ye mera instagram id hai aap ispe contact kar sakte hai 👉 kgufran195
@@c4chiller9984
Ji jarur
Actuator ka video banaye or actuator bypass kaise hota hai ye bhi bataye sir plzz
Ji hamne already actuator ki vidio upload ki hui hai aor use by pass aap manuel kar sakte hai ya phir agar apke pass BMS system hai to waha se 100%open ki commond de dijiye sukriya
Chiller water me konsa pipe use kiya jata hai?
@@Myamazingdiary G.I. ki pipe
@@c4chiller9984 2 way valve and 3 way valve ki video banaye full details me kaha install hota hai aur work kya hota hai kyun use karte hain?
@@Myamazingdiary Ok ji jaise hi time milega ham upload kar denge sukriya
bhai interview m chiller opeator ka, kaam puche ga toh kya kya batana hoga plz guide me
Check the vidio
Chiller oprater ko kya karna padta hai ... Link diya hai hamne aap dekh lijiye
Baaki 3 vidio dekh lijiye jo maine upload ki hui hai interview ki
1. Top 10 interview questions and answers
2.top 9 interview questions and answers for dubai
3. Ahu top 7 questions and answers
Ye dekh lijiye aap i hope agar apme intrest rahega to apka interview sure clear ho jayega
Oil pressure PSID me Yahan so kr Raha hai humare chiller m kpad m so karta h Kya difference h bato
100 kpa me 14.5 psi hota hai .. apke display pe 220 to 240 tak kpa sho karega
Sir set point kya hota hai.
Aur kitna hona chahiye .
Agar temperature ziyada ya Kam hojaay set point se , tu kya hosakta hai
Set point apka around 40 to 43 digri celcius rahta hai isse kam ho jayega to chiller start nahi hoga low temp. Alarm ayega .. aor jab chiller running condition pe aa jata hai to 50 to 60 digri celcius pe chalta rahta hai ।। Sukriya
Centrifugal chiller ko service mode mai chlne se Kya hota hai
Kuch extra data ke liye .. jo normal mode pe show nahi karta ..👍
@@c4chiller9984 kuch detail mil skti hai iski apse
Ok we try
Sir screw comp me v 40 se uper temp hoga tave start hoga
👍👍👍
Sir ye kriscool chhillet me unsafe oil pressure trip alarm ye problem ko kaise slow kre
ek baar chiller ko shud oun karke wapas se start karo aap
@@c4chiller9984 usse bnd to hua kuch der k liye pr phir vhi problem dikha rha hai
Phir bhi thik nhi hua sir usse to bnd hua phir vhi problem show kr rha hai
sir panal ke wiring par bataye
Ji konse panel ki wiring apko janna hai ??
Sir,
Standard oil pressure kitna hota hain?
35 to 40 psi ke beech me ...
@@c4chiller9984 sir, thank you. Be long live. I am from Bangladesh. Please make more videos regarding HP LP switch wiring.
ok ji ..time milega to ham jarur upload kar denge sukriya 👍
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Sir Good evening
Sir hm jaha job krte hai vha Chiller 1000 Tr ki hai sir ,6 Chiller hai,
Aaj use start krne ke badh uska Condenser Temperature or Condenser pressure Dono high Jaa rha hai sir , Cooling tower vhi ok Condison tha , please sir kya problem ho shakta hai btaye mujhe please sir 🙏🏻🙏🏻
1. Cooling tower se air रिलीज करो ठीक से
2. Cooling tower fan check
3. Chiller ke hisab se ahu ka load kitna hai wo check karo
4. Chiller ko 80% load pe start karo pahle
bhai ppm m
1. weekly m kya kya hota h
2. monthly
3. 3month
4. 6month
5. 1year m kya kya krte h
plz guide me
👉Daily cleaning
👉 Weekly checking equipment and cleaning and all leakege
👉Month check all इलेक्ट्रिक terminal 👉 6 month oil testing and filter checking
👉1year filter change all electrick terminal check and oil level chcek proper all leakege check
If Condenser approch going high so descaling the condenser
Sukriya
sukriya bhai
sukriya bhai
Sir low lube oil pressure ka alam jo iss chiller pe jo aaya tha woh kis wajeh se aaya tha aur sir Chiller over load aur chiller under load ka kya matlab hota hai ??
Qki hamne chiller ko 100 % off kar diya tha jisse ki heater off gaya aor oil temp. Bilkul low chala gaya
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Sir oil heater kitne watt ka hai?
2 kilowatt
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
No, not at all. One is a heater and the other is an oil circulation pump۔۔
If oil pump damage so will come alarm oil pressure low 👉not come low oil temp. Sukriya
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Oil temp high hoke alram or shutdown hua to kya kare sir or oil temp high hone ka reason kya he solution kya he
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Water cold chilar hai
Iow oil pressure alarm 50 क्या है इसका कारण
Kis company ka chiller hai jaha pe alarm 50 aa raha hai ??
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Sir oil low pressure alarm kab aata h..??
Jab oil pressure 33 psi se down jaane lagega 30 psi ke neeche
Thanks sir
Sir oil ka temperature kitna hota haii
50 to 60 digri celcius
Oil ka bowling point kitna hota hai sir
Around 👇 poe oil boiling point
273 digri in celcius
650 digri in Fahrenheit
@@c4chiller9984 523.4 degree farhenheit right I think
bhai baffles kya hota hai please explain please
?
Sir chiller me display nhi aarha he
Ek Baar poore chiller ko 100% off karo aor phir 2 minutes Baad on karo
User manual pdf kse download kre link hoga sir
Dost
Link to ni hai hai ...but aap ko kis chees ka manual chaiyye ??
Sir ddc kya hota hai.
Ye ek panel ka name hai
Jiska full form Direct digital control panel hota hai ye waha pe use hota hai jaha pe BMS ka system ho sukriya
Lo evp temp alarm aaraha hai kya reason hai sir
1. Chiller ka load check karo
2. Primery pump ka pressure check karo
3. Set point temperature check karo
4. Gas ka pressure Kya hai
👉 isi me apko reason mil jayega ..ye pahle check karo aap
Can you help me pro u have same problem i tryed but it didn't work yet
What showing oil temp.??
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Thank you sir ji
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Bro explanation english plz 🙏🏽
My brother...here is many brothers that's don't know proper English...that's why I making vidio in Hindi language...
If you have any doubt or question so it's my Instagram I'd come and here and ask your question..I'd 👉 kgufran195
AHU And FAHU BMS system alarm reset work going on
question jara aap clear kare dost ...??
th-cam.com/video/KQEh6t7pdCw/w-d-xo.html
Please bro reply
please question reply!!!!!
Good day bro this chiller direct drive k h ya gaer box drive h ap k pass mara pass jo chiller h Trane k wo gaer drive h or ois main bhot sound ho Raha h abnormal 33000 running hours ho gai h chiller k ap ois bara main Koi advice dain
Check step by step
1 prv (igv) open properly laod according
2. Greasing time
3. Approch temp.
4. Start chiller with low FLA around 75 %
Sir oil pressure kitna hona chahiye
32 psi to 36 psi
Sir please help me all questions answers 🙏🙏
R134a refrigerant ka..
Superheating Temperature?
Saturation Temperature?
Subcooling Temperature?
R134a refrigerant Expansion valve ke bat temperature kitna hota he?
& R134a refrigerant evaporator se out hone ke temperature kitna hota he?
Chiller normal working condition me Suction and Discharge pressure kitna hota he?
Meroko interview me pucha tha ..
Mene answer nehi de paya..
Please bata dijiye sir🙏
Ji jarur batayenge
Lekin aap kis post ke liye interview dene gaye the 🤗
@@c4chiller9984 Technical Supervisor
Sir please answer bata dijiye..
R134a data
👉Discharge temp. 40 digri celcius
👉Condenser me temp. 30 to 35 digri celcius
👉And evaporater temp.3 to 6 digri celcius
👉Subcooling 3 to 5 digri celcius
Chiller normal conditions pressure
👉Suction 37 to 40 psig
👉Discharge 110 to 120 psi
Yaad rahe jab bhi koi cheej load pe jaata hai to uske parameters bhi kam jyada ho jate hai।।।। ye jo maine bataya hai ye lagbhag standard hai sukriya 🙏
Thank you sir..