Sir ap na kha dono pump ak sath ni operate hota. Jab main pump on hoga tu off jockey pump ka sath off hoga. Means 165 psi off pressure of both main and jockey pump. Please guide.
Sir ,RCC water Tank grouted nozzle size (diameter) aur suction header line size (dia.)kya honi chahiye.5 pumps ke liye in hydrant system.main pump 3nos( 171m3/ hr) aur jockey pump 2 nos
जब भारी मात्रा में पानी की जरुरत होती हैं तो ऑटो कटऑफ नही होगा क्योकीं पानी use हो रहा हैं तो पाईप लाईन में प्रेशर नही maintain होगा, तो मेन पंप चालू ही रहेगा जब तक आप पानी use करते रहोगे, तो manual mode off क्यों चाहिये ?
Mere channel pe fire fighting system ke bare me all information diya hai testing maintenance kiya gaya hai interview related questions ❓ or answers diya gaya hai
Nice video sir bohot dhanyawad 🎉❤
Welcome.
Very informative and concept clearing video
Bahut acche se bataya sir ji aap ne 👍
thanks for watching.
Thanks you Sir. Aap Bahut achha kaam kar rahe, Aap ka Samjhane ka tarika bahut achha hai, Aap kaise hi achhi achhi Videos late rahe .
thanks.
Good information Sir ❤️🙏
कमाल की जानकारी है सर
जितनी तारीफ की जाय वह कम है
कृपया HVAC का भी डिटेल देने की कृपा करें
अपना नम्बर भी दें
thanks and welcome.
U should go through NFPA 20 guidelines to set pressure sequence as we want to know technical point of view.
ok sir. Thanks for your valuable suggestion.
Nice information sir
Thanks and welcome
Knowledgeable Video
thanks.
Sir please 1 video ro filter installation aur maintenance pe banaiye plzz
ok
Sir firefighting se related or bhi video banaye.
sure.
Sir please continue......
sure.
best knowledge
thanks.
Good
thanks.
awesome 👍
Thanks ✌️
Nice video, Add Electrical standby pump also.
thanks.
Sir ap na kha dono pump ak sath ni operate hota. Jab main pump on hoga tu off jockey pump ka sath off hoga. Means 165 psi off pressure of both main and jockey pump. Please guide.
Please send your query on our mail id. we will explain your doubts.
Sir hydropnumetic system kya hota hai batao na?
sure.
Sir ,RCC water Tank grouted nozzle size (diameter) aur suction header line size (dia.)kya honi chahiye.5 pumps ke liye in hydrant system.main pump 3nos( 171m3/ hr) aur jockey pump 2 nos
Spring kular kise kahtye hae
will update the video soon on this.
❤❤❤
What will be time delay for electric pump to start if pressure is not maintained from jockey
it is purely pressure based feature. no time delay is required.
Fire fighting system all information diya gaya hai
Thanks
👍
thanks.
Please make continue video because here we are interested to see all video with good language as you use already... Please sir make all FFTG videos
sure.
Sir how to calculate nos of pump required in pump room for any plant
will update a video soon.
Any IS code refers this?
Sir ,hydrant pump kaise pressurise karte hai???
As per set pressure hydrant pump will start in auto mode.
जब भारी मात्रा में पानी की जरुरत होती हैं तो ऑटो कटऑफ नही होगा क्योकीं पानी use हो रहा हैं तो पाईप लाईन में प्रेशर नही maintain होगा, तो मेन पंप चालू ही रहेगा जब तक आप पानी use करते रहोगे, तो manual mode off क्यों चाहिये ?
Ap please thoda detail mai apka sawal bataiye.
We will reply definitely.
Hydrant pamp kise kahtye hie
which maintain the pressure of hydrant line.
Electrical pump auto pey stop kyun hota hai
Sir ye 3 kya hota hai
As per
did not understand. kindly ask your question IN detail.
Joky pamp ka kay kam hye
to maintain the low pressure drop.
Divide by 10 and add 3
Any specific reaosns pls
divide by 10 provide head. minimum 3 kg/cm square pressure is required at terrace level.
Mere channel pe fire fighting system ke bare me all information diya hai testing maintenance kiya gaya hai interview related questions ❓ or answers diya gaya hai
ok
pls provide english subtitles
ok we will take care in next video.
Sharing Wrong information ,pls read nfpa
what is wrong. please mention.
3 hi kyon jodu
Nice information sir
Keep watching