  • Need to brush up on ring final circuit testing? This video is available to Trade Skills 4U students as a revision aid, however we thought we would make it available for all. This was created by one of our tutors hence why it's a little rough around the edges but still great content. Remember if you are not trained or experienced in electrical installation don't try to install at home or anywhere else for that matter.

ความคิดเห็น • 87

  • @gapster77
    @gapster77 6 ปีที่แล้ว +17

    Listen up Sparks!
    This is the best explanation about this non-exciting, yet need to know test procedure that I’ve seen.
    This Gent explains it concisely and without waffling on, telling you how to do the test and what patterns in the results you should expect to see, and further more why this is the case.
    You are not going to get it explained to you any better than this ...good work fella!
    Wagos are the future, and a very handy addition to your test kit, don’t know why people use the old choc-blocks anymore? Little tip, the newer clear sort with the Brite Orange flat tabs are almost half the size, and unlike the ones used in this vid they can take both a solid and a stranded 4mm.

  • @jayAsparks
    @jayAsparks 5 ปีที่แล้ว +14

    Why can't all teachers be like this. Easy to understand and great at explaining the purpose of what he is testing. Great work, hopefully you do more videos on testing.

  • @neilcowie8446
    @neilcowie8446 2 ปีที่แล้ว +3

    I've watched all the Ring Final Test videos from all the different TH-cam channels. This is by far the most understandable one. Sitting FICA exam next week

  • @jimgeelan5949
    @jimgeelan5949 5 ปีที่แล้ว +7

    Thanks for this vid, it's been one of the most straight forward and clearly explained videos I've seen 👍

  • @user-yp9bx9tj3r
    @user-yp9bx9tj3r 5 ปีที่แล้ว +1

    Trade skills are best. Thank you guys for best time a have spend at your training centre when I did my level 2,3 . Best training in UK

  • @philrichmond7567
    @philrichmond7567 7 ปีที่แล้ว +9

    Brilliant video. Thanks uploader

  • @markandrews8437
    @markandrews8437 6 ปีที่แล้ว +5

    Excellent vid, you sir should make more, your explanation was very clear and understandable well done and thank-you

  • @coolskool1.061
    @coolskool1.061 3 ปีที่แล้ว +4

    Brilliant, excellently delivered lesson, thanks for making it so clear!

  • @ferventheat
    @ferventheat 6 ปีที่แล้ว +3

    great vid, follows it all step by step and good to see it on and actual circuit, rather than it being explained on text book or training.

  • @pyotrleflegin7255
    @pyotrleflegin7255 7 ปีที่แล้ว +25

    p.s. The WAGO blocks are a great idea!

  • @neilwilliams2409
    @neilwilliams2409 6 ปีที่แล้ว +3

    Very good job spot on . Easy to follow step by step guide.

  • @pyotrleflegin7255
    @pyotrleflegin7255 7 ปีที่แล้ว +2

    A very informative video -- thank you.

  • @adrianJUPANU
    @adrianJUPANU 4 ปีที่แล้ว +2

    One of the best videos Ive ever seen !

  • @catherineweitbrecht4107
    @catherineweitbrecht4107 5 ปีที่แล้ว +1

    thank you .. I figured out that my emmersion heater was causing the problem with the ACE THANKS

  • @train4905
    @train4905 4 ปีที่แล้ว +1

    Dear sir a most brilliant video.superbly explained.very clear and concise.thankyou most kindly.has helped me out loads keep up the great work abs videos.

  • @yavare22
    @yavare22 7 ปีที่แล้ว +11

    Best educational video about testing that I ever seen .BIG LIKE Hence and many thanks

  • @stephenhamilton3472
    @stephenhamilton3472 6 ปีที่แล้ว +2

    Thanks for sharing this video it was one of the best explanations of this topic I've seen

  • @stevethomas5849
    @stevethomas5849 7 ปีที่แล้ว +1

    Simply, very well explained. Thanks

  • @steve42681
    @steve42681 4 ปีที่แล้ว +2

    TOP VIDEO. TOP INSTRUCTOR. THANK YOU FOR UPLOADING

  • @geoffdaniel1534
    @geoffdaniel1534 7 ปีที่แล้ว +1

    Brilliant video can I put a water proof consumer unit in a outside shed with armeded cable from back of a socket from conservatory thanks

  • @johnkk7863
    @johnkk7863 6 ปีที่แล้ว +2

    I really like this Kewtech testing equipment, must get a one

  • @Rosscoff2000
    @Rosscoff2000 5 ปีที่แล้ว +1

    That was a useful summary and very clear, but you didn't look at all at the really interesting entry key case of a cross connection on the ring which you showed on the first diagram. I can see that a cross connection could give some puzzling results during testing and make it impossible to reduce the normal numbers, but I've always struggled to see why it might be any kind of safety problem in normal use of the circuit, in fact it seems to me it should improve the performance of a ring.

  • @johnxenofontos628
    @johnxenofontos628 4 ปีที่แล้ว +1

    Thanks for the video well demonstrated and explained.

  • @barnabamatiku6808
    @barnabamatiku6808 6 ปีที่แล้ว +1

    Thanks my Broo... God Bles u.

  • @toddy10hd76
    @toddy10hd76 6 ปีที่แล้ว +2

    I finally understand it after watching this video. Thanks

  • @shaunbeard593
    @shaunbeard593 6 ปีที่แล้ว +2

    Hi Andy a great video. I'm about to embark on an electricians course, all be it rather late in life. I am wondering which way the leads are connected in back of you test machine thanx

  • @curryhouse1377
    @curryhouse1377 7 ปีที่แล้ว +3

    The Best......

  • @adammc2339
    @adammc2339 5 ปีที่แล้ว +3

    Very helpful. Finally!

  • @train4905
    @train4905 4 ปีที่แล้ว +1

    Superb sir.spot on thankyou.very helpful.

  • @misterbaleize
    @misterbaleize 6 ปีที่แล้ว +2

    Excellent instruction; thank you.

  • @train4905
    @train4905 4 ปีที่แล้ว +1

    Superb sir an excellent video.
    Very clear sir.

  • @anelectrician
    @anelectrician 6 ปีที่แล้ว +1

    A very good upload well done.

  • @1987kahil
    @1987kahil 5 ปีที่แล้ว +2

    Very detailed. Thank you

  • @andrewbowes5727
    @andrewbowes5727 4 ปีที่แล้ว +2

    Very clear and easy to follow. thanks

  • @videos40058
    @videos40058 6 ปีที่แล้ว +1

    Sir Bless you!

  • @swanthorn
    @swanthorn 6 ปีที่แล้ว +1

    great video! thanks!

  • @thomashewittknewit5510
    @thomashewittknewit5510 8 ปีที่แล้ว +1

    Yes it was

  • @jimbo2629
    @jimbo2629 6 ปีที่แล้ว

    I am not an electrician, but I would have expected wires to be be correctly connected and checked physically and visually. With good workmanship all this fancy testing should just be an extra. I suppose there are plenty of cowboys about. If there is wrong polarity in a ring I would have thought it would trip or fuse or worse, so you would already know there was a major problem. I still refer to wires as live or positive, negative or neutral.and earth or ground. I like to understand what’s going on when I engage a tradesman, so for me it’s an excellent video.

  • @Mark-ij2nh
    @Mark-ij2nh 7 ปีที่แล้ว +6

    Ha I got 0.02 on all my ring main circuits plus this is the easiest test end to end in college you have to do the more complicated figure of eight test to pass which is what the connector blocks are used for live and neutral and live and cpc

  • @mgabrielle2343
    @mgabrielle2343 6 ปีที่แล้ว

    Do you not have to test the insulation breakdown chjeck using a high voltage source (meggar)

  • @BillsAllotmentDiary
    @BillsAllotmentDiary 5 ปีที่แล้ว +1

    Not a spark but great clear and informative video even if your bad at maths this breaks it down so the reasoning for readings is clear even for inumerate types. have saved this to my watch latter folder.

  • @ianmcklatchie4390
    @ianmcklatchie4390 4 ปีที่แล้ว +1

    Does it necessarily follow that, after the installation of a new Consumer Unit, there must follow a whole-house electrical safety check that is similar in extent and scope of any ordinarily ordered domestic electrical safety check? I really don't know this subject and I'm asking it from an angle of don't-know-anything about the Trade, at all, so be gentle with me, if you would.

  • @zahidkamaly9682
    @zahidkamaly9682 2 ปีที่แล้ว

    Thank you, very easy to understand. helps alot

  • @mainlyhappy7330
    @mainlyhappy7330 7 ปีที่แล้ว +1

    Very good

  • @UDASAN1
    @UDASAN1 7 ปีที่แล้ว

    Well explained

  • @001Neal100
    @001Neal100 6 ปีที่แล้ว

    Very well explained

  • @sheriffagboola2710
    @sheriffagboola2710 6 ปีที่แล้ว +1

    this was great we need yo to load for cooker

  • @johnnevin5706
    @johnnevin5706 7 ปีที่แล้ว +1

    big like cheers

  • @flasher395
    @flasher395 6 ปีที่แล้ว

    Can you explain why you expect the grounding wires to have a higher resistance than the line and neutral wire? I would have expected them to have an even lower resistance than the others.

  • @Oldhogleg
    @Oldhogleg 6 ปีที่แล้ว +1

    Wow! I'm a licensed electrical contractor here in the U.S., and running a "ring" circuit is not only illegal here, but also makes no economical rational sense because you're unnecessarily consuming extra cable by having two home runs instead of one for the same circuit. It's also illegal to have more than one conductor in each terminal here in the U.S.
    The other thing that's different, it's illegal here in the U.S. to use the use devices such as receptacles as spicing devices, we have to use pigtails as circuit taps for all devices so the circuit is never interrupted (especially ground) by a defective device, or by the removal of the device.
    Seems like there's no benefit in doing the extra expense of a second home run, especially since it makes trouble shooting much more complicated by creating two power sources in the same circuit?
    Your load center designs are very different from ours here in the U.S. , we have much more room to organize our wiring within the panel, and our bus bars are in the middle of the panel with circuit breakers snapping on both sides.

  • @futurecarslondon1109
    @futurecarslondon1109 4 ปีที่แล้ว

    Great teacher

  • @tonypalmer4039
    @tonypalmer4039 5 ปีที่แล้ว +1

    Very good indeed. Couldn't be clearer.

  • @bernardcharlesworth9860
    @bernardcharlesworth9860 2 ปีที่แล้ว

    Lovely quick video for 3291

  • @pavel29jenny
    @pavel29jenny 5 ปีที่แล้ว +1

    Hello! Tell me please; is that type of a circuit, so called "socket ring circuit" you have in each house in U. K. ?? Very interesting (?) what is the reason for that type of wiring the socket’s in the ring??
    Can you tell me please (?) why you do that for??????
    What is that ring good for???
    How it is working???
    Can you please answer in the video (?) so I can get to the point of it, please???!!!!

  • @iraqviva7670
    @iraqviva7670 3 ปีที่แล้ว +1

    In my house I'm getting a reading between r1&rn and getting reading between conductors but getting 0.00 in r1 and r2 what could it be

  • @malcolmevans941
    @malcolmevans941 4 ปีที่แล้ว

    Another great video

  • @lifeis2shortuk
    @lifeis2shortuk 5 ปีที่แล้ว +1

    Thank you .very clear .

  • @russellwallman13
    @russellwallman13 8 ปีที่แล้ว +8

    are we going to get more frequent videos?, this was very helpful .

  • @sukandarazam9623
    @sukandarazam9623 7 ปีที่แล้ว +1

    Thats my tutor....

  • @shoaibahmad4301
    @shoaibahmad4301 7 ปีที่แล้ว +1

    Hello tell me please I replaced my home main breaker 63 amp with 40 amp earth leakage before that mcb it can be trip by the joining the Neutral & phase room breaker now it cannot trip other then it can be trip when phase touch in water or iron.

    • @zaks8285
      @zaks8285 4 ปีที่แล้ว +1

      HAHAHAHAHA

  • @keinnaciri5452
    @keinnaciri5452 6 ปีที่แล้ว

    سلام خیلی ممنون از زحمات شما

  • @joelaw5207
    @joelaw5207 5 ปีที่แล้ว

    At exactly 5.12 sec you say on 2.5mm / 1.5mm T& E the reading should be 1.67 times higher due to the smaller cpc cable. However, On my house the reading is only 0.2 higher. IE. L1-L2 is 0.22 N1 - N2 is 0.22 E1 -E2 is 0.24 My Question is what does this small cpc reading show? The circuit operates ok. But id like to know what it tells us? Also on the cross connection test (L1-N2 & L2 - N1) the reading should be HALF the L1 L2 reading but on mine its the same 0.22. what does this mean.?

  • @rdl4028
    @rdl4028 5 ปีที่แล้ว +1

    amazing thanks

  • @chestermartin2356
    @chestermartin2356 5 ปีที่แล้ว

    I don't get what the 4 resistances are? 4 sockets?

  • @lifeis2shortuk
    @lifeis2shortuk 5 ปีที่แล้ว +1

    Why for r1 and r2 you test all ring and radial together ?

  • @omaryabdul2256
    @omaryabdul2256 7 ปีที่แล้ว

    thanks

  • @vijaymani6476
    @vijaymani6476 7 ปีที่แล้ว

    sir maximum how many ohm in ckt loop...tell to ohms range in loop

  • @MrMahmedkhan
    @MrMahmedkhan 6 ปีที่แล้ว

    thank u sir []

  • @MrSailbadthesinner
    @MrSailbadthesinner 6 ปีที่แล้ว +1

    Who noticed that the L-N connections had magically changed just before Step three!

  • @Amirhussain-jm1hn
    @Amirhussain-jm1hn 4 ปีที่แล้ว +1

    sir can I electrical work without education certificate

  • @TerminaterJB
    @TerminaterJB 6 ปีที่แล้ว +1

    great! now i've got a damn headache

  • @Jamal_Tyrone
    @Jamal_Tyrone 6 ปีที่แล้ว

    I was told to call it a socket adaptor rather than a socket tester, that's sparky terminology for you though - it's not a bulb, it's a lamp! :-P

  • @PompeyMatt17
    @PompeyMatt17 4 ปีที่แล้ว +2

    Downthumbs are from competing course providers :)

  • @alunroberts1439
    @alunroberts1439 4 ปีที่แล้ว

    I don't see why it will go up if the socket is reversed

  • @sheriffagboola2710
    @sheriffagboola2710 6 ปีที่แล้ว

    sorry also need for cooker and installation resistance test

  • @JG-wx2xs
    @JG-wx2xs 5 ปีที่แล้ว

    That wiring on the test board is rough

  • @kkpropertysolutions3785
    @kkpropertysolutions3785 4 ปีที่แล้ว

    Bit confusing about the regs .where it’s the safety no fuse on the spur ,two wires from the consumer unit one on the spur same csa🤔🤔🤔can anyone explain???

  • @ALKUKES
    @ALKUKES 6 ปีที่แล้ว

    To much paperwork

    • @bitTorrenter
      @bitTorrenter 4 ปีที่แล้ว +1

      Not much you can do about that. It's part of the regulations.

  • @MrDasmaster
    @MrDasmaster 6 ปีที่แล้ว

    rings are a disgrace and should be banded