Motors: Conductor sizing and overcurrent protection

แชร์
ฝัง
  • เผยแพร่เมื่อ 1 ต.ค. 2024
  • This video shows how to size conductors and overcurrent devices for motors.

ความคิดเห็น • 36

  • @karlringsdorf5858
    @karlringsdorf5858 5 หลายเดือนก่อน +11

    I heard a comment that I still use when teaching this material. FLC = Full Load CODE, use the tables to size conductors, OCPD, devices. FLA = Full Load ACTUAL use for sizing the Overloads. Great little cheat, for remembering it.

  • @JohnThomas-lq5qp
    @JohnThomas-lq5qp 3 หลายเดือนก่อน +1

    I disagree with the too high of a value motor amps when connecting 2, 4 or 6 pole plain jane Nema frame motors that in my 50 years as a commercial electrician covered over 99% of installtions. Of the thousands of motors that I have replaced, moved, installed or PM'ed never came across a single motor that was within 10% of the NEC ampere. Just went 125% of the motor FLA & if a long run would calculate voltage drop and would increase wire size if needed. We had AHU'S that had two 60 to 125 HP motors where both supply motors ran 24/7 but seldom over 50% of full speed and on VFD'S. I could run over 1200 amps of AHU motors from a 800 amp distribution panel for 50 years snd never trip out the 800 amp breaker because of constant reduced speeds feed from VFD'S. Only time a supply motor ran close to full speed was when other motor was down for PM or rare replacement.

  • @Matthew-fk2vv
    @Matthew-fk2vv 4 หลายเดือนก่อน +5

    Sure, the NEC sits there accessible in our rooms, work vehicles & classrooms etc. It's instructors like this gentleman, however, who inspire us to read and apply it to our work.
    Good teachers are a gift to the world, thank you for sharing, sir.

    • @boeing757pilot
      @boeing757pilot 4 หลายเดือนก่อน

      Agree. He's an outstanding instructor!

  • @marianoetom1531
    @marianoetom1531 5 หลายเดือนก่อน +3

    A very gifted instructor.

  • @rafalszachnowicz2831
    @rafalszachnowicz2831 5 หลายเดือนก่อน +2

    I really enjoy your videos. The topic is explained in a very logical and easy to understand way. Much better than procedural instruction given at school: you do this, then take this and based on that you do that because the table allows you this if that but not this because of that. Thank you. You helped another electrician to enjoy his job.

  • @stillthakoolest
    @stillthakoolest 5 หลายเดือนก่อน +3

    Thanks for all you do Ryan. One of the best instructors out there. Great video

    • @boeing757pilot
      @boeing757pilot 5 หลายเดือนก่อน

      Definitely. He's excellent!

  • @Pusacat_75
    @Pusacat_75 13 วันที่ผ่านมา

    Hi all! Why most of the electrical designer I know is using 175% NOT 250% to size breaker for a single motor?

  • @margaretosgood9706
    @margaretosgood9706 3 หลายเดือนก่อน

    I'm a little confused about when to use the 430.6 (1) Exception No 3. 42 minutes into this video, there's a motor nameplate with both HP and full load current. Why are the NEC Part XIV tables used instead of the nameplate values?

  • @brianfisher6799
    @brianfisher6799 หลายเดือนก่อน

    This is probably the stupidest question, but would generators be under the same constraints?

  • @jsb7546
    @jsb7546 หลายเดือนก่อน

    I love the videos man. Nice to have a guy like you that helps clarify some things in the code. Im always bugging the masters and other journeyman I know about code and you are honestly a better resource them some of them.

  • @manuellastrollo2168
    @manuellastrollo2168 4 หลายเดือนก่อน

    is voltage drop a factor if the motor is 150ft, 30Hp 3Ph?

  • @ed6837
    @ed6837 3 หลายเดือนก่อน

    Excellent video!! Thank you.

  • @troydhansen4990
    @troydhansen4990 4 หลายเดือนก่อน

    if you pulse DC power, you will get more out than in

  • @9bnmadden
    @9bnmadden 5 หลายเดือนก่อน +1

    Awesome video, very informative! Thank you, Ryan.

  • @savemyneighborhood
    @savemyneighborhood 5 หลายเดือนก่อน +1

    Thank you, Ryan. Love your explanation and concept as it is easy to understand.

  • @benedalati1527
    @benedalati1527 4 หลายเดือนก่อน

    One word, Just Excellent.

  • @mattv5281
    @mattv5281 5 หลายเดือนก่อน

    I'm glad I only have to size the circuit for my 6.5hp shop vac based on the FLC (13A). Otherwise it looks like I'd need an 80A 120V circuit for it!

  • @boeing757pilot
    @boeing757pilot 5 หลายเดือนก่อน +1

    Thanks! You're an excellent instructor. You clearly explain the concept, address the nuance, anticipate and answer questions, and explain the "why" and applications.. Excellent. I wish many of my flight instructors were as good.

    • @RyanJacksonElectrical
      @RyanJacksonElectrical  5 หลายเดือนก่อน +2

      Thanks for the donation! And thanks for the kind words, that's very nice of you to say.

    • @boeing757pilot
      @boeing757pilot 5 หลายเดือนก่อน

      @@RyanJacksonElectrical You're quite welcome, Ryan!

    • @jsb7546
      @jsb7546 หลายเดือนก่อน +1

      That is exactly it, the why to me is really important. I know a lot of guys that just say hey that's code so just do it, but having that why really helps me understand the code a lot more.

    • @boeing757pilot
      @boeing757pilot หลายเดือนก่อน

      @@jsb7546 Absolutely!

  • @jeffreyknowles6265
    @jeffreyknowles6265 5 หลายเดือนก่อน

    I need to replace the service on my house, I am a union electrician, I normally do not do Residential work.I would like to see a video from you about what I need to know about arc fault breakers. I graduated from my locals apprenticeship program in 1996, way before arc fault circuits.

  • @Roommate625
    @Roommate625 5 หลายเดือนก่อน

    Ryan, always a pleasure watching you and I love the refreshers.
    Being a little bold and hopefully not requesting too much, I'd love a refresh on multi-motor crane calculations and arc welder calculation for conductor, etc.
    Again, thank you for everything you do for the electrical community!!!

  • @RickVillarreal0892
    @RickVillarreal0892 วันที่ผ่านมา

    47:26😂

  • @EdwardPerez-s2x
    @EdwardPerez-s2x 4 หลายเดือนก่อน

    I watched the entire video it helped me better to understand article 430 about motors rules . Thank you..

  • @Farmerdave11008
    @Farmerdave11008 5 หลายเดือนก่อน +1

    Thank you Ryan!

  • @smittylikesto
    @smittylikesto 4 หลายเดือนก่อน

    🔥

  • @Jeremiah9909
    @Jeremiah9909 2 หลายเดือนก่อน

    would you do a video on 225.30

    • @RyanJacksonElectrical
      @RyanJacksonElectrical  2 หลายเดือนก่อน

      @@Jeremiah9909 Great idea! Part II of Article 225 is so misunderstood

  • @johnkling3537
    @johnkling3537 5 หลายเดือนก่อน

    Nice build up to 430.6 - overcoming inertia

  • @jarrydee2799
    @jarrydee2799 5 หลายเดือนก่อน

    See you in Bay City once again!!