Obviously sir uppka videos other youtubers se best hai specially for utl gamma plus 😍😍and upka haar ek cheez samjhaneka tarika bhi bohot accha hota hai😀🤩😍
Sir mere pass Utl Gama plus 12v h 220 ah battery h jayda backup ke liy kitne ah ke battery or Lagay me 330 watts ke teen panel lagana chata hu Bijli off rakhna h din me load 300 watt night me 6baje se10baje Tak 400 watt bad me average 100watt tak hota h
Grid-Solar-Battery= Hybrid Solar-Battery-Grid= Pcu Solar-Grid-Battery= Smart Low power cut = Pcu Medium power cut= Smt High power cut = Hybrid. Best mode is Smt. Pcu mode will decrease battery life. Hybrid mode is best if you have high power cut. Like if I am right.
Bhai mera PSU mode me h jab grid se connect ho jata h to next day solar power 20 amp ho tab bhi grid se disconnect ne hota.manualy mujhe main of Krna prta h. Tab vo disconnect hota h help me
Sir namste🙏 Mere yha utl gaama plus 12v 1kva lga hai or 270 ah battery bank or 960 waat polly panal to sir bust satting kya rhege mere invartr ki muje gird jayda use nhi karni din ke time only light on rhti hai light ka load 130 waat hai plzz help me sir🙏
For Bill saving you can use PCU mode. Calibration explained here- th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html Battery settings here- th-cam.com/video/1RMkdRQ1vg4/w-d-xo.html
Sir mera utl Gamma plus 12 inverter ups mod me bhi mains pe hi chalta hai solar or battery pe chlane ke liye mains off karna padta hai. Please problem solve kijiyega.
I am from Kerala.I installed utl 375w perck two panel with 12v utl rmptsolar inverter.using 12v utl 150ah battery.panel is connected parallel.Inverter shows 40v amp 3.6 like.The setting is as L battery 11.5 H 16.5 spv. Boost 14.4 spv flat 13.8 boost main 14.4 flat 13.5.After 6 clock light shows red.Battery shows low.I am using PCU mode.I am expecting your great reply.Your viedo is very understandable and useful.Thanking you.
Hello Sir, 1. If the panels are connected in Parallel, The Amperes should be Total of IMP (Written on back of panel). I shall guess 17 to 20 Amps total. 2. Low amperes can happen due to Variety of Reasons. Such as Faulty Panel, Faulty PCU or even Less load, As discussed here- th-cam.com/video/pS_MZ00l3so/w-d-xo.html 3. Red screen Explanation here- th-cam.com/video/wEOpbYA767Q/w-d-xo.html Calibration explained here- th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html 4. You're welcome.
Sir mere pass 1kva 24 volt ka gmmaa plus inverter hee . Grid power supply not available jb ratt me battery down hojata he subha jb solar atahe inverter automatic on nehi hota sab din manually on karna padta he
Mera ek doubt he jab ratt me battery khatam hata he inverter off ho jata hee Uski bad jab surj niklti he battery charge hota he lekin on Nehi hota automatic
#Ask Zen सर नमस्कार, मैं अपने gamma + को स्मार्ट मोड में चलाता हूँ (300 वाट के तीन पैनेल )और दिन में ग्रिड स्विच आफ कर रखता हूँ तथा ग्रिड चार्ज डिसएबलड रखता हूँ। दिन में पैनेल 30 वोल्ट 16 + एम्पस का करन्ट जनरेट कर रहा था मैने ग्रिड आन कर दिया तो मैंने देखा कि पैनेल करन्ट घटकर 30 वोल्ट 4 + Amps पर आ गया जबकि लोड में कोई परिवर्तन नही किया गया था । जैसा कि मुझे समझ में आया कि ग्रिड आन करने के बाद कुछ लोड 360 वाट [( 30x16 )- (30x4 )] ग्रिड द्वारा टेकओवर कर लिया गया जबकि पैनेल का आऊटपुट 120 वाट का रह गया । क्या यह सामान्य था या मेरी सेटिंग में कुछ परिवर्तन करना चाहिए । मैने आपके बताये अनुसार एँडवांस कैलिबरेशन कर रखा है। कृप्या मार्गदर्शन करे। धन्यवाद एवं आभार
Sir my utl gamaplus one kva inverter switches to eb even when the battery voltage is above the reconnect voltage (pcu mode is set) I haaaave two off gird solar systems and it has produced less then 1000 units for the past 27 months since installation. Bothe the systems have two 435luminous monoperc (half cut) pannels in parallel connected to one kva utl gama plus inverters(2 units) one unit has two 12v 200ah tall tubular batteries in parallel and the other one is one c10 12v 200 ah battery. I am living in Chennai, Tamil Nadu. Kindly advise. Thank you, I am a subscriber of your channel and follow them regularly .For two batteries unit the spc charging current is 38.9 and for the single battery unit is spv charging ampere is 18. For both reconnect voltage is 11.8
If there are no other faults, This usually happens due to the typical behaviour of lead acid battery. The voltage sags below 11.8 whenever any heavy load is started and the inverter switches to mains. Try playing with the reconnect voltage to 11.6 and report back. Also, check the actual performance of solar panels using a good clamp meter.
@@ZenInnovations Thanks a lot sir. Will follow your suggestion. Now i have switched off e.b. . can i do that Sir. Thanks once again for your prompt reply
Sir, I have two questions: 1. I kept my utl gamma + at pcu mode. But at night it does not take from battery. What is the problem? 2. I have one 150w solar panel connected with utl gamma+. When solar voltage becomes low(before sunset), fans of utl on and off frequently. That makes me annoyed. Is it normal?
Sir Mera inverter main line se chlta rhta h. Jb power cut hoto h to automatically bettry pr shift nhi hota on ka button dbane se shift hota h kese shi hog
Sir 30 april ko aj ke din din me 2 baje 3 335 ke panel only 7.2 amp current de rahe hai yadi grid chalu rakhte hai to. Or jab grid band hai to 19 amp sahi de raha hai sir g ye grid ke sath itni kam q de raha hai on hybrid mode
@@ZenInnovations sir g mere matlb hai jab grid on hai to panel kam amp nikal raha hai light band karne k bad amp jyada aa rahe hai kya problem ho sakti h
Hello sir, My utl gamma reconnect voltage setup is 11.8. I am using pcu mode. At night (when I am checking), my battery voltage is 12.3. When I on the main (grid) switch, the utl gamma inverter is started to run load on grid. But say that in pcu mode, inverter run load on battery if battery voltage is greater than reconnect voltage i.e. 11.8. Why this happens?
Smart mode m Sam k time jb solar energy km ho jayegi aur load chalane k liye paryapt nhi rahegi tb load solar aur grid milakar chalega ya sirf solar se chalega
I have changed low voltage to 11 volt but at 11.6 low voltage beep starting . My battery is 150 ah and around 40 % load running that time. Is it a problem with utl pcu (12 volt) or its normal?
मुझे नेक्सस 1kva/12v लेना है लेकिन उसमें पीसीयू मोड नही है बस स्मार्ट और हाइब्रिड मोड है तो क्या सही रहेगा या फिर UTL Gamma+ ही ले लूं लेकिन नेक्सस में 1200 वॉट तक पैनल लगा सकते है और UTL Gamma+ में नही ??? प्लीज बतायें
Sir; I use the HYB mood but my problem is when machine backup mood gone then machine continue vibration big sound come in from inside so can u help me fix this problem, thanks
सर अगर हम ग्रिड चार्ज का ऑप्शन बंद न करें तथा main line kafi der tak yani ratri lagbhag 8 baje tak band rakhen aur uske bad khol de to kya aaya aam aadami ke liye theek nahin rahega.
mere pass luminus ka inverter h vo main grid se hi chalta rhta h 1000w solar west hi hoty rhty h m kya keru koi solution do ki mera inverter pcu ban jay
@@ZenInnovations hi..my amaron quanta smf 120 Ah has a boost charge value of 13.8v and float voltage of 13.5v. It's written on the battery itself. Shall I follow them or go for factory values? Please let me know. Thanks in advance.
@@ZenInnovations thanks for the answer. I have a doubt. Battery says boost charging @13.8v and float @13.5. On my gamma plus can I use 14.2v to 14.4v for bulk charging? I am asking this because when I set my bulk voltage to 13.8v the backup has been reduced..
Sir , my led tube lights starts flickering when I am running on solar inverter. I have 2Kva 24 system utl gamma plus . I get the flickering when running smps loads. Any solution for this issue ? Thanks
Very useful information ❤️ Sir agar hyb mode on hai or solar charging ho rhi hai to kya grid se bhi charging hi rhi hogi ya ek time mai ek se charging hoti hai
@@ZenInnovations kya aisa possible hai ki bina battery charge kiye direct load chlaya ja ske Mtlb inverter solar se mil rahi dc ko ac mai badl kr direct load chlaye (no involvement of battery)
I am using Gamma+ recently. Want to know what to set in Gramma+ because I am only using solar, without Grid supply. Using the Gamma+ 2600 model with two 150Ah batteries in series and 440. Watt 24v two panels in parallel,
@@ZenInnovations Thank you. I am using two 150 Watt 12V panels in first series and then I have connected them with two 440 Watt 24V , can the 150 watt panels affect the efficacy of the 440 watt panels. Please suggest, because I didn't got any video on this issue.
Sir, your video is very helpful to me. I want to know if I will set HYB mode and if the solar panel is present with sufficient sunlight then what will happen? The load will run on the grid, battery will charge on the grid. My concern is, the solar energy will not use in HYB mode? If yes how? I appreciate your prompt reply. Thank you so much.
@Tech Sandeep main aik solar battery luminous ka aur hybrid mode ka solar inverter lena chahta hoon taki mere battery ka charge din me khatam na ho night me youse karo iske liye luminous me koyee solar inverter ata hai
I will make panel testing videos on this channel. Stay subscribed! In the meanwhile you can compare Panel voltages with Sticker spec mentioned in the back of panel.
Hi! Your videos on UTL Gamma Plus Solar Inverter and others are excellent, informative and very useful. Thank you. I have a query. I run my UTL Gamma PLUS in SMT mode. On bright sunny days, the inverter turns the mains on (screen turns bright orange) and “SPV Amp” gets down to zero (with “SPV Volt” ~59.4). In addition, there is a screen that says “SPV Hi”. Do I need to change any particular setting? I have two 300 Watt solar panels connected in series. The DC current comes from the solar panel to the inverter via a 16 A circuit breaker. The circuit breaker does not get off during “SPV Hi”. I connected two batteries of equal capacity in parallel to the inverter. I would be thankful for a solution to the problem.
Sir mere pas utl Gamma plus inverter hai Livfast ki solar battery and 325watts ke panel. Neeche maximum 6.5 amp hi ate hai. Battery full charge kisi-2 din hi hota hai. 2 maheene to sab kush sahi chala abhi battery sham ko hi low ho jati hai. Kya is trah se battery khrab ho skti hai agr kafi dino ta full charge na ho
Sir am currently using Luminous 200Ah solar battery with Utl gamma+. My full charge of battery goes between 14.2- 14.3 volts. Also in smart mode, during evening till mains is reconnected, battery charge comes down to 12.5. Is it normal?
@@ZenInnovations thank you sir. This battery voltage is confusing. Battery is 12V but full charge goes upto 14.3V . Confused on what volts the battery can be said to be discharged by 80%
Hello Mai UTL Gamma plus 12 volt use kr rha hu, solar panel 165x3 hai, aur 150Ah ki tubular battery hai, Kis mode par Gamma Ko rakhu? Mujhe bijli bill kum krni hai
Guys Advanced Calibration Video has been launched ! UTL Gamma Plus Solar Advanced Calibration | Optimum Settings Explained, Each Mode In Details [Hindi] th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html
#askzen नमस्कार Sir मेरा नाम अमित कुमार है मेरा आपसे एक सवाल है और आप से उम्मीद है कि आप उसका जवाब मुझे जरूर देंगे मेरा सवाल है कि मैं अपने सोलर पैनल को किस तरह से कनेक्ट करूं जो मुझे ज्यादा बेनिफिट मिले मेरे पास जो भी इंस्ट्रूमेंट है उनका लिस्ट में नीचे लिख रहा हूं 1. मेरे पास 2 पैनल हैं 12 Volt ,165 वाट के जिनकी VOC 23.04 है 2. एक ट्यूबलर बैटरी है 150 AH की 12 वोल्ट 3. एक इनवर्टर है UTL Gama Plus 12 वोल्ट and Voc 45 और सर अगर मैं एक पैनल और ले लूं सेम वाट का यानी के जब मेरे पास 3 पैनल हो तब मैं इनको कैसे कनेक्ट करूं गा Please Sir reply जरूर देना
@@Hiteshmeena123-f7m I cannot help you with physical faults. They have to be checked by expert technicians. Maybe something is blown up. Check the fuses.
1) Upto which level, battery is charged in SMART mode when grid charging is off (full charged or 30% charged). 2) Do auto shifting of load from main to solar happens in HYBRID mode ? 3) Which Mode is best for this PCU for savings and battery backup. Using: Solar UTL Gama PCU
Sir video bohot aacha thanks for sharing the information with us 👍👍👍😃
Most welcome Dip ji !
Keep supporting !
Obviously sir uppka videos other youtubers se best hai specially for utl gamma plus 😍😍and upka haar ek cheez samjhaneka tarika bhi bohot accha hota hai😀🤩😍
Wah dip ji. Nice to know that videos are helping people.
Sir hamare area m power cut Kari frequent h to konsa mode best rhega
Sir mere pass Utl Gama plus 12v h 220 ah battery h jayda backup ke liy kitne ah ke battery or Lagay me 330 watts ke teen panel lagana chata hu Bijli off rakhna h din me load 300 watt night me 6baje se10baje Tak 400 watt bad me average 100watt tak hota h
Ek aur 200 ya 220 AH batttery lagaiye parallel me-
th-cam.com/video/IuXsJBSOn1A/w-d-xo.html
Grid-Solar-Battery= Hybrid
Solar-Battery-Grid= Pcu
Solar-Grid-Battery= Smart
Low power cut = Pcu
Medium power cut= Smt
High power cut = Hybrid.
Best mode is Smt.
Pcu mode will decrease battery life.
Hybrid mode is best if you have high power cut.
Like if I am right.
Sir nexus 1ka plus 12v model or utl gamma plus 1kva 12v ka comparigen video bnaye or isme kone sa badiya hai plz video bnaye
I will try in Future. Thanks!
Can I use Utl gamma 2000kv without batteries, Grid supply aur solar panels input दोनों देना होगा या सिर्फ सोलर पैनल से इनपुट देना है।
No
Bhai mera PSU mode me h jab grid se connect ho jata h to next day solar power 20 amp ho tab bhi grid se disconnect ne hota.manualy mujhe main of Krna prta h. Tab vo disconnect hota h help me
We discussed this on Telegram Group Today itself. You can Join.
Agar ham hybrid mod pe grid charging off karde to solar panel se battery charge hogi ya nahi, merr pas 165w panel hai aur 80amp battery hai
Yes.
Sir namste🙏
Mere yha utl gaama plus 12v 1kva lga hai or 270 ah battery bank or 960 waat polly panal to sir bust satting kya rhege mere invartr ki muje gird jayda use nhi karni din ke time only light on rhti hai light ka load 130 waat hai plzz help me sir🙏
For Bill saving you can use PCU mode.
Calibration explained here-
th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html
Battery settings here-
th-cam.com/video/1RMkdRQ1vg4/w-d-xo.html
Gama plus ups ko wifi connection karnaka liya kaya karna paraga
Direct nahi ho sakta. But you can try this -
th-cam.com/video/zNZ_1_CpKDI/w-d-xo.html
550watt ke 2 panel chal jayege kya utp gama plus 3350 batado yaar mene utl gama order kar Diya hai
smt mood me bettry charge hoti h kya
Pls watch the video full.
HI SIR WHO IS THE BEST UTL,VISPRA,LUMINOUS, AND MPPT CHARGE CONTROLLER PLS TELL ME
th-cam.com/video/V2J2il91kyc/w-d-xo.html
Sar utl sigma + solar pcu ma Bina lod k kitna watt kunjum karta hai
Sir mera utl Gamma plus 12 inverter ups mod me bhi mains pe hi chalta hai solar or battery pe chlane ke liye mains off karna padta hai. Please problem solve kijiyega.
Calibrate the settings properly like this th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html
I am from Kerala.I installed utl 375w perck two panel with 12v utl rmptsolar inverter.using 12v utl 150ah battery.panel is connected parallel.Inverter shows 40v amp 3.6 like.The setting is as L battery 11.5 H 16.5 spv. Boost 14.4 spv flat 13.8 boost main 14.4 flat 13.5.After 6 clock light shows red.Battery shows low.I am using PCU mode.I am expecting your great reply.Your viedo is very understandable and useful.Thanking you.
Hello Sir,
1. If the panels are connected in Parallel, The Amperes should be Total of IMP (Written on back of panel). I shall guess 17 to 20 Amps total.
2. Low amperes can happen due to Variety of Reasons. Such as Faulty Panel, Faulty PCU or even Less load, As discussed here-
th-cam.com/video/pS_MZ00l3so/w-d-xo.html
3. Red screen Explanation here-
th-cam.com/video/wEOpbYA767Q/w-d-xo.html
Calibration explained here-
th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html
4. You're welcome.
Hello to save electricity should turn off grid charging and mains connection in smart mode ?
You can.
@@ZenInnovations ok thanks
Sir maine spv amp 25amp rakha hi single battery 150ah chalega ya battery kharab ho jayegi
calibration ka video dekho...
Bro 900 watt panel me gana+ ke sath 0.5 ho pump chalega ki nehi?
Not recommend.
Bina panel ka main se normal inverter ke jasa use kar sakte hain? please reply konsi mode per
Hyb
Sir gamma 3350 ko only light se chalane ke liye kya koi setting karni hoti hai
Hyb mode
Sir mere pass 1kva 24 volt ka gmmaa plus inverter hee . Grid power supply not available jb ratt me battery down hojata he subha jb solar atahe inverter automatic on nehi hota sab din manually on karna padta he
Replace or upgrade the battery.
@@ZenInnovations neya 24 volt ka lithium battery
Mera ek doubt he jab ratt me battery khatam hata he inverter off ho jata hee
Uski bad jab surj niklti he battery charge hota he lekin on Nehi hota automatic
@@suryakantabhokta7992 nahi hoga.
Sir Gama + Ka display brightness Kasey adjust kare
You cannot adjust the Brightness.
#Ask Zen
सर नमस्कार,
मैं अपने gamma + को स्मार्ट मोड में चलाता हूँ (300 वाट के तीन पैनेल )और दिन में ग्रिड स्विच आफ कर रखता हूँ तथा ग्रिड चार्ज डिसएबलड रखता हूँ। दिन में पैनेल 30 वोल्ट 16 + एम्पस का करन्ट जनरेट कर रहा था मैने ग्रिड आन कर दिया तो मैंने देखा कि पैनेल करन्ट घटकर 30 वोल्ट 4 + Amps पर आ गया जबकि लोड में कोई परिवर्तन नही किया गया था । जैसा कि मुझे समझ में आया कि ग्रिड आन करने के बाद कुछ लोड 360 वाट [( 30x16 )- (30x4 )] ग्रिड द्वारा टेकओवर कर लिया गया जबकि पैनेल का आऊटपुट 120 वाट का रह गया । क्या यह सामान्य था या मेरी सेटिंग में कुछ परिवर्तन करना चाहिए । मैने आपके बताये अनुसार एँडवांस कैलिबरेशन कर रखा है।
कृप्या मार्गदर्शन करे।
धन्यवाद एवं आभार
Yeh Bilkul normal hai.
PCU utna hi solar use karega jitna zaroorat hai.
More explanation in this video-
th-cam.com/video/pS_MZ00l3so/w-d-xo.html
Sir my utl gamaplus one kva inverter switches to eb even when the battery voltage is above the reconnect voltage (pcu mode is set) I haaaave two off gird solar systems and it has produced less then 1000 units for the past 27 months since installation. Bothe the systems have two 435luminous monoperc (half cut) pannels in parallel connected to one kva utl gama plus inverters(2 units) one unit has two 12v 200ah tall tubular batteries in parallel and the other one is one c10 12v 200 ah battery. I am living in Chennai, Tamil Nadu. Kindly advise. Thank you, I am a subscriber of your channel and follow them regularly .For two batteries unit the spc charging current is 38.9 and for the single battery unit is spv charging ampere is 18. For both reconnect voltage is 11.8
If there are no other faults, This usually happens due to the typical behaviour of lead acid battery. The voltage sags below 11.8 whenever any heavy load is started and the inverter switches to mains.
Try playing with the reconnect voltage to 11.6 and report back.
Also, check the actual performance of solar panels using a good clamp meter.
@@ZenInnovations Thanks a lot sir. Will follow your suggestion. Now i have switched off e.b. . can i do that Sir. Thanks once again for your prompt reply
Sir, I have two questions:
1. I kept my utl gamma + at pcu mode. But at night it does not take from battery. What is the problem?
2. I have one 150w solar panel connected with utl gamma+. When solar voltage becomes low(before sunset), fans of utl on and off frequently. That makes me annoyed. Is it normal?
1. Upgrade your Solar panels & battery bank
2. Normal.
@@ZenInnovations thanks a lot
Agar solar inverter me neutral mains se liya to mains ke metter me unit count hoga ky
th-cam.com/video/aLc4bGIm1Go/w-d-xo.html
Sir Mera inverter main line se chlta rhta h. Jb power cut hoto h to automatically bettry pr shift nhi hota on ka button dbane se shift hota h kese shi hog
Contact service center
क्या इस इनवर्टर से सेमी आटोमेटिक वाशिंग मशीन और फ्रिज चल सकता है।
Pls watch These videos-
Washing machine-
th-cam.com/video/eYYAeYWGZX8/w-d-xo.html
th-cam.com/video/-kTYyBdBV5s/w-d-xo.html
th-cam.com/video/bs1Yp1X0bUc/w-d-xo.html
Fridge-
th-cam.com/video/X5-3Xs_eghY/w-d-xo.html
th-cam.com/video/QaoWGrwExdw/w-d-xo.html
Sir 30 april ko aj ke din din me 2 baje 3 335 ke panel only 7.2 amp current de rahe hai yadi grid chalu rakhte hai to. Or jab grid band hai to 19 amp sahi de raha hai sir g ye grid ke sath itni kam q de raha hai on hybrid mode
Normal behavior.
Pls watch solar QNA to understand
@@ZenInnovations sir g mere matlb hai jab grid on hai to panel kam amp nikal raha hai light band karne k bad amp jyada aa rahe hai kya problem ho sakti h
@@ZenInnovations subah se 9 ghante ho gaye par battery full charge ni hui
Koi problem nahi hai. Amp ON DEMAND hota hai.
Sir g mujhe ap mail id do pls m ek chhoti si recording karke apko bhejta hu us se samjhna pls
Hello sir,
My utl gamma reconnect voltage setup is 11.8. I am using pcu mode.
At night (when I am checking), my battery voltage is 12.3. When I on the main (grid) switch, the utl gamma inverter is started to run load on grid.
But say that in pcu mode, inverter run load on battery if battery voltage is greater than reconnect voltage i.e. 11.8.
Why this happens?
sag is typical Behavior of lead acid battery
Same problem.
What is the solution?
@@imtiazmallick989 lithium batteries.
Sir very very nice video
App bohut achha tare samjhate hai mere pass gamma plus
1kilo inverter hai
App se bohut kuch sikneko mila hai
Thanks & Welcome!
Smart mode m Sam k time jb solar energy km ho jayegi aur load chalane k liye paryapt nhi rahegi tb load solar aur grid milakar chalega ya sirf solar se chalega
At particular voltage points it will shift to grid.
I installed "Advon 1200" inverter but i nothing understand about their features plz explain all the features
I have changed low voltage to 11 volt but at 11.6 low voltage beep starting . My battery is 150 ah and around 40 % load running that time. Is it a problem with utl pcu (12 volt) or its normal?
Seems OK. Some tolerance is present.
Sir luminous nxg pro 1kva vs utl gama + isme konsa best'he
I'll try making videos on it.
मुझे नेक्सस 1kva/12v लेना है लेकिन उसमें पीसीयू मोड नही है बस स्मार्ट और हाइब्रिड मोड है तो क्या सही रहेगा या फिर UTL Gamma+ ही ले लूं लेकिन नेक्सस में 1200 वॉट तक पैनल लगा सकते है और UTL Gamma+ में नही ??? प्लीज बतायें
Such choices should always be made by the customer as per needs. Also check the service in your area.
Sir; I use the HYB mood but my problem is when machine backup mood gone then machine continue vibration big sound come in from inside so can u help me fix this problem, thanks
Contact service center
सर अगर हम ग्रिड चार्ज का ऑप्शन बंद न करें तथा main line kafi der tak yani ratri lagbhag 8 baje tak band rakhen aur uske bad khol de to kya aaya aam aadami ke liye theek nahin rahega.
Better use PCU mode.
bhaiya mera pcu mode hai aur battery 12v + rahte huye bhi mains me chala jata hai aur cut voltage 11v rakhe hai fir bhi plz help
check the battery. It maybe weak.
@@ZenInnovations bhai battery new h 160 ah livguard ka
Same situation with me , with a 200ah battery
I'm also facing the same issue. Commisioned on 23rd October, and proper starting date 26th October.
@@hustle119 bhai koi solution mila plz bata dijiye
mere pass luminus ka inverter h vo main grid se hi chalta rhta h 1000w solar west hi hoty rhty h m kya keru koi solution do ki mera inverter pcu ban jay
I am bring this Smart MPPT product in near future. Stay subscribed. Review is being made.
Sir I have bought Utl Gamma Plus and Only One 540 watt Mono Perc 24 volt panel. Can I place this on PCU mode ?
That's unlikely to work unless you have very less load.
Can I connect UTL 12V Gamma Plus with Waaree 540Wp Bifacial solar panel?
Check voc of panel supports or not
Sir 150w 6 soler panel 900w 1 panel ampere 8 (8×6=48) ampere Gama plus charge controller 40 ampere to kya support Karega
Yes, But better to go like this-
th-cam.com/video/_i1C4Y6Hi5I/w-d-xo.html
Hi...pls tell me how to save the settings after calibration..it seems my settings are not being saved..✌
Hit the Return (Back) Button for few seconds to exit. I will also launch Calibration video soon. Stay subscribed !!
@@ZenInnovations hi..my amaron quanta smf 120 Ah has a boost charge value of 13.8v and float voltage of 13.5v. It's written on the battery itself. Shall I follow them or go for factory values? Please let me know. Thanks in advance.
@@jerryta Following Battery Manufacturer's values are always better
@@ZenInnovations thanks for the answer. I have a doubt. Battery says boost charging @13.8v and float @13.5. On my gamma plus can I use 14.2v to 14.4v for bulk charging? I am asking this because when I set my bulk voltage to 13.8v the backup has been reduced..
Sir, HOE Error Kya hoti hai? 3 baar pcb jal chuka hai.
Sir , my led tube lights starts flickering when I am running on solar inverter. I have 2Kva 24 system utl gamma plus . I get the flickering when running smps loads. Any solution for this issue ? Thanks
Join my telegram group for detailed discussion
@@ZenInnovations Hi, May i know why Room lights flickering when gaming pc(750 watt power supply) is used in solar inverter. I have gamma plus 1kva 12v
Sorry I don't have telegram
Install, Its free.
@@ZenInnovations don't want to install bhai
Very useful information ❤️
Sir agar hyb mode on hai or solar charging ho rhi hai to kya grid se bhi charging hi rhi hogi ya ek time mai ek se charging hoti hai
It depends. On settings. Solar generation. Battery voltage etc.
@@ZenInnovations kya aisa possible hai ki bina battery charge kiye direct load chlaya ja ske
Mtlb inverter solar se mil rahi dc ko ac mai badl kr direct load chlaye (no involvement of battery)
@@mnknight7480 only in true hybrid inverter which is not available in India.
@@mnknight7480 only in true hybrid inverter which is not available in India.
I am using Gamma+ recently. Want to know what to set in Gramma+ because I am only using solar, without Grid supply. Using the Gamma+ 2600 model with two 150Ah batteries in series and 440. Watt 24v two panels in parallel,
It won't matter.
@@ZenInnovations Thanks for the fast reply. I mean I will set in which mode SMT PCU or HYB.
@@mmadevelopers that's what I said. In absence of grid, modes won't matter. Use any mode. Maybe try hyb
@@ZenInnovations Thank you. I am using two 150 Watt 12V panels in first series and then I have connected them with two 440 Watt 24V , can the 150 watt panels affect the efficacy of the 440 watt panels. Please suggest, because I didn't got any video on this issue.
@@mmadevelopers watch solar QNA ep06 & 18 where I have explained about mixed panels. The effective voltage of your panels should be same in parallel.
Sir, your video is very helpful to me. I want to know if I will set HYB mode and if the solar panel is present with sufficient sunlight then what will happen?
The load will run on the grid, battery will charge on the grid. My concern is, the solar energy will not use in HYB mode? If yes how?
I appreciate your prompt reply. Thank you so much.
Solar will be used only in case of power cut.
Thank you 🙏 so much for your prompt reply.
Sir pcu mode ma mains kab disconnect hota hai,din k time ma???
13.5v battery with 100% current.
@@ZenInnovations thank u sir
@Tech Sandeep main aik solar battery luminous ka aur hybrid mode ka solar inverter lena chahta hoon taki mere battery ka charge din me khatam na ho night me youse karo iske liye luminous me koyee solar inverter ata hai
th-cam.com/video/V2J2il91kyc/w-d-xo.html
Sir ye utl gama plus 12 v kitna load utha skta h please btana
th-cam.com/video/BVCy8TO3720/w-d-xo.html
@@ZenInnovations sir mnye dekha h isko m ye puchna chhta hu ki gama + ak sath kitna watt ka load utha skta h
@@mathscurrent4995 700w approx. Resistive.
@@ZenInnovations thanks sir
Sir letus gaama model pe setting ki video banaiye 1kv 12volt
Already made.
Can I use 24v and 330watt's 3 panel with utl gamma+
Yes.
@@ZenInnovations I have 1kv gamma plus with single 200Ah battery
Still can I use??!
th-cam.com/video/pleFXQMESpA/w-d-xo.html
After giving the IPS line, many mobile chargers were damaged. What is the way to prevent mobile charging?
Query unclear.
Solar se charging ke time pe boost charging kam karta hey keya?
That function is irreverent for solar.
Solar charging settings is separate.
@@ZenInnovations OK thanks
Sir is there any alarm before battery full empty?
Yes.
Sir I disconnected one panel and it show same amp and voltage.again I disconnect another panel show same amp and voltage.I hope panel is ok
I will make panel testing videos on this channel. Stay subscribed!
In the meanwhile you can compare Panel voltages with Sticker spec mentioned in the back of panel.
Too good! Very informative
Please create a video on Havells solar PCU 850/1100va
দাদা আমাকে বলুন গ্যামা প্লাস Inviter এমন কোন সিস্টেম আছে, রাতে মেন অন রেখে ব্যাটারি আগে শেস হবে পরে মেন চালু হবে। জানাবেন ।
English or Hindi pls.
Boost chg k samne vali green light on ha usko kya kare?
off krdo jada amere se charge hogi advance setting me check krlo boost me kitna set hai
Hi! Your videos on UTL Gamma Plus Solar Inverter and others are excellent, informative and very useful. Thank you.
I have a query. I run my UTL Gamma PLUS in SMT mode. On bright sunny days, the inverter turns the mains on (screen turns bright orange) and “SPV Amp” gets down to zero (with “SPV Volt” ~59.4). In addition, there is a screen that says “SPV Hi”. Do I need to change any particular setting? I have two 300 Watt solar panels connected in series. The DC current comes from the solar panel to the inverter via a 16 A circuit breaker. The circuit breaker does not get off during “SPV Hi”. I connected two batteries of equal capacity in parallel to the inverter. I would be thankful for a solution to the problem.
I am surprised your unit did not blow up like this one-
th-cam.com/video/q1OEGGb2W4Y/w-d-xo.html
@@ZenInnovations I connected the panels in parallel and it solved the issue.
Sir mere pas utl Gamma plus inverter hai Livfast ki solar battery and 325watts ke panel. Neeche maximum 6.5 amp hi ate hai. Battery full charge kisi-2 din hi hota hai. 2 maheene to sab kush sahi chala abhi battery sham ko hi low ho jati hai. Kya is trah se battery khrab ho skti hai agr kafi dino ta full charge na ho
Pls Increase Panels. 325W is not enough.
Sir am currently using Luminous 200Ah solar battery with Utl gamma+. My full charge of battery goes between 14.2- 14.3 volts.
Also in smart mode, during evening till mains is reconnected, battery charge comes down to 12.5.
Is it normal?
Yes. Normal.
@@ZenInnovations sir will it affect my battery DOD or anyway reduce its life?
No. Assuming Battery standing voltage is 12.6v, the 12.5 is pretty much full charge.
@@ZenInnovations thank you sir.
This battery voltage is confusing. Battery is 12V but full charge goes upto 14.3V . Confused on what volts the battery can be said to be discharged by 80%
Yes. lead Acid batteries are slightly hard to judge. However stay subscribed, dedicated videos are coming on the topic !
Sir plz ek video 1kva utl gama plus 12v or 1kva plus nexus soler pcu ka comparigen video bnaye
Sure, if I get such a product.
@@ZenInnovations thanks sir i wait for u this video
Off grid system me without electricity par boost charging on karne par solar charging speed badhegi
No
Hello
Mai UTL Gamma plus 12 volt use kr rha hu, solar panel 165x3 hai, aur 150Ah ki tubular battery hai,
Kis mode par Gamma Ko rakhu?
Mujhe bijli bill kum krni hai
Watch the above video pls.
Difference between gamma and alfa series inverter?
Alpha plus has a heavier build
@@ZenInnovations I expected a more technical reply like difference in power factor etc
@@singhparambir Even the companies manuals don't disclose. How can a youtuber say?
@@ZenInnovations What is the maximum load you have been able to put on UTL 3KVA ALFA?
@@singhparambir I don't have one.
Please make one video for sigma plus modes..
Due to ur bones tip I m subscribed ur Chanel..
Reconnect volt kese set hoga bhai
You can enter advanced calibration as shown in the user manual.
Guys Advanced Calibration Video has been launched !
UTL Gamma Plus Solar Advanced Calibration | Optimum Settings Explained, Each Mode In Details [Hindi] th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html
#askzen नमस्कार Sir मेरा नाम अमित कुमार है मेरा आपसे एक सवाल है और आप से उम्मीद है कि आप उसका जवाब मुझे जरूर देंगे
मेरा सवाल है कि मैं अपने सोलर पैनल को किस तरह से कनेक्ट करूं जो मुझे ज्यादा बेनिफिट मिले
मेरे पास जो भी इंस्ट्रूमेंट है उनका लिस्ट में नीचे लिख रहा हूं
1. मेरे पास 2 पैनल हैं 12 Volt ,165 वाट के जिनकी VOC 23.04 है
2. एक ट्यूबलर बैटरी है 150 AH की 12 वोल्ट
3. एक इनवर्टर है UTL Gama Plus 12 वोल्ट and Voc 45
और सर अगर मैं एक पैनल और ले लूं सेम वाट का यानी के जब मेरे पास 3 पैनल हो तब मैं इनको कैसे कनेक्ट करूं गा
Please Sir reply जरूर देना
I also have same doubt
What a explanation hats off... Keep up the good work
Thanks.
Sir, Mere Paas UTL Taqnia inverter (without solar) hai to usme HYBD/SMRT/PCU Mode me se konsa mode rakha hoga taaki battery ko Koi damage Naa ho?
Hybrid
Thanks, nice and simple explanation
You are welcome Harshal !
Bahut hi accha hai video thanks for information.
Welcome!
गिरड चार्ज ऑप्शन बंद कर देंने पर अगर रात्रि में बैटरी डाउन होती है तो किस प्रकार चार्ज होगी।
Next day with Solar energy.
PCU mode me battery reconnect voltage par load grid se chalega, morning me wapas load grid se solar par kis condition me aayega?
When 14.5v achieved on battery or 13.5v with 100% Current. This is for TUB mode.
@@ZenInnovations kindly elaborate 13.5v with 100% current
@@anuragsingh7664 means the solar current is more than enough to run load as well as charge the battery.
Advantage and disadvantage of using solar PCU vs (Charge controller + inverter)
Pls watch QNA EP1 & 2.
Good information 👍👍👍
So nice of you Bhupendra !
Nice video Zen ji for new users of utl gamma plus...
Glad you liked it SS !
हेलिएक1200पर बिडियो बनाइये
1200 nahi but 2550 pe video banayi hai-
th-cam.com/video/sW38g-AFsGA/w-d-xo.html
@@ZenInnovations 1200मोडल मे बैटरी फुल चार्ज हो जाने पर कैसे मालूम चलेगा मै ये इनवटर लिया हूँ बैटरी फुल चार्ज नहीं समझ आता है
इसपर बिडियो जरुर बनाइए
it should show FLT or float mode.
How to fix E 7 error plz solve we are in vain
Service center
@@ZenInnovations sir any other option . Sir you have any trick plz sir give me
@@Hiteshmeena123-f7m I cannot help you with physical faults. They have to be checked by expert technicians.
Maybe something is blown up. Check the fuses.
Thank you sir for advice
Sir please bus ek akhiri request.
E 7 jo cummnication error hai eska matlab bata do kya hota hai brief mein thoda bhot plz sir🙏
Awesome.. Awaiting 👍👍
Coming soon
अच्छी जानकारी दी आपने।धन्यवाद।
Thanks ji.
ग्रीड चार्ज का ऑप्शन shamshi मॉडल में आया है।
Ok.
सोलर प्लेट नही है बैटरी से चलना है कौन सा मुड़ लगाए
मेरा utl helic 1050 का इन्वेंटर है
Hyb
Nice information sir
Please sir 1 nexus inverter 2.5 kv mppt pcu pe video banaye .
Ok coming soon. Just edited it today !!
Best information sir..in short time
You're welcome.
grid charging ko off kaise kare
th-cam.com/video/6DSq_IUrJ0Q/w-d-xo.html
Bhai bypass kese kre
th-cam.com/video/xeicZ9XLTew/w-d-xo.html
@@ZenInnovationshybrid mode mein agar solar generation acha hai fir bhi grid use hogi?
Happy with your class
Gee! Thanks.
मेरे पास 660 165 k 4 पैनल लेलिन बैटरी चार्ज नही होती नाउ बैटरी ह 200 ah
Depends on load, settings.
Awaiting for your video sir😊
Very soon
Very good and informative
Thanks
Good explanation 👍👍
Thank you 😃
1) Upto which level, battery is charged in SMART mode when grid charging is off (full charged or 30% charged).
2) Do auto shifting of load from main to solar happens in HYBRID mode ?
3) Which Mode is best for this PCU for savings and battery backup.
Using: Solar UTL Gama PCU
Watch the video carefully.
Nice information..Thanks
Glad you liked it Prasanth !
Best very useful information sir 👍🏻👌
Thanks and welcome
Mera only solar se chlta no electricity kon sa mod apply kaaru
Any
Battery bhi hai Bina mode ke bhi chla skte h