Hey thanks for the video, I am an Electrical Field Engineer, I understand the electrical terminology. However seeing the actual Motor Control Breaker and unit really paints a bigger picture. Allowing me to understand the technician side of the work making it easier for me to understand his side and explain it better in my side. Both fields of study are very important in the Field. Thanks a lot again.
Excellent videos!! Thank You! I am surprised that at my work none of the crew wear Ppe and we deal with 277-480 volts !! I have learned more from you In 10 minutes than I have in a semester or any journeyman at work.
That level of PPE is unnecessary at voltages of 480 and lower. I have only suit up like that when dealing with higher voltage busses as an industrial electrician. With that being said, working in an horizontal panel like in the video does present additional safety concerns as he is work over top of the live lines.
Just a tip. when you test the line side power or any power make sure that you pull both leads of the meter off so you do not carry over an arc when checking the other phases. Just a tip to keep you safe.
I was not aware of this hazard. I'm a newbie electrician and would like to get more knowledgeable on working/troubleshooting in panels along with associated hazards. What's a good online resource or book for this topic? That all covered in NFPA 70e? I haven't delved into that area much. Thanks
Thanks for this video. I went to a 5 yr apprentice program and this type of stuff they don’t teach. Should be able to learn on the job but maybe you cover once than just get stuck doing wire pull or cable tray for 2 years at a data center.
Great video, thank you for taking the time to make this. In the field, for the sake of time, I would do more half-splitting when checking for voltages. For example, I would have started by checking for mains voltage right at the starter, and only gone back to the breaker if I didn't have power at the starter itself.
Thorough troubleshooting, but it would have been much safer to test for any motor wiring shorts to ground before going for a motor start. Glad to see you promoting proper selection and use of PPE.
Your awesome videos are very helpful. How do motors designed for both wye and Delta configurations change/switch from starting wye to running Delta? Please and thank you.
Wow, amazing explanation sir, I'm getting, or should I say, I'm learning a lot with this presentations. Thank you very much for sharing this, and for your time and dedication on doing this videos. God bless.
Great video ! It would be nice if you could do a demo video on how the Auto function works with a common problem like PLC signal missing or any other signal problem. Very good job showing the hand function of the motor! Will definitely check some of your future videos!
Ive had to check a lot of these. I would check the overload for tripping first. Then the 480 V fuses and then the motor for grounds. I found that rarely did the control circuit had problems.
Hello. Why did you test closed contact by measuring both 95 and 96 from holding contact? Is there any other way to measure it without measuring it from holding contact? Thank you for your very helpful videos
very good video the only thing that I would recommend is always to use the RED in the hot and the black always to ground. when troubleshooting 24v this can cause read errors for technicians
Doesn’t matter when measuring AC. I suggest a basic electrical theory class for you!! Besides if he were measuring DC it would simply put a - before the number. No big deal.
Appuraj, Thanks for commenting on the video. we will be putting out more content regularly. we are currently trying for once a week. There will be a new VFD video coming out tomorrow morning, so stay tuned.
I have 4 mixer motors at a WWTF. I have had to turn the yellow amp adjustment from 8 to 14 amps to keep them running with out tripping. 1 of of them however now runs for 1-3 mins then trips everytime. Pulled and megged motor. It is good. Voltage is good and consistent with other mixer motors. I have not seen Amps above 7 on anyof the motors including the one tripping. Any suggestions? Going in circles with Evoqua. Plant is 1 year old. All ran good first 6 months then developed issues after that.
277 volts 554 volts. i wonder if they will cause motors to burn up and started to go out faster kinda like the 120 volt incandescent lightbulb, and most houses are at 127-130 volts.
Really good video...just an observation looks like it's permissible in the US to use probes with excessive metal showing ? This would be shunned in the UK although it does occur here amongst some pros.
Thank you for your comments. Requiring test equipment and overall electrical equipment to be finger safe is much further along in the UK and in the rest of Europe than in the US. I think there is some movement in that direction, but we are not there yet.
Good video - as likely mentioned below, you need to check that all phases are fully pulling in on the contractor/starter. An apprentice will learn this VERY quick the first time they replace a motor only to find out it's a bad contactor. :D
Some of our motor controllers have permissives which make it harder to troubleshoot. Especially in our galley where the control circuit is tied into fire switches, dampers, gaylord wash panels which has its own circuit, and fire pull down switches. Finding shorts is a nightmare where no indication of burns can be found, only thing you got is blown control circuit fuses. Thats why its good to learn to read electrical schematics and diagrams.
Walter, circuit energize and pulls in the contractor immediately when powered. I have wired in multiple push button stations and buttons have no control after wiring in multiple push buttons. I have a time delay and a latching relay. I was running into a situation where I could not take my finger off the start button. Now it is continuous. I traced wires and everything seems to be in order. Could a relay be burned in ?
Somehow you either have power from your start buttons supplying your coil when the buttons should be open, or you holding relay is closed and immediately energizes the coil. Pull the jumper from the coil to the holding contact off. Turn on power. If the coil closes then the problem is on the start button side of the circuit. If the starter does not start then the problem is on the holding side of your circuit.
I'm sure this is a dumb question, but when testing the hand mode switch and start push button, I see the black lead you were using but where was the red lead?
@nella003, the lead was on the neutral from the 120 volt transformer. You can see where my leads are at the 5:49 mark and the black lead is on terminal 96 which is the neutral from the transformer feeding the Overload. That is where my other lead was in the 4:44 mark.
good video... as he covered all the steps. If he had checked across the NC contacts after he had checked both sides and received his control voltage then he would have known that the NC contacts were open. If it was closed he would have received 0VAC. Also I don't know what level is this but I think it would have been helpful if he explained what the "holding contacts "were and there purpose.
parmathwal99, the voltage across the Normally Closed Stop button would have the same potential on both terminals, so it will not register on a meter measuring between those two points. But if you measure to the neutral at the transformer, or before the tripped overload, to the Stop button you will have 120 volts. Remember that you will still have voltage at the stop button and it can still shock you but you won't see voltage on your meter if measuring from a point with the same potential.
Thanks for commenting madfrogs! On several of the videos we show the schematic at the same time I am going over the physical wiring. Check out this for an example of what I am talking about. th-cam.com/video/kHbXbK7S188/w-d-xo.html. Also, the video coming out this week will also have a schematic and live wiring example of a forward reversing starter.
Good information. I was wonder if you can answer this question for me. I have a 400v coil ABB DOL Starter. I keep getting different information from other people out in the field. Main isolation switch was burnt out on 2 phases, I fitted new isolation switch and found starter to turn on by itself, so I fitted new DOL starter aswell with overload. Breaker tripping. I have tested motor phase to Earth and getting 30.06 ohms. Other companies have looked at it and can't get it fixed. I feel the motor is leaking to earth, however other people I have talked to say that is normally reading . I was always taught you should not have a reading going to earth open circuit good, closed circuit bad. Any information would be appreciated.
@@AccessToPower Thanks for replying back to me. That is what I thought, I was correct and the other people where wrong. One other question, I forgot to mention in last statement. The old switch was was pretty old so upgraded it to a new starter switch with a limit switch connected to door so it stops motor when door is open. I have wired switch to 95 and other wire to a2 of contactor. Does that sound correct and one other thing was there is no neutral connected and main power switch
ian fraser i usually don’t add any control switching to the OL side of the control circuit besides the OL contact, but there isn’t really anything wrong with doing that. It should work, but without seeing a schematic of your control circuit, it’s hard for me to advise you. Please use caution and be careful.
so the nuertral/fuse went out and I know you said it came from the motor. How do you ensure that the fuse/neutral doesnt cause the trip to happen again?
It is the overload that tripped on the neutral side of the starter coil. It is not a fuse. This overload is set to protect the motor from drawing more current than it is rated for. This is to protect the motor from overheating and eventually failing. You will want to verify if the motor is operating within acceptable parameters. If it isn’t, the problem is not the overload, but most likely the motor. Or the load the motor is operating is to great for the motor itself.
I just had to diagnose a starter where the coil in the contacter wouldn't release. There were three disconnects with stop/start controls. On one of the disconnects, the hot of the stop button broke off and was making contact with the line side of the start button, bypassing the stop buttons
Questions??? I wish i could send a photo on here ,, 3 phase motor will not run if i hit the forward or reverse button yet it will run if i manually push in the starter??
@@AccessToPower yes 240v 3 phase machine it has a start ,forward ,reverse , stop in front and rear i have tested alll buttons and the only saftey estop too . The starters both have all 2 legs at top but do not pull in when any bottons pushed . The machine will run if i push in manually, there is big pass through over load im going to jump it out and see if it will run . The nigjt shift says it just stopped working . It is a very old set up FURNAS ESP 100 22HS+32A STARTER SETUP , YOU CAN SEE pics online , im wondering if that overload inside is bad , again the wires pass through it like an amp clamp , i will jump the 2 smaller wires that go back to the starter n see if runs . Cannot get why the push buttons wont pull in either direction, really a simple old set up i suspect inside the overload may be stopping it , it resets, but still nothing
@@AccessToPower and i did as i said jumper out the overload and it works it must be fried inside they had one coil jam a month ago i cleaned the contacts they are old n big .may time to hook up new started but its a rarely used machine .
@Angel----You will feel a moment of intense pain and then will fall in the direction of the missing leg.How unfortunate that with the suit of armour he as decked himself out with that it blows off his leg,can't win them all.
Very informative video! I loved the way you start from selecting the appropriate PPE before beginning your troubleshooting and the way the you undertake your measures problems solving by following the troubleshooting steps which is ABCDE. The problem with this wonderful video was that we cant see clearly what you're reading and how your turn your nob to either; Voltage, current and ohms when digging for the neutral line that was missing in the circuit.
I would suggest testing for a short (grounded conductor) or megging the motor first before turning the HOA to hand or pressing the start button....good video though!👍
Hi Dark Knight. Toward the end of this video th-cam.com/video/kHbXbK7S188/w-d-xo.html I go over how an overload turns off a motor by breaking the neutral to the starter coil.
This video should be used to train any motor controls tech. Took me years to get to this point, this would’ve saved a lot of trial and error.
Me as well. I spent 12 years as a locomotive technician and had to learn a lot on my own. Good video.
this is one of those rare gems you find every once an awhile. thank you so much for this video walter!
Hambone. thanks for your very generous comment. it's very much appreciated!
Hey thanks for the video, I am an Electrical Field Engineer, I understand the electrical terminology. However seeing the actual Motor Control Breaker and unit really paints a bigger picture. Allowing me to understand the technician side of the work making it easier for me to understand his side and explain it better in my side. Both fields of study are very important in the Field.
Thanks a lot again.
Excellent videos!! Thank You! I am surprised that at my work none of the crew wear Ppe and we deal with 277-480 volts !! I have learned more from you In 10 minutes than I have in a semester or any journeyman at work.
That level of PPE is unnecessary at voltages of 480 and lower. I have only suit up like that when dealing with higher voltage busses as an industrial electrician.
With that being said, working in an horizontal panel like in the video does present additional safety concerns as he is work over top of the live lines.
I mean I agree we don’t use that much PPE either but if you follow OSHA this is what you get
You have definitely earned my subscription! Seeing the troubleshooting process "step by step" really made the knowledge click for me. Great job
Thanks, I'm a field testing tech, but I have long ways to go. This helps me that's why I watch your videos.
Glad these videos are helping you. I appreciate the feedback
Well I must say this is the most informative video I have every seen. With hand on on demo. Thanks
Thanks for the great comment!
Dude Thanks for the call out on the NFPA cat levels & what it needs to be compliant.
Just a tip. when you test the line side power or any power make sure that you pull both leads of the meter off so you do not carry over an arc when checking the other phases. Just a tip to keep you safe.
I was not aware of this hazard. I'm a newbie electrician and would like to get more knowledgeable on working/troubleshooting in panels along with associated hazards. What's a good online resource or book for this topic? That all covered in NFPA 70e? I haven't delved into that area much. Thanks
Read the NFPA70E handbook that will get you started in the right direction.
Thanks for this video. I went to a 5 yr apprentice program and this type of stuff they don’t teach. Should be able to learn on the job but maybe you cover once than just get stuck doing wire pull or cable tray for 2 years at a data center.
I agree. Thanks for leaving the comments. Glad the video is helpful
Great video, thank you for taking the time to make this.
In the field, for the sake of time, I would do more half-splitting when checking for voltages. For example, I would have started by checking for mains voltage right at the starter, and only gone back to the breaker if I didn't have power at the starter itself.
Chris Lawson great point. This will spread up the trouble shooting process.
Just another tip, always check the leads to your meter and make sure there are no nicks in the conductor insulation
One time I was testing voltage, 90vdc, found out meter was bad. I check on known voltage to check meter.
Thank you for this video. I wish school focused on this topic, but I’m sure my new job will train me in this aspect.
Thorough troubleshooting, but it would have been much safer to test for any motor wiring shorts to ground before going for a motor start.
Glad to see you promoting proper selection and use of PPE.
Your awesome videos are very helpful. How do motors designed for both wye and Delta configurations change/switch from starting wye to running Delta? Please and thank you.
Awesome video! Just wish you can see the meter display while doing the voltage checks. Will definitely check out some of your other videos.
thanks for the comments. I appreciate the feedback.
Nice video. After testing if voltage at coil. Shut down disconnect wires to coil and ohm coil. Sometimes it's bad.
Wow, amazing explanation sir, I'm getting, or should I say, I'm learning a lot with this presentations.
Thank you very much for sharing this, and for your time and dedication on doing this videos.
God bless.
Great video ! It would be nice if you could do a demo video on how the Auto function works with a common problem like PLC signal missing or any other signal problem. Very good job showing the hand function of the motor! Will definitely check some of your future videos!
Sire please how can I troubleshoot an Smc flex soft starter tripping on fault 18 no load. Please help me out. Thank you.
What a good video and nice gentleman. Thank you very much.
Super educational very informative. Do you have some of the best videos on TH-cam for electrical applications. Thanks
Great video! My instructor recommended watching.
Ive had to check a lot of these. I would check the overload for tripping first. Then the 480 V fuses and then the motor for grounds. I found that rarely did the control circuit had problems.
Finally got the right lesson. Very simple and important
Such a gem of a video
Hello. Why did you test closed contact by measuring both 95 and 96 from holding contact? Is there any other way to measure it without measuring it from holding contact? Thank you for your very helpful videos
very good video the only thing that I would recommend is always to use the RED in the hot and the black always to ground. when troubleshooting 24v this can cause read errors for technicians
Doesn’t matter when measuring AC. I suggest a basic electrical theory class for you!! Besides if he were measuring DC it would simply put a - before the number. No big deal.
my comment was for technician on control system and not for just a simple electricians
@@lalotrbeca so let me get this right....What you are saying is that your comment was pointless?
Awesome video, awesome channel! You're truly changing lives with sharing your knowledge
Jake Lesperance thanks for your comment. I appreciate it.
Excellent video,many thanks for this wonderful information
Very good video, please continue 🎉
Before testing to ground it is always good practice to test ground to ground to make sure you have a good ground
Thats stupid how are you going to measure ground to ground when your not sure if you have a good ground
That's rather useless. There's no potential either way whether you have a good ground or not. You will see 0 volts in both instances... Nice try
Test the resistance on the ohms settings. Come on lads. Use your nogging
@@bendoherty7721 still doesn't yeild reliable results as a low resistance does not garantee current carrying capability.
Thank you. I'm a new mechanic. i've learned a lot from your videos.
Great tutorial video and very informative .Thank you
When testing power to the hand off auto did you go to power to ground?
Great video. Please also do a video in trouble shooting VFD panels
Appuraj, Thanks for commenting on the video. we will be putting out more content regularly. we are currently trying for once a week. There will be a new VFD video coming out tomorrow morning, so stay tuned.
great video Walter.
Thanks a bunch bro
Absolutely amazing quality video and explanation.
Thank you
When you check for power on the switch did you have the other rod on ground cause I just see the black one?
I have 4 mixer motors at a WWTF. I have had to turn the yellow amp adjustment from 8 to 14 amps to keep them running with out tripping. 1 of of them however now runs for 1-3 mins then trips everytime. Pulled and megged motor. It is good. Voltage is good and consistent with other mixer motors. I have not seen Amps above 7 on anyof the motors including the one tripping.
Any suggestions?
Going in circles with Evoqua. Plant is 1 year old. All ran good first 6 months then developed issues after that.
277 volts 554 volts. i wonder if they will cause motors to burn up and started to go out faster kinda like the 120 volt incandescent lightbulb, and most houses are at 127-130 volts.
Really good video...just an observation looks like it's permissible in the US to use probes with excessive metal showing ? This would be shunned in the UK although it does occur here amongst some pros.
Thank you for your comments. Requiring test equipment and overall electrical equipment to be finger safe is much further along in the UK and in the rest of Europe than in the US. I think there is some movement in that direction, but we are not there yet.
Good video - as likely mentioned below, you need to check that all phases are fully pulling in on the contractor/starter. An apprentice will learn this VERY quick the first time they replace a motor only to find out it's a bad contactor. :D
What is the method for checking?
*contactor not contractor
Thanks for video, question how can someone find a ahu motor size from the starter in a 460 volt panel box?, thanks
GREAT WORK MY FRIENDS
Wow, want more control panel troubleshooting Video 💖💖💖
Some of our motor controllers have permissives which make it harder to troubleshoot. Especially in our galley where the control circuit is tied into fire switches, dampers, gaylord wash panels which has its own circuit, and fire pull down switches. Finding shorts is a nightmare where no indication of burns can be found, only thing you got is blown control circuit fuses. Thats why its good to learn to read electrical schematics and diagrams.
That does sound like a nightmare. Honestly I feel like we are using flawed systems in the us at least some of the old ones.
Question, why is your neutral and ground not color coated, they are both red ?
Thanks
Walter, circuit energize and pulls in the contractor immediately when powered. I have wired in multiple push button stations and buttons have no control after wiring in multiple push buttons. I have a time delay and a latching relay. I was running into a situation where I could not take my finger off the start button. Now it is continuous. I traced wires and everything seems to be in order. Could a relay be burned in ?
Somehow you either have power from your start buttons supplying your coil when the buttons should be open, or you holding relay is closed and immediately energizes the coil. Pull the jumper from the coil to the holding contact off. Turn on power. If the coil closes then the problem is on the start button side of the circuit. If the starter does not start then the problem is on the holding side of your circuit.
I'm sure this is a dumb question, but when testing the hand mode switch and start push button, I see the black lead you were using but where was the red lead?
A schematic of the circuit being tested would be helpful. And starting around 4:44 I don't see where you are putting the red test lead.
@nella003, the lead was on the neutral from the 120 volt transformer. You can see where my leads are at the 5:49 mark and the black lead is on terminal 96 which is the neutral from the transformer feeding the Overload. That is where my other lead was in the 4:44 mark.
good video... as he covered all the steps. If he had checked across the NC contacts after he had checked both sides and received his control voltage then he would have known that the NC contacts were open. If it was closed he would have received 0VAC. Also I don't know what level is this but I think it would have been helpful if he explained what the "holding contacts "were and there purpose.
Great vid sir! Would the stop button give a voltage across the Stop button on a tripped Overload?
parmathwal99, the voltage across the Normally Closed Stop button would have the same potential on both terminals, so it will not register on a meter measuring between those two points. But if you measure to the neutral at the transformer, or before the tripped overload, to the Stop button you will have 120 volts. Remember that you will still have voltage at the stop button and it can still shock you but you won't see voltage on your meter if measuring from a point with the same potential.
@@AccessToPower its For an exam question where they ask what device will measure 120v if the OL trips in the control circuit
@@US-Warrior I see. Both sides the stop button will still read 120 volts when measured to ground or the neutral before the OL contacts.
Great videos, thank you! Is there any way we can see the wiring schematics? I'm sure it's basic, but I'm new, learning and curious. :)
Thanks for commenting madfrogs! On several of the videos we show the schematic at the same time I am going over the physical wiring. Check out this for an example of what I am talking about. th-cam.com/video/kHbXbK7S188/w-d-xo.html. Also, the video coming out this week will also have a schematic and live wiring example of a forward reversing starter.
Great information and well taught
follow the power. that easy. great vid!!
Great video. Do you plan to post more videos.I hope so.
Yes, I hope to make more videos. Thanks
Good information. I was wonder if you can answer this question for me. I have a 400v coil ABB DOL Starter. I keep getting different information from other people out in the field. Main isolation switch was burnt out on 2 phases, I fitted new isolation switch and found starter to turn on by itself, so I fitted new DOL starter aswell with overload. Breaker tripping. I have tested motor phase to Earth and getting 30.06 ohms. Other companies have looked at it and can't get it fixed. I feel the motor is leaking to earth, however other people I have talked to say that is normally reading . I was always taught you should not have a reading going to earth open circuit good, closed circuit bad. Any information would be appreciated.
30 ohms to ground from the motor windings is Not normal. If it was megaohms the motor might still be ok, but ohms, the motor is bad.
@@AccessToPower Thanks for replying back to me. That is what I thought, I was correct and the other people where wrong. One other question, I forgot to mention in last statement. The old switch was was pretty old so upgraded it to a new starter switch with a limit switch connected to door so it stops motor when door is open. I have wired switch to 95 and other wire to a2 of contactor. Does that sound correct and one other thing was there is no neutral connected and main power switch
ian fraser i usually don’t add any control switching to the OL side of the control circuit besides the OL contact, but there isn’t really anything wrong with doing that. It should work, but without seeing a schematic of your control circuit, it’s hard for me to advise you. Please use caution and be careful.
@@AccessToPower Thanks for the quick reply. Have a good weekend and stay safe
Great video 👍
Yeah safety is first, but in my type of business we wouldn’t get anything done with all that on...thanks for the video
Stickeler Winner where do you work the burn treatment center?
That's OSHA for ya
This is very useful thank you 😊
Thank you, I appreciate your comments. Glad the contact was useful
so the nuertral/fuse went out and I know you said it came from the motor. How do you ensure that the fuse/neutral doesnt cause the trip to happen again?
It is the overload that tripped on the neutral side of the starter coil. It is not a fuse. This overload is set to protect the motor from drawing more current than it is rated for. This is to protect the motor from overheating and eventually failing. You will want to verify if the motor is operating within acceptable parameters. If it isn’t, the problem is not the overload, but most likely the motor. Or the load the motor is operating is to great for the motor itself.
I just had to diagnose a starter where the coil in the contacter wouldn't release. There were three disconnects with stop/start controls. On one of the disconnects, the hot of the stop button broke off and was making contact with the line side of the start button, bypassing the stop buttons
Nice job
Do you have the diagram for the motor 480, 3-phase start/stop?
Are u using ground to check controls
Questions??? I wish i could send a photo on here ,, 3 phase motor will not run if i hit the forward or reverse button yet it will run if i manually push in the starter??
Sounds like there is a problem with the control wiring
Do you have power to your coil on the starter while pushing either the Forward or the reverse buttons?
@@AccessToPower yes 240v 3 phase machine it has a start ,forward ,reverse , stop in front and rear i have tested alll buttons and the only saftey estop too . The starters both have all 2 legs at top but do not pull in when any bottons pushed .
The machine will run if i push in manually, there is big pass through over load im going to jump it out and see if it will run . The nigjt shift says it just stopped working .
It is a very old set up FURNAS ESP 100 22HS+32A STARTER SETUP , YOU CAN SEE pics online , im wondering if that overload inside is bad , again the wires pass through it like an amp clamp , i will jump the 2 smaller wires that go back to the starter n see if runs . Cannot get why the push buttons wont pull in either direction, really a simple old set up i suspect inside the overload may be stopping it , it resets, but still nothing
@@AccessToPower they need to make this so i can add photos n show more .. but i know its only youtube ha
@@AccessToPower and i did as i said jumper out the overload and it works it must be fried inside they had one coil jam a month ago i cleaned the contacts they are old n big .may time to hook up new started but its a rarely used machine .
Great video. How you check when you lose a leg
@Angel----You will feel a moment of intense pain and then will fall in the direction of the missing leg.How unfortunate that with the suit of armour he as decked himself out with that it blows off his leg,can't win them all.
Hello sir. Does the control circuit has its own power supply? Thanks!
EIM - NCII Alaktrician the control circuit has a control transformer fed by the main 480 volt circuit in the panel.
@@AccessToPower Thank you for your answer sir! Your tutorial surely helped.
This is a very good point to point video. Thank you.
Very informative video! I loved the way you start from selecting the appropriate PPE before beginning your troubleshooting and the way the you undertake your measures problems solving by following the troubleshooting steps which is ABCDE. The problem with this wonderful video was that we cant see clearly what you're reading and how your turn your nob to either; Voltage, current and ohms when digging for the neutral line that was missing in the circuit.
Tim I have a LC1 D12 from Telemecanique that I have isolated and I get resistance reading on the coil leads, does it mean the starter is bad?
You should have resistance across the coil of the starter.
Wondering if you could do a video on megging out a motor? Thx
Thank you for suggesting the video for megging a motor. I will try to do that soon.
That was awesome! Thank you
Thank you
Does anyone have a wiring diagram for this scenario?
Thank you for the video,
Your welcome
Great video man!!
Excellent video
Thank you very much!
Appreciate the video! Thank you!
Great job! Thank you so much!
Hi, I like your video. Thanks
First thanks but what todo if overload is ok
great video! learned alot!
Very good video. ❤
Excellent vid
Thank you for your comments. I am glad you found the video helpful.
Why are the contacts labeled 95 & 96 and 97 & 98. It appears random. Why not 1 & 2 and 3 & 4?
Very helpful....please make more
Good video very helpful Big T
Thank you for share your knowledge. Great video
I would suggest testing for a short (grounded conductor) or megging the motor first before turning the HOA to hand or pressing the start button....good video though!👍
great guide for biginers. thanks
Do you have a video on how the overload works? Still not getting your answer to my questions.
Hi Dark Knight. Toward the end of this video th-cam.com/video/kHbXbK7S188/w-d-xo.html I go over how an overload turns off a motor by breaking the neutral to the starter coil.
Great video
Don't these motor starter have an overload indication to show that overload had tripped?
great video, thank you for your expertise!
Walter, I assume you're still buying C-H controls from Willie Electric?
Superb. Thank you
Wish i cud see the readings... amazing video
can you show schematic of it and in details whats connected to what
Axiomteck see part 2 where I show the schematic th-cam.com/video/1J36SgPABFo/w-d-xo.html
Very useful.. Thanx...
Brilliant please make more videos of installation too. Thank you
Good video. Very informative. I may have done it a bit differently, but a good informative video.