How to Properly Diagnose a Failed TXV

แชร์
ฝัง
  • เผยแพร่เมื่อ 11 ต.ค. 2018
  • Bryan gives a masterclass to Kalos Techs on why TXV/TEV valves are misdiagnosed, how to properly diagnose a failed TXV, and how thermostatic expansion valves work.
    TXVs are designed to maintain constant superheat, and many people suspect TXV issues when the suction pressure is low. When technicians see low suction pressure, many of them may add charge and then realize that the TXV throttles down to maintain constant superheat. So, they condemn the TXV even though it's working as it should because they simply don't understand how the TXV works.
    TXVs generally have an external equalizer, which supplies a closing force to the TXV. The spring also supplies a closing force, but the sensing bulb applies an opening force. The size of the TXV's orifice depends on the combination of the opening and closing forces. There is a fixed amount of refrigerant inside the sensing bulb, so the hotter the bulb, the more the refrigerant expands. The more the refrigerant expands, the more opening force it will exert on the TXV. When the bulb doesn't have enough (or any) refrigerant, it can't exert enough force on the valve to open it. However, you may be able to replace the powerhead without condemning the entire TXV.
    The TXV needs a full line of liquid coming into the valve for it to work properly, so we need to check the subcooling or look at a sight glass (in the case of refrigeration). We can get vapor in the liquid line from restrictions or excessively long lines.
    TXVs may also have an inlet screen, which can become restricted and prevent the proper amount of refrigerant from reaching the valve. The TXV also needs a proper pressure drop (about 100 PSI); without that pressure drop, the TXV can't do its job properly.
    When the suction pressure is low, the technician should take the subcooling and superheat inside and outside. The goal is to look for the temperature differences between the inside and outside measurements. If the differences are drastic, then there could be a restriction somewhere (often in the line drier or an airflow restriction).
    If suction pressures are low and the temperatures are close to freezing, the next step is to take the remaining measurements of your 5 Pillars (superheat, subcooling, delta T, suction pressure, and head pressure). Use those to diagnose the problem; the superheat at the evaporator coil should be 6-14 degrees, and it's usually not productive to condemn the TXV over a couple of degrees due to the possible inaccuracy of our tools. Instead, it's more likely that you have an airflow problem.
    However, if the outdoor superheat is 27 degrees and the indoor superheat is 23 degrees, then you'll have to check for restrictions. If you don't have any restrictions (which may cause low head pressure) and have sufficient subcooling and pressure drop, then it would be safe to condemn the TXV.
    When taking measurements, make sure your test instruments are calibrated and work properly. Otherwise, you could misdiagnose a TXV problem.
    Moisture, carbon, and other forms of contamination can lead to inlet screen restrictions and possibly even premature TXV failure. If the superheat is high, you can temporarily open the valve more by increasing the suction pressure by placing the bulb somewhere else. NEVER open the valve more if you have low superheat! If you have low superheat, try to see how well the bulb is connected to the suction line; for the TXV to work properly, the bulb needs to be strapped in a way that makes it have good contact with the suction line. In cases where the bulb needs to be insulated, make sure it is insulated.
    Read all the tech tips, take the quizzes, and find our handy calculators at www.hvacrschool.com/

ความคิดเห็น • 474

  • @petalumapapi
    @petalumapapi 5 ปีที่แล้ว +113

    I've been watching videos of you classes you're very informative I really appreciate the information you guys are awesome

    • @georgeadebesin1148
      @georgeadebesin1148 4 ปีที่แล้ว +2

      Ppppppppp pppp0pppppp pop pop pop pop pop pop pop pop ppppppp0p0

    • @petegalvan609
      @petegalvan609 3 ปีที่แล้ว

      @@georgeadebesin1148 7 up 7 I GL i8 up hmm m NM

    • @petegalvan609
      @petegalvan609 3 ปีที่แล้ว

      Blu ymp hi S Q UP

    • @samuelcuen4049
      @samuelcuen4049 3 ปีที่แล้ว +3

      BILLY ORR! You're the fucking man, bro!!!! You explain in my language. Keep it simple, realistic terms and terminology. Good looking homie

    • @billni3952
      @billni3952 2 ปีที่แล้ว

      How to know is good fully refrigerant charged walking box freezer and cooler

  • @padilla7019
    @padilla7019 5 ปีที่แล้ว +4

    Watch this video a couple of times and makes me feel good to get this knowledge about txv

  • @sterlingarcher46
    @sterlingarcher46 5 ปีที่แล้ว +23

    If only they taught me this well ... Fantastic class , sir , I wish I'd had my training with you guys 👍

  • @b1conis
    @b1conis 3 ปีที่แล้ว +14

    Very good instructor. I have 45 years experience and 20 of that with Carrier and York. I’m still learning.

  • @greentea111
    @greentea111 5 ปีที่แล้ว +27

    THis is by far the best explained txv operation and fail operation ive seen yet... THank you for the very good lesson

    • @YuShudNoe
      @YuShudNoe 4 ปีที่แล้ว +1

      Completely agree!!! 💯

  • @seandardis9409
    @seandardis9409 2 ปีที่แล้ว +1

    Excellent Brian ! You can explain the workings of refrigeration parts in an easy to understand way .

  • @billcamp8183
    @billcamp8183 3 ปีที่แล้ว +5

    Great, great class this instructor is an asset to the hvac trade. Good job.

  • @mrc6032
    @mrc6032 3 ปีที่แล้ว +9

    This guy is a great instructor. I don't really have that gift. So i appreciate anyone who can instruct/teach/facilitate

  • @Sctronic209
    @Sctronic209 5 ปีที่แล้ว +4

    I like the explanation of the bulb being the opening force.👍

  • @Rodzilla408
    @Rodzilla408 5 ปีที่แล้ว +23

    Good video I'll be watching this one a few more times.

    • @MrGarcon98
      @MrGarcon98 3 ปีที่แล้ว +1

      he is a very fast talker LOL

  • @craigspicer4296
    @craigspicer4296 2 ปีที่แล้ว +2

    This has been a great Lesson and reminder about how to do the job better on properly diagnosing the TXV.

  • @tonang33
    @tonang33 ปีที่แล้ว +7

    I am not a tech but I love learning about many things. Having a good A/C tech is important. More importantly someone who is trustworthy. I will continue to watch his videos. Thank you for your knowledge.

  • @itsnotfar
    @itsnotfar 3 ปีที่แล้ว +4

    Great information. I'm new to this stuff, so it was lots of food for my brain. You explained it in a way I could easily understand. Thank you

  • @derrickseidenberg8105
    @derrickseidenberg8105 7 หลายเดือนก่อน

    We often use your videos for our weekly training with our techs. This one was great! Thank you again for what you do for the industry.

  • @adamz4345
    @adamz4345 4 ปีที่แล้ว +1

    Very informative, I've also been a last resort to change a txv,but over the years have had a few that were the TXV valve was bad..

  • @kurtschaefflerakaclaudio4853
    @kurtschaefflerakaclaudio4853 2 ปีที่แล้ว +12

    I watch Brian to sharpen my understanding of refrigeration as it relates to automotive air conditioning.
    What a great teacher and orator. Thank you Brian for doing what you do...

    • @robertwojtowicz933
      @robertwojtowicz933 11 หลายเดือนก่อน

      You getting too long-winded with your explanation’s

  • @Bluecollarworkingman
    @Bluecollarworkingman 5 ปีที่แล้ว +2

    This is solid information. Presented and spoken well. Awesome.

  • @vernroach3413
    @vernroach3413 4 ปีที่แล้ว +2

    Most excellent and informative video with an excellent instructor.....Thank you Testo.

  • @chriscooley906
    @chriscooley906 4 ปีที่แล้ว +4

    Pure gold Bryan, So technical you really drive home the facts, I love the videos and podcasts great reminders to strive for greatness and never assume without having all the facts Thanks again.

  • @benswafford8608
    @benswafford8608 3 ปีที่แล้ว +2

    I learned a lot from this video that I can use everyday. You are a HVAC wizard.

  • @Stuart68505
    @Stuart68505 3 ปีที่แล้ว +2

    Thanks- lots of insights that are new to me. The review of the complete diagnosing procedure was also helpful. One service manager told that first thing he would do was to put his amp probe on outdoors to get an idea about how much refrigerant charge is in the system and to see if the compressor was running. I used that idea to check a new refrigerator at my apartment which was icing up constantly. The store technicians came and told me that it was improperly sloped and not draining & that’s why it was freezing. How ever it continued to freeze up. It was only drawing about 2 amps instead of the rated 6 amps under full load. They eventually replaced that new unit with another new refrigerator.
    I don’t understand why it makes a loud clicking noise every time the compressor starts up that is coming from inside the cabinet and not down at the compressor.

  • @channelcatchaser9426
    @channelcatchaser9426 3 ปีที่แล้ว +12

    Probably one of the best HVAC channels TH-cam

  • @QSSCEO
    @QSSCEO 2 ปีที่แล้ว +3

    Great video! Spot on!! The TXV has got to be the most misunderstood component of the trade.

  • @harvindersingharora3845
    @harvindersingharora3845 3 ปีที่แล้ว +6

    My teacher of the day! I have unlearned and re-learned a few things from your video.
    Thank you for the wonderful session. You added a fourth angle to my triangle.

  • @jeffreykubiak5126
    @jeffreykubiak5126 5 ปีที่แล้ว

    Thanks Bryan great video technician going possible back into field after 14 years in house maintenance. Probably watch again.Beer can cold days are long over. Thanks got your app on my phone!

  • @armandorodriguez6447
    @armandorodriguez6447 2 ปีที่แล้ว +2

    Really good lesson or over view. I’m recommending this lesson to the green hvac bros coming into our co. This will make a good tech out of the average tech filter changers and part changers

  • @bhutehole
    @bhutehole ปีที่แล้ว +3

    calling the TXV a constant superheat valve is a good trick for remembering what it does

  • @charlesdegaulle6465
    @charlesdegaulle6465 4 ปีที่แล้ว +8

    23:00
    I FEEL VINDICATED.
    I should save this video for every customer who “just wanted” their 20 year-old, never maintained attic AC in their 120 year old house “fixed” instead of replaced.

    • @Niveous23
      @Niveous23 3 ปีที่แล้ว

      or a crawlspace....

  • @brs4389
    @brs4389 4 ปีที่แล้ว

    flawless articulation of details

  • @mrV1et
    @mrV1et 11 หลายเดือนก่อน

    I subscribed to this channel because as a restaurant owner , I’ve been taken advantage of 4-6 times over the course of 4 years between my walk in cooler and freezer , ice maker and main ac unit. I now carry my own gauges and temp probes to sadly check their work. I video and picture log all my equipment to make sure they don’t “ break “ something they should be doing . I constantly ask the tech questions and their approach and results they are aiming for to verify. I collect their answers and back research info from your channel . Thanks for these videos. They are less inclined to pull a scam on me now .

  • @billymonis8978
    @billymonis8978 4 ปีที่แล้ว +7

    I just replaced a txv yesterday. It had low suction pressure about 50 psig ( R22) SH was about 45 deg. high head pressure at 400 this was after the day shift added 22. SC way high. Took some out until suction pressure started going down. then pumped unit down, couldn't get low side below 40 psig before the compressors internal bypass opened. The head pressure got all the way down to almost 0 psig. the coil was freezing up. Put the new one in and was getting the perfect cycle. Good feeling!

    • @garycox1459
      @garycox1459 4 ปีที่แล้ว

      Exactly. Tech knowledge good. Experience is key

    • @mikefreedom5612
      @mikefreedom5612 4 ปีที่แล้ว

      Head pressure 0psig?

    • @ryanjordan6144
      @ryanjordan6144 4 ปีที่แล้ว

      Billy Monis your over charged! That’s why it won’t pump down. Txv is not your problem

    • @jskipperddg80
      @jskipperddg80 3 ปีที่แล้ว

      @@ryanjordan6144 if the TXV has been starving the compressor long enough it will go out on high heat when pumping it down. Doesn’t mean overcharged!

  • @baylifehvac991
    @baylifehvac991 5 ปีที่แล้ว +18

    Awesome video. From my experience with txv is I always see the outlet of the valve with frost build up and my subcool doesn’t make since or is way to high. I know so many installers who braze with out nitrogen and years down the road this is then end result. Honestly on all my service calls are maintenance I always check for dirty indoor coils , filters, ductwork and blower wheels that will cause low air flow. God bless

    • @jericosha2842
      @jericosha2842 3 ปีที่แล้ว +1

      great comment, thank you

    • @USA-GreedyMenOfNoIntegrity
      @USA-GreedyMenOfNoIntegrity 3 ปีที่แล้ว +1

      I purged with nitrogen on all of the systems I’ve installed in the last 20 years. I still have lots of TXV failures. They are junk, engineering in the USA and poorly made in China. Greedy corporations don’t have any problem paying their suits millions.

  • @carlosportillo8863
    @carlosportillo8863 5 ปีที่แล้ว

    Very nicely explained Bryan. Thanks

  • @dergadergaful
    @dergadergaful 2 ปีที่แล้ว

    We have a Lennox unit that takes 29lbs of refrigerant and it worked perfectly fine in second stage but we were getting the typical readings of a txv valve failure, low suction. I traced the line to the condenser and saw a hell of a mess of a braising job. Traced the TXV and saw that someone had melted the copper with the torch and the pipe was pinched to the point of no airflow when tested with nitrogen. Pointed it out to the Linux tech who recommended we change the solenoid first. We changed the TXV and braised everything. Pressure tested it over the weekend checked for leaks and recharged it. Works like a charm

  • @alejandromata825
    @alejandromata825 2 ปีที่แล้ว +1

    I’ve changed power heads before only to find that the valve was restricted at the body, I’d rather just change the whole thing if time and conditions permit. Good class!

  • @alexaderreyes5945
    @alexaderreyes5945 3 ปีที่แล้ว

    Very interesting class it really helped me a lot on my Jobs thank you God bless you brother

  • @markbeiser
    @markbeiser 4 ปีที่แล้ว +1

    A note on your statement at the end about what happens if a valve core is left in the port the equalizer line connect so.
    On many valves, there is not a perfect seal around the rods the diaphragm pushes on to drive the valve open, so refrigerant inside the valve can leak through and push the valve closed.
    It will be higher pressure than the refrigerant in the evaporator coil, and has no place to go, so will force the valve too far closed.
    I ran into it a few times back when AS/Trane switched to providing aluminum replacement coils for their air handlers with copper coils.
    The coils come with no TXV, so you have to field install it, and people were not pulling the valve core out of the port.
    After starting the system up, the valve would start off forced wide open, flooding the coil, then slowly close down until the superheat was way too high.

  • @chuckdearruda6271
    @chuckdearruda6271 5 ปีที่แล้ว

    Great video! Thanks Bryan!

  • @amantek3545
    @amantek3545 4 ปีที่แล้ว

    VERY good explanation keep up the good work

  • @LongTrout
    @LongTrout 2 ปีที่แล้ว +2

    Been doing service since 87....Love the vids....It is making me a better tech and helps me hone my skills....Thanks.

  • @mrod72785
    @mrod72785 5 ปีที่แล้ว

    Thanks Bryan, good stuff.

  • @Froggin87
    @Froggin87 3 ปีที่แล้ว

    Absolutely great explanation thank you for that

  • @jspilly82
    @jspilly82 4 ปีที่แล้ว +2

    some aircons have check (one way) valves that will give some of the same symptoms as a bad txv. if you are thourough in the diagnosis it will become obvious but always use both hi and lo gauges and check system temps in lots of places. its been rare to have a check valve fail but they can give you a real hard time if your not aware of them.

  • @OldePhart
    @OldePhart 3 ปีที่แล้ว

    That was outstanding instruction. Well done.

    • @HVACS
      @HVACS  3 ปีที่แล้ว

      thanks!

  • @ernestorodriguez2711
    @ernestorodriguez2711 4 ปีที่แล้ว +2

    I am currently pretty hungover and I can’t sleep. But I just watched your video and I understood all of the information. Wow. Such a great video, I had to subscribe. I will watch again when not hungover to make sure I retain everything. Thanks so much. Great job.

  • @poopathyraaja9949
    @poopathyraaja9949 2 ปีที่แล้ว

    Awesome video 👍. Such a valuable information.

  • @kenshofalco8326
    @kenshofalco8326 2 ปีที่แล้ว

    That was an excellent presentation.

  • @chadbrown4918
    @chadbrown4918 5 ปีที่แล้ว

    Cheers. Good job Brian.

  • @nicaman96
    @nicaman96 5 ปีที่แล้ว

    Thanks for a great class

  • @vnesmuonnam
    @vnesmuonnam 2 ปีที่แล้ว

    Great lecture for TXV

  • @beardowns8050
    @beardowns8050 5 ปีที่แล้ว

    Good stuff man.Thanks! 👍🏼

  • @austinisfullpleasedontmove653
    @austinisfullpleasedontmove653 ปีที่แล้ว

    Mr. Orr here is what one would call an Hvac God. Love this dude and he has helped me through many a quandary.

  • @rastagrastag7784
    @rastagrastag7784 2 ปีที่แล้ว

    Great information.. well explained thank you👍👍👍👍👍👍

  • @UNITEDHVACSYSTEMS
    @UNITEDHVACSYSTEMS 4 ปีที่แล้ว +4

    Nice videos...
    Can understand how txv works and fails

    • @UNITEDHVACSYSTEMS
      @UNITEDHVACSYSTEMS 4 ปีที่แล้ว

      Please like to my channel also
      th-cam.com/channels/VGxieHOcnRHZqMyC8ZrWtw.html

  • @j.r.1223
    @j.r.1223 4 ปีที่แล้ว

    Great instructor!

  • @tribenitribhowan3638
    @tribenitribhowan3638 3 ปีที่แล้ว

    Explain very well, I learned a lot 👍

  • @jimmyclause847
    @jimmyclause847 4 ปีที่แล้ว

    So educative and classified lecture..

  • @iskenderbytyqi
    @iskenderbytyqi หลายเดือนก่อน

    you are the best master in my country. Republic of Kosova. Thanks for all.😇

  • @bryanharayda1975
    @bryanharayda1975 3 ปีที่แล้ว +1

    Constant super heat valve is accurate. Easiest way to check valve is measure superheat and subcool when close to or at temp. Always measure suction temp closest to TXV sensor bulb to calculate superheat. TXV, EXV, DTC valves are fun!

  • @ronyben-nachum7803
    @ronyben-nachum7803 2 ปีที่แล้ว

    Thank you very much for the wonderful explanation. Rony - from Israel

  • @BartSimpson-nr1dy
    @BartSimpson-nr1dy 3 ปีที่แล้ว

    I really miss this instrumental intro to your videos. Please consider using this tune in future videos.
    Great instructions on diagnosing a failed TXV

  • @VMac-eg7fb
    @VMac-eg7fb 5 ปีที่แล้ว

    Excellent training, super informative, thank you.

  • @josemarieantepasado5267
    @josemarieantepasado5267 5 ปีที่แล้ว

    Good day. If i may ask, i currently have a problem on an R22, 50 TR system with high superheat but with about normal suction pressure of 65psi. I've also observed that hissing sound you mentioned on the TXV and solenoid valve side. I am confused if this could be a case of a faulty TXV since my suction pressure isn't that low. I hope for your kind advice. Thank you.

  • @TheSixStringGuy
    @TheSixStringGuy 3 ปีที่แล้ว

    Great lesson, thank you sir!

  • @deonnarine4363
    @deonnarine4363 5 ปีที่แล้ว

    Great job sir , from Trinidad and tobago.
    Deon's air conditioning services here

  • @donnierobertson3088
    @donnierobertson3088 3 ปีที่แล้ว

    Great job and video like always

  • @ssantoro36
    @ssantoro36 10 หลายเดือนก่อน

    As a tech, I love these videos.

  • @Stuart68505
    @Stuart68505 3 ปีที่แล้ว

    Very helpful information thank you

  • @ronaldmelgar8907
    @ronaldmelgar8907 3 ปีที่แล้ว

    Very helpful thanks,can I have a question,it is possible to charge freon r404a while the expansion valve r22? Thats for walking freezef

  • @jasonbentley4522
    @jasonbentley4522 4 ปีที่แล้ว

    so say a unit reads 20 on suction and 140 head pressure. And when it runs for a minute it starts to over heat/rattle and cuts of the outdoor system. and your indoor unit start to freeze up at the txv but no further than the txv. could that be a sign of a bad/restricted txv valve or clogged screen?

  • @trebrehenuf
    @trebrehenuf 5 ปีที่แล้ว +43

    Learned more in 30 minutes watching than 2 years working with journeyman.

    • @chrismesser7051
      @chrismesser7051 5 ปีที่แล้ว +3

      sorry to hear that man you must of worked with some bad guys, i feel the opposite iv learned way more in the field to the point where i dont get much from alot of his videos, not bragging but alot of his material is introduction to stuff and very basic

    • @Noverificationneeded
      @Noverificationneeded 5 ปีที่แล้ว +7

      trebrehenuf .......you’ll learn even more and much faster when you put hands-on. And more still when you’re on your own, with nobody watching you. Also, this is a trade that is very cerebral and you’ll constantly learn. Like the instructor said, even a seasoned tech can misdiagnose.

    • @FlyEaglesFly19111
      @FlyEaglesFly19111 5 ปีที่แล้ว +13

      The best techs have made the most mistakes.. they learned from them and made themselves better.

    • @hvacae6904
      @hvacae6904 4 ปีที่แล้ว

      Exactly...

  • @Imwright720
    @Imwright720 4 ปีที่แล้ว +1

    My friend is taking night classes in south Florida. The instructors first language isn’t English. Poor kid can understand half of what the teacher says. I wish he had you. You are an excellent instructor.

  • @brs4389
    @brs4389 4 ปีที่แล้ว +4

    one time I suspected a kink and the line temp difference between ID and OD was like 15-20 degrees. I searched and sure enough the lineset was bent where it exited the wall cavity.

    • @jericosha2842
      @jericosha2842 3 ปีที่แล้ว

      So was the indoor temperature of the suction line more normal and the temperature of the outdoor line really low?

  • @winkhvac62
    @winkhvac62 3 ปีที่แล้ว

    Excellent training!!

  • @garycox1459
    @garycox1459 4 ปีที่แล้ว +2

    Txv is pure gut feeling. I change out 9 every summer

  • @soloch69
    @soloch69 ปีที่แล้ว

    Great video like always 🙏🏻

  • @nickdaggitt5079
    @nickdaggitt5079 ปีที่แล้ว +2

    Bryan great video as always, but ive always wondered and asked what refrigerant is used inside of a sensing bulb. It would make sense to me that the bulb would have a small amount of liquid refrigerant of whatever the system uses that its rated for but i have never been able to find documentation or get a definitive answer. Just a question ive had for 10 plus years.

  • @MrGarcon98
    @MrGarcon98 4 ปีที่แล้ว

    our teacher who had at the time little over 35 years in the trade told us that 3 degrees in HVAC is close enough and dont sweat it too too much ,,,,just cool that house LOL ,,,,specially in miami /ftlaud / etc southern fl,,,nice show

  • @Kevin-ib4gv
    @Kevin-ib4gv 4 ปีที่แล้ว

    Is there a way to test a TXV prior to installation just make sure it works properly, or does it need to be installed and under operating conditions in order to evaluate properly?

  • @passandscore_
    @passandscore_ 4 ปีที่แล้ว

    Great video!

  • @boolve
    @boolve 2 ปีที่แล้ว

    Good talk. It did exploded my head.

  • @foreverendeavors6210
    @foreverendeavors6210 3 ปีที่แล้ว

    Priceless information 👌

  • @yisroelsones4552
    @yisroelsones4552 5 ปีที่แล้ว +1

    Professional and precise and very detailed

  • @armandoacevedo932
    @armandoacevedo932 4 ปีที่แล้ว

    Thanks .excellent videos 👍👍👍

  • @billyk5107
    @billyk5107 11 หลายเดือนก่อน

    Thank you I’m working on a unit now that I have to check all this because when I got there it was frozen so I told him I would be back the next day to hook up everything again and run it properly and see what’s going on before I condemn anything

  • @rodgraff1782
    @rodgraff1782 5 ปีที่แล้ว +2

    It’s a good idea to install a 1/4” flare T at the connection for the equalizer line at the evaporator. The extra port can be used to get a pressure measurement for the actual evaporator pressure at the tail coil, where the bulb is located. This is the proper place to read suction pressure when calculating evaporator superheat

  • @juanitamulima6414
    @juanitamulima6414 4 ปีที่แล้ว

    Got some real issue with a chilled water bank system. It's a R22gass system, using ×2 Copland (6.8) hp rottary compressors and 2 TGEX expansion valves the system is a water cooled condenser. Issue here is am getting a very high head pressure even causing the relief valve to engage at 300psi (which it's labled) even besides dropping the gas level to a point were the LP switc (electronic) regards low in sync with my guages low side when I push on the contactor the head pressure doesn't seem to stop rising NOTE this is a brand new system has never worked since purchase date what would be the issue?

  • @keithbrooks8220
    @keithbrooks8220 5 ปีที่แล้ว

    You mentioned that you run into a lot of problems with Lennox heatpumps. Can you elaborate on this issue please. I have sold a few, so I would like to know personally.
    Thanks

  • @mariomartinez4143
    @mariomartinez4143 2 ปีที่แล้ว

    on a traulsen two door commercial refrigerator can the body of the txv sit externally? outside the evaporator housing? as long and the bulb is inside?

  • @andreagate542
    @andreagate542 3 ปีที่แล้ว

    Thank you for this wonderful video.... I understand everything you explain in this video minus one factor. When you have a moment can you kindly explain why your DeltaT will go up when you have a bad TXV. Many thanks

    • @jericosha2842
      @jericosha2842 3 ปีที่แล้ว +2

      If the TXV is underfeeding, there will be a noticable drop in pressure in the indoor coil. This will cause the coil to significantly drop in temperature. The air being pulled across will lose a lot more heat because of the colder than normal coil. This is what gives you a higher delta T.

  • @sethmeistergee
    @sethmeistergee ปีที่แล้ว

    REALLY appreciate your explanation about how a restriction can actually show lower high side pressure-- as a refrigeration guy I see that all the time on LG fridges with partial cap tube restrictions.

  • @hailthesuccubus5764
    @hailthesuccubus5764 5 ปีที่แล้ว +2

    Love the videos! Thank you for these!

  • @adambarrett3296
    @adambarrett3296 2 หลายเดือนก่อน

    Thanks for the lesson teach

  • @dirtygully9938
    @dirtygully9938 3 ปีที่แล้ว

    Is there any content on hooking up a ductless blower to a central air condenser?

  • @Lemonpepperclub
    @Lemonpepperclub 4 ปีที่แล้ว +1

    i should be taking notes!!!

  • @laworder6092
    @laworder6092 4 ปีที่แล้ว

    What do you mean by inside and outside superheat?is it compressor superheat and evaporator superheat? Or something else? When you have mentioned evaporating temp 33.6 F and inside temp 75 F where you talking about evaporator approach? Please clarify

  • @ralphnabozny8494
    @ralphnabozny8494 2 ปีที่แล้ว

    does running your unit at a higher house temp ( thermostate set point at 81 rather that 78 degrees) help the longevity of the life of the unit? It cycles more but not as long.

  • @alejandromata825
    @alejandromata825 2 ปีที่แล้ว

    I found a jumped O-ring keep the needle closed on a 30 ton once, unfortunately tried ordering and changing the power head first.

  • @jonathancastillo8235
    @jonathancastillo8235 ปีที่แล้ว

    WOW this guy is very good

  • @louisvelez943
    @louisvelez943 4 ปีที่แล้ว +2

    Please tell me where on the inside do I take my superheat and subcooling thanks.

    • @dnorris724
      @dnorris724 4 ปีที่แล้ว

      Thank you Louis I've been in tons of classes and watched online videos ect... most show these numbers and temp ect... but they never show you exactly where and how there placing there test instruments which is very key...he does touch on it but showing is much better. Showing is best along with the explanation but this man seems very knowledgable so I commend him. Please do videos showing this testing and explaining it.