  • Have you ever wondered what the kitchen suppression system does and how it works? Checkout the following video of a trained and licensed suppression manager explain one of the most common suppression deficiencies, a clogged detection line.

ความคิดเห็น • 49

  • @andrewbandarovich1751
    @andrewbandarovich1751 5 ปีที่แล้ว +11

    Great video. Unfortunately a lot of service companies just replace links and never cut test anything. Even worse, some just replace their tags to the ones with new dates and go.

  • @williamday3521
    @williamday3521 4 ปีที่แล้ว +2

    I am about to disassemble an ansul fire suppression system. I found this video to be super helpful in understanding how this system works. thank you

  • @kgrfirdjy
    @kgrfirdjy 2 ปีที่แล้ว

    learning about all that engineering is fascinating. i always wondered how those fire suppression emergency systems worked?

  • @tomf7170
    @tomf7170 ปีที่แล้ว +1

    Why isn't there a fusible link in the duct?

  • @ricky11va
    @ricky11va 7 ปีที่แล้ว

    Great educational video !

  • @rynesherman9099
    @rynesherman9099 3 ปีที่แล้ว +2

    Thats why you should probably test end of line first. I mean that's what the book from ansul says to do.

    • @cannabros
      @cannabros ปีที่แล้ว

      he did test the end of line its called the terminal sensor

  • @tahernabieh6096
    @tahernabieh6096 3 หลายเดือนก่อน

    WHERE IS THE CONNECTION WITH FIRE ALARM PANEL?

  • @daviddoherty1257
    @daviddoherty1257 5 ปีที่แล้ว +2

    Didn’t use locking bar before screwing out cartridge

    • @joshuaborem7063
      @joshuaborem7063 3 ปีที่แล้ว

      Lock bars are for scaredy cats who don’t trip systems. Me and my team don’t ever use lockout bars.

  • @franciscoesterripa7912
    @franciscoesterripa7912 ปีที่แล้ว

    What certification you need to inspect systems like that

  • @tonyhernandez3873
    @tonyhernandez3873 ปีที่แล้ว

    Why you say connect your appliances on ceriesl I guess it's on parallel to the contractors

  • @haydeevalentin4670
    @haydeevalentin4670 6 ปีที่แล้ว

    Hi , Please you repeat procedure spanish . The excelent explain . I need all visual complete prosedure , the all

  • @josebermudez8364
    @josebermudez8364 6 ปีที่แล้ว +1

    No protection on the opening.. a link must be install above every equipment and duct opening.. .

    • @Troacoli
      @Troacoli 4 ปีที่แล้ว +1

      I think this is a training/demo system. But yes.

  • @stanlleypajdak8547
    @stanlleypajdak8547 5 ปีที่แล้ว +1

    How do you reset the system

    • @Sophsfghds
      @Sophsfghds 3 ปีที่แล้ว

      You need a Ansul tension resetting tool to reset the automatic & manual actuation pulley wire lines

  • @user-xh3zr8fh4k
    @user-xh3zr8fh4k 4 ปีที่แล้ว

    you didn't say anything about the alarm?

  • @nationalfireprotectioninc.843
    @nationalfireprotectioninc.843 4 ปีที่แล้ว +1

    he is using wrong detection bracket . those detector bracket are for Range guard. you must use Ansul system detector or Ansul will not responsible for that.

    • @joshuaborem7063
      @joshuaborem7063 3 ปีที่แล้ว

      I agree that you’re correct but it’s a useless fact.
      The bracket being the wrong brand will not affect system operation.

    • @nrtxdragon1703
      @nrtxdragon1703 3 ปีที่แล้ว

      these detector are used all across the uk with no issues Ansul them self have no issues with these detectors

  • @ThomasShue
    @ThomasShue 4 ปีที่แล้ว +1

    You could use a zip tie for a test link.

    • @joshuaborem7063
      @joshuaborem7063 3 ปีที่แล้ว

      Why would you do that? Just use a test link or a real link.

  • @jukebox40000
    @jukebox40000 2 ปีที่แล้ว

    🔥🔥🔥🔥

  • @khalidkhalid-dn2pt
    @khalidkhalid-dn2pt 3 ปีที่แล้ว

    Where Is duct Link

  • @safety_news
    @safety_news ปีที่แล้ว

    I am Robert.Tamilnadu safety council. Secretary. Helping hearts foundation trust. Secretary.
    Safety Reach World.CEO.
    Iyarkai Foundation.NGO.
    Human Rights International Federation. Tirupur South president.
    Tirupur emergency response team. founder 💝👩‍🚒🙏

  • @farrukhmahmood4099
    @farrukhmahmood4099 3 ปีที่แล้ว

    Hello sir how are you. Sir my system is ansul pirhana. My problem is how to fix manual release and fuse ablelinks rope fixing in mechanical realease medole how to fix fuseable link cable???

    • @farrukhmahmood4099
      @farrukhmahmood4099 3 ปีที่แล้ว

      Please reply me very soon

    • @justinlee4022
      @justinlee4022 3 ปีที่แล้ว

      Yes if you still need help . Let me know as well

    • @joshuaborem7063
      @joshuaborem7063 3 ปีที่แล้ว

      Your question is too vague to answer. “How to fix” isn’t specific enough.

    • @nrtxdragon1703
      @nrtxdragon1703 3 ปีที่แล้ว +1

      get a trained Ansul engineer to do it? there the only one that should be touching a system

  • @suppression7630
    @suppression7630 4 ปีที่แล้ว +1

    You are using wrong detector. Those detector are not for Ansul system

    • @nrtxdragon1703
      @nrtxdragon1703 3 ปีที่แล้ว

      I'm a trained Ansul engineer in the uk this detector are correct. usless the only ones you have see are the old horse shoe ones that are now out dated and need to be replaced

  • @enjazalawsat1176
    @enjazalawsat1176 ปีที่แล้ว

    Hi sir how are you

  • @farrukhmahmood4099
    @farrukhmahmood4099 3 ปีที่แล้ว

    Assalamualkum

  • @wa6lie
    @wa6lie 5 ปีที่แล้ว +1

    Hmmm... that detection line did not get that way in 6 months. The service company is NOT doing their job right. What happened to the REQUIRED detector in the exhaust duct just left of the end of line detector? In addition, the scissor links are NOT suppose to be positioned up in the bracket as shown. They are supposed to hang down freely. This also helps prevent additional drag on the cable for proper operation.
    To keep the scissor from falling off the cable, using a weight like vise grips to weight the cable without actually gripping the cable on the end of line detector, allowing it to move freely. This way, there is always some tension on the scissors so they don't fall apart while installing the other fusible links on the detection line. Every service, 6 months or more frequently, depending upon kitchen operation whereas grease build up is greater than normal. This may include restaurants open 24 hours with char broilers or Chinese Woks for example. Somebody needs to go back to ANSUL school. I have been installing and servicing "ANSUL" type of restaurant systems since 1982 and in this video the service company providing the service is doing a dis-service to our professional service technicians. Go to the fire system manufactures training school to know how to do it right, or not all.

    • @stephencarroll6590
      @stephencarroll6590 5 ปีที่แล้ว +3

      "Install the linkage and the correct ANSUL approved fusible link in the remainder of the detector brackets. Make certain all detector linkages are positioned against either the front or back upper lip of the formed detector bracket."
      That is directly from the ANSUL manual. Might I suggest you follow your own advice and go back to ANSUL school?

    • @justinlee4022
      @justinlee4022 3 ปีที่แล้ว +1

      Boom! Yes Stephen is correct! They do belong inside the detector housing just not straight up. Either front or back has a lip indent that the detector belongs in to prevent slag, the link detector is not suppose to be outside just hanging as the weight, vibration , and or cable can be running against something and could accidentally be cut/frayed overtime or damaged and you could have a accidental discharge.
      However , the rest of your information is correct. I have been testing,installing and selling Ansul systems for 10 years. Also was the department manager and sales person for service and contracting sales for the largest company in Arizona. Almost a million in Kitchen suppression system sales alone in a fiscal year .

    • @joshuaborem7063
      @joshuaborem7063 3 ปีที่แล้ว

      You criticize them without any specifics except the scissors hanging down (of which you’re incorrect- because the Ansul book requires them to be tucked upward into the brackets )

  • @pepperwilliams4428
    @pepperwilliams4428 6 ปีที่แล้ว

    This guy did a great video, but probably need to exercise more. He sure was breathing heavily throughout.

    • @danbardales6734
      @danbardales6734 6 ปีที่แล้ว

      Pepper Williams you might have a fitness body...

  • @ThomasShue
    @ThomasShue 4 ปีที่แล้ว

    Good job reading a paper. Just be real and talk to us brother.

  • @frankfarkle2924
    @frankfarkle2924 6 ปีที่แล้ว +1

    the scissor isn't even crimped to stay on the line. Poor guy is going to sweat all day looking for the scissor that falls after testing.

    • @darrelldawson4823
      @darrelldawson4823 5 ปีที่แล้ว +3

      I've seen "crimped" scissors cause cable fraying on the detection line, that's a terrible reccomendation. A technician should not spend time searching for the missing scissor either. After a system discharge due to a fire, the scissor containing the fusible link that separated should be replace as well as any other scissors exposed to extreme temperatures. ALL links should then be replaced.

    • @joshuaborem7063
      @joshuaborem7063 3 ปีที่แล้ว

      Don’t crimp the scissors!
      My team has had 20 system dumps per year and no issue with finding the scissor.
      Besides that, if the scissor is missing then you just install a new one.