YOUR VIDEO IS EASY TO UNDERSTAND, BUT I HAVE ONE DOUBT. TO CONVERT KW TO KVA WE NEED TO DIVIDE WITH PF 902/0.8. BUT IN THIS VIDEO SHOWS MULTIPLY BY PF 902*08, KINDLY CLARIFY
Can you please clarify one point, When Normal Load is Running there will be some voltage drop at bus-bar. Let suppose, a 415V system and voltage during normal load(except largest motor load) is 5% which is 394.25V. Will we take take this voltage as a reference for the starting of Largest Motor?
Does Under voltage test is sufficient for MV cable or in addition to under voltage test hi pot test is also required, could you please provide me some information ?
Bro @14.38, to convert base load KW to KVA, power factor is to be divided. isn't it...?? Then 1500KVA is not adequate because it will make 139% overloading.
Thanks, bro for dealing with these types of messy things and making it understandable for us.
The base load with out larg motor is 902/0.80
Thank you so much
YOUR VIDEO IS EASY TO UNDERSTAND, BUT I HAVE ONE DOUBT.
TO CONVERT KW TO KVA WE NEED TO DIVIDE WITH PF 902/0.8.
BUT IN THIS VIDEO SHOWS
MULTIPLY BY PF 902*08, KINDLY CLARIFY
How to calculate diversity factor?
Can you please clarify one point,
When Normal Load is Running there will be some voltage drop at bus-bar. Let suppose, a 415V system and voltage during normal load(except largest motor load) is 5% which is 394.25V. Will we take take this voltage as a reference for the starting of Largest Motor?
Is this applicable to dewa regulation also?
Does Under voltage test is sufficient for MV cable or in addition to under voltage test hi pot test is also required, could you please provide me some information ?
IF CALCULATE BY 902/0.8 MEANS I GOT TRANSFORMER OVERLOAD PERSENTAGE IS 0.639%
IS IT CORRECT
thanks brother please upload adequacy check for voltage drop
thanks bro
please make 3rd part voltage drop for transformer.
Please tell me how to calculate cable size 1200kw lv panel
Bro @14.38, to convert base load KW to KVA, power factor is to be divided. isn't it...?? Then 1500KVA is not adequate because it will make 139% overloading.
Still less than 150%
How about 3tx with 2 bus coupler
Please send part 1 for transformer selection
It is in the same playlists
Where is The Part 1?