FDAS ay Hindi adviseable na iOFF hanggat walang trouble as to their special function to alarm when a fire alert took place neither it is Addressable or conventional type.
Contaminated Smoke Detector , on this it is on Zone 2. Sa FDAS na conventional easy detection is by swapping contaminated zone, eg: Zone 2 (contaminated) Zone 3 good.
O/c error related to overload or short circuit zone. To verify and for troubleshooting purpose, kalasin ung zone na may O/C at maglagay ng EOL resistor. Kapag nawala ung O/C, check ang linya sa zone kung saan nag O/C.
Zone 2 false alarm, contaminated so causing false alarm. Same method sa pag detect ng trouble sa O/C ay kalasin ung load sa zone na may false alarm then ikabit ung EOL, kapag walang false alarm check MPS and SD.
❤
ilang smoke dector lemet sa zone 1 sir conventional
5 Smoke Detector for each zones. 1 MPS for each zone.
good evening po sir..ano po sira pag ganyan ang trouble? Ganyan po kasi trouble sa conventional fire alarm ko
False Trigger lang ng smoke detectors gawa ng dust need pm.
Good pm sir..may on and off po ba yan just in case gusto namin patayin po?lalo kung aalis kami ng bahay po
FDAS ay Hindi adviseable na iOFF hanggat walang trouble as to their special function to alarm when a fire alert took place neither it is Addressable or conventional type.
idol paano mo na i solve ang problema na ganyan sa battery po ba yan..? kung sa zone walang indicate na redlight peru na alarm. 💪💪❤️
Ok Battery ka-Basic, nandun lang sa Smoke Detector, vacuum cleaner lang muna para walang false trigger resulting to false alarm cause dust.
Ano po kya ang naging dahilan bkit ganoon
Contaminated Smoke Detector , on this it is on Zone 2. Sa FDAS na conventional easy detection is by swapping contaminated zone, eg: Zone 2 (contaminated) Zone 3 good.
Anong error code po ito o/c error
O/c error related to overload or short circuit zone. To verify and for troubleshooting purpose, kalasin ung zone na may O/C at maglagay ng EOL resistor. Kapag nawala ung O/C, check ang linya sa zone kung saan nag O/C.
Idol pa help naman. Anong pong problema sa error na ito..
Zone 2 false alarm, contaminated so causing false alarm. Same method sa pag detect ng trouble sa O/C ay kalasin ung load sa zone na may false alarm then ikabit ung EOL, kapag walang false alarm check MPS and SD.