Analysis of Singly Reinforced Concrete Beam! (Reinforced Concrete Design)

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ก.ย. 2024
  • IN THIS SESSION:
    How does the strength of the beam change with a various number of tension bars given the beam width, effective depth, material properties, and tension steel area?
    Enroll in GERTC’s ONLINE REVIEW! Details here:
    • DETAILS about GERTC ON...
    ----------------------------------------------
    Enroll in GERTC Review Lite: / @gillesaniaengineering...
    Learn about GERTC Review Lite here: • GERTC Review Lite! Rev...
    FOLLOW US ON FACEBOOK!
    Gillesania Engineering Videos on Facebook: / gillesaniaengineeringv...
    GERTC Review Center: / gillesaniareviewcenter
    OFFICIAL ENGINEERING REVIEW BOOKS SHOP
    Official Website: www.gertcrev.c...
    Facebook: / ditgillesaniabooks

ความคิดเห็น • 31

  • @erwincatalan3733
    @erwincatalan3733 4 ปีที่แล้ว +4

    Hi sir thank you for very clear video tutorial on beams. Can you Please make a video on distribution of loads from slab to beam thank you very much.

  • @mjoshuaray
    @mjoshuaray 2 ปีที่แล้ว +1

    Good day Engr, doon po sa @16:21 , instead na 20.7 po, 27.5 po dapat ang fc' pero ang true answer ay 269.8mm parin for c. Thanks

  • @alexejcrescini263
    @alexejcrescini263 4 ปีที่แล้ว +5

    pwede sir paresquest sir doubly reinforced design,T beams slabs, coloums,footings and pile footings.

  • @javec5306
    @javec5306 3 ปีที่แล้ว +1

    Malaking tulong po yung mga video nyo sakin sir. Sir pwede po ba magrequest ng series ng design from roof to footing po. Atleast two-storey house po sana. Naka STAAD po kasi yung ibang video na napanood ko. Gusto ko po kasi matuto ng manual magdesign 😅

  • @faithmontejo4012
    @faithmontejo4012 11 หลายเดือนก่อน

    Babalik po ako dito pag naging RCE nako sir. Thank you sir Gilli.

  • @rodeliocastillo9300
    @rodeliocastillo9300 4 ปีที่แล้ว +1

    Sir problem "c" f'c mistake 20.7MPa should be 27.5MPa the result of c is wrong. Thanks

  • @shrekfive5034
    @shrekfive5034 2 ปีที่แล้ว

    Thank you Sir Diego Engr na ako ;D. MARAMING SALAMAT PO

  • @ninomarompoc7707
    @ninomarompoc7707 4 ปีที่แล้ว +1

    Thank you po sir G.😊😊, medyo na recall ko po ung RCD, more Structural Vedios sir G.

  • @gnidnoeled786
    @gnidnoeled786 3 ปีที่แล้ว +1

    @Gillesania Engineering Videos Sir after na macompute nyo ang fs = 600(d-c)/c = 1557 MPa, this means that fs > fy. Thus, it shows steel yields?

  • @raulmontealtojr2280
    @raulmontealtojr2280 2 ปีที่แล้ว

    ang galinggg thank you po nagets ko na po singly reinforceddd more tutorial and videos po, godbless

  • @bardzzz8934
    @bardzzz8934 2 ปีที่แล้ว +1

    Good evening sir. Tanong lang po. What if wala po effect depth? At hindi po equal ang bars sa tension bars? For example po sa tension bars, 6 bars sya, 2 sa taas at 4 sa baba. Pano po makukuha ang effective depth?

  • @gnidnoeled786
    @gnidnoeled786 3 ปีที่แล้ว

    @Gillesania Engineering Videos Kapag po ba nag-yield ang steel (tension controlled) ibig sabihin good design dahil magbigay ng warning ang structure sa occupants at di biglaan ang collapse? O meron po bang iba pang dahilan gaya ng pagiging economical but safe?

  • @harrygarcia1269
    @harrygarcia1269 2 ปีที่แล้ว +1

    Sir hindi po ba dapat yung ginamit po sa fs = 600 (d-c)/c, dapat po dt which is the centroid nung extreme reinforcement? Sa NSCP po kasi Et nakalagay which is the strain of the extreme tension reinforcement not the centroid of all tension reinforcement. As per NSCP po kasi Et is defined as net tensile strain in extreme layer of
    longitudinal tension reinforcement at nominal strength, excluding strainsdue to effective prestress, creep, shrinkage, and temperature.

  • @jordanrodriguezph
    @jordanrodriguezph 3 ปีที่แล้ว

    Magandang gabi po sir, paano malaman kung singly siya or doubly?

  • @wenlagahit3630
    @wenlagahit3630 3 ปีที่แล้ว

    Ty po sir, very understandable! Salute!

  • @aillennielzimvafrancisco1882
    @aillennielzimvafrancisco1882 2 ปีที่แล้ว

    sir dina po kailangan ng dt/d pag nakuha ng rho bal ? thanks sir

  • @joselitosinglan2685
    @joselitosinglan2685 4 ปีที่แล้ว

    Thank you sir, very clear.

  • @luisjosephb.5904
    @luisjosephb.5904 2 ปีที่แล้ว

    Sir base din po ba ito sa NSCP?

  • @geneevavillamor3921
    @geneevavillamor3921 4 ปีที่แล้ว

    Ayos pats!

  • @ainarchive
    @ainarchive 4 ปีที่แล้ว

    Thankyou Sir 😊

  • @markanthonysalatan9062
    @markanthonysalatan9062 4 ปีที่แล้ว

    ayos na ayos

  • @michaelandrew5654
    @michaelandrew5654 4 ปีที่แล้ว

    Good day tanong ko lang po. In reality po pag nagddesign po ng beam pag di nag yield yung bakal (compression controlled) automatic na ekis po agad yung design na yun? Bale po dapat nasa tension controlled ka lagi pag nagddesign? Thank you po sa sasagot

    • @gnidnoeled786
      @gnidnoeled786 3 ปีที่แล้ว

      @ Michael Andrew Yes, tension controlled dapat. Nagbibigay kasi ng warning kapag unang nagyield ang rebar. Di kagad mag collapse ang concrete. May panahon para makatakbo ang occupants. Tsaka na-o-optimize ang gamit sa rebars.

  • @michaelandrew5654
    @michaelandrew5654 4 ปีที่แล้ว

    sir may question po ako. kasi yung nilesson po sa amin dati pag yung strain daw po less than 0.004 automatic 0.65 po ginagamit? bakit po kaya o baka mali po yung naturo sa amin? pahelp po salamat.

  • @kindof6444
    @kindof6444 3 ปีที่แล้ว

    nice

  • @antonioescober8897
    @antonioescober8897 4 ปีที่แล้ว

    notice ko lang po, f'c used sa 3rd case is 20.7 MPa, bakit po kaya?

    • @kabayanhustler
      @kabayanhustler 4 ปีที่แล้ว +1

      Typo error lang yun. Just use f'c = 27.5 MPa.
      0.85(27.5)(0.85c)(330) = 4419(600)*(450-c)/c
      6,556.7c = 2,651,400*(450-c)/c
      c = 269.8 mm
      :D