How Does a Circuit Breaker / Trip Switch Work? - Pt 1

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ต.ค. 2024
  • Please support my content creation by using my Amazon Store:
    astore.amazon.c...
    ----------------------------- Click "Show more" ------------------------------------------
    In this video:
    We take a look inside a thermal magnetic circuit breaker to see how it works with both AC and DC.
    I do a practical demonstration on how the circuit breaker works to protect against overloads and short circuits.
    We take a look at some circuit breaker ratings such as:
    In: Rated current - maximum current that the breaker is designed to carry continuously at an ambient air temperature of 30 °C.
    Icu: Ultimate short-circuit breaking capacity.
    Ics: service short-circuit breaking capacity.
    I test what parameters (voltage vs current) affect the overload protection of a circuit.
    I demonstrate the instantaneous breaking / tripping capability of a circuit breaker on an oscilloscope under various loads.
    I show circuit beakers that are designed to cater for electric motor start-up inrush current with an adjustable instantaneous trip setting.
    en.wikipedia.or...
    Understanding Electric shock / Electrocution:
    en.wikipedia.or...
    ------------------------------------------------------------------------------------------------------
    My website and forum:- www.mjlorton.com
    Donations and contributions:- www.mjlorton.com
    My techie channel MJLorton - Solar Power and Electronic Measurement Equipment - / mjlorton
    My Techie Amazon Store: astore.amazon.c...
    My other channel VBlogMag - For almost any topic under the sun! - / vblogmag
    My VBlogMag Amazon Store: astore.amazon.c...
    ------------------------------------------------------------------------------------------------------
    ===================================================
    Video sponsor, Pass Ltd - their websites:
    At checkout use the discount / promotion code "mjlorton" for 5% off.
    www.tester.co.u... - Test Equipment and Test-meter suppliers and
    www.calibrate.c... - Calibration and service of test equipment
    ===================================================
    $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
    Bitcoin (BTC) Donations: 1K7PeF55e7ssE7W3WVCoa7c4j2PHzy6ASv
    $$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
    **********************************************************************************
    Music clip from TH-cam Music Library - Phase Three by Huma-Huma
    **********************************************************************************

ความคิดเห็น • 133

  • @alext9067
    @alext9067 9 ปีที่แล้ว +10

    This is such a good explanation of how the circuit breaker works. It should be taught in school rather than Chaucer and Shakespeare. Another great video. Thank you.

    • @xblindx
      @xblindx 6 ปีที่แล้ว

      alex tworkowski could do both

  • @pauludrea4082
    @pauludrea4082 ปีที่แล้ว +1

    Thank you for the effort in making such a detailed presentation. It helped me understand the importance of using a well designed and reliable breaker.

  • @vaishakhmonti
    @vaishakhmonti 7 ปีที่แล้ว +1

    Excellent demonstration. Inverse current time duly demonstrated. Great effort Mjlorton

  • @eagleflies9947
    @eagleflies9947 8 ปีที่แล้ว +4

    easily the best video on YT for the topic! comprehensive and clear

  • @jimanderson2518
    @jimanderson2518 6 ปีที่แล้ว +1

    Great work learned this thirty years ago but now I learnt it all over again . :)
    Really really well done
    .

  • @abdulkhaleqah4783
    @abdulkhaleqah4783 9 ปีที่แล้ว

    hey mjlorton. I really admire your work and the effort you are putting into publishing these tutorials for general public as I have gained a lot of information through your videos which helped me in many ways. Keep up the good work and we will continue to show you support.
    If i may, I would like to request you if you can upload videos on complete working of Electrical Standard products like Air Circuit Breakers, Moulded Circuit Breakers, Changeover Switches, Contactors & relays, basically all Switchgear Products. It will be of further great help than from what I have already been receiving from you. Cheers.

  • @chungchichiu9779
    @chungchichiu9779 7 ปีที่แล้ว

    good work. I have no knowledge about electricity.
    You may save my life by making this video. thanks

  • @JahanZeb1976
    @JahanZeb1976 9 ปีที่แล้ว +1

    Excellent demonstration as always. Cleared a lot of concept in this video. Great work.

  • @snaprollinpitts
    @snaprollinpitts 9 ปีที่แล้ว

    hey Martin, thanks for the in depth analysis of how breakers work, thanks mk

  • @SeanBZA
    @SeanBZA 9 ปีที่แล้ว +6

    Just a note a circuit breaker in the distribution board is only to protect the fixed wiring, which is in the walls, not the equipment attached. You need another protective device inside equipment to handle failure inside the equipment.
    In the USA you will also come across RCD outlets and AFCI breakers, which serve a different function to a circuit breaker, though the protection function of the circuit breaker can also be added to it, and in most cases already is.

    • @mjlorton
      @mjlorton  9 ปีที่แล้ว

      SeanBZAThanks, my mistake...adding an annotation now.

    • @TheChipmunk2008
      @TheChipmunk2008 9 ปีที่แล้ว

      SeanBZA Not true everywhere, in parts of Europe (not the UK) the fixed breakers in the board DO protect at least part of the appliance (usually the cord)

    • @SeanBZA
      @SeanBZA 9 ปีที่แล้ว +2

      ***** Not unless the cord is rated to survive. A 20A breaker will do very little to protect a 0.7mm cord ( like on a clock radio) from melting, until it gets to the point where it shorts out, which very well might be well after the fire is raging. On a 1.5mm cord it will provide some protection, but it's main point is to prevent the 2.5mm wiring in the house from burning if say you connect a 2 kW heater to the outlet and then connect a second 2kW one to the same circuit from another socket, then plug in the 1.5kW vacuum cleaner to do the floor.

    • @TheChipmunk2008
      @TheChipmunk2008 9 ปีที่แล้ว +1

      ***** Does this not still happen? (20 amp earth bond test) ?

    • @jakethesnake9528
      @jakethesnake9528 7 ปีที่แล้ว

      Have a qualified electrician use a clamp-on amp meter to check the circuit load. If the load is within the limits of the rated breaker, then replace the breaker as they have been known to go bad.

  • @TheOldmankk
    @TheOldmankk 9 ปีที่แล้ว +2

    Good ! Hopefully, next ep will be shed some light on the In-Line GFCI Ground-Fault Circuit interrupter.

  • @JRPM
    @JRPM 9 ปีที่แล้ว

    As already mentioned before, when you connect a source of constant current to the circuit breaker, doesn't make sense to test changing the voltage of the power ... the time of break-out will be always the same. Anywhere, the video is very interesting !!!

  • @saboorsaboor704
    @saboorsaboor704 8 ปีที่แล้ว +5

    oh wow! this was a very educational video..well done!! I learned a lot...well done

  • @hlaingmintun5791
    @hlaingmintun5791 5 ปีที่แล้ว

    Thanks you for your explanation and demostration because your video was fully understood me how to work the breaker cutoff.

  • @LAH1234.
    @LAH1234. 6 ปีที่แล้ว

    Excellent video and explanation. Great to learn and clear concepts by watching these educational videos.Looking forward to watching some more. Great job.

  • @Gringo_In_Chile
    @Gringo_In_Chile 9 ปีที่แล้ว

    Maybe a part 3 can cover protection more downstream of the breaker box such as: AFCI breaker outlet, isolation transformers, and power regulators/conditioners.

  • @pikaonyoutube2139
    @pikaonyoutube2139 9 ปีที่แล้ว

    thanks for the indepth explaination looking forward to seeing pt2
    cheers

  • @ranjan1436
    @ranjan1436 5 ปีที่แล้ว

    quite comprehensive, thanks, looking forward to new videos on new topics.

  • @electronicsNmore
    @electronicsNmore 9 ปีที่แล้ว

    Excellent job you did with this video.

  • @freddiemortos8519
    @freddiemortos8519 9 ปีที่แล้ว +4

    Nice,,very informative video.. Looking forward to see the second part..

  • @sssttt6533
    @sssttt6533 9 ปีที่แล้ว +3

    Very very very great explaination

  • @dessalegnendalamaw9386
    @dessalegnendalamaw9386 2 ปีที่แล้ว

    so was detailed and help the researcher more understand

  • @RealationGames
    @RealationGames 9 ปีที่แล้ว

    Very interesting, thanks for the infotainment. It would've been cool to design that kind of system. The amount of features and functionality you need to satisfy require a fair bit of engineering vision.

  • @ahmedalizafa
    @ahmedalizafa 7 ปีที่แล้ว +28

    Why the hell has someone thumbed this down? Some people just hate education

    • @-pyrosef-
      @-pyrosef- 7 ปีที่แล้ว +3

      bad formatting, too many tangents. Don't assume they don't like learning.Accept people's criticism.

  • @AleksandarKospenda
    @AleksandarKospenda 9 ปีที่แล้ว +1

    You should do one of these for earth leakage breaker (ELCB)

  • @louleslie2042
    @louleslie2042 4 ปีที่แล้ว

    This shows the importance of cct brkr box location. Out in the open air or outside wall, winter temps increase trip time.

  • @mike97525
    @mike97525 9 ปีที่แล้ว

    Nice work bench Im impressed

  • @invisibilitycriterion6782
    @invisibilitycriterion6782 2 ปีที่แล้ว

    #25:42 The reason the voltage setting of the power supply is independent of the Thermal Trip Unit (TTU), is because the two are independent variables: the power supply is acting as a current source and the (TTU) is a function of the I^2R dissipation in the Bimetallic Strip. In this case 376.36x Bimetallic Strip resistance. The power supply is operating in current limit by definition: see the Clamp-On ammeter 19.4A reading in this case. The voltage setting of the power supply doesn’t come into it.
    “...In this case with the heating of that Bimetal strip, it’s not the power but it’s the current you are carrying through the breaker that will dictate the time in which it takes to break…”
    No, it’s power that determines the TTU. Current, in and of itself, is not a measurement of energy. This can easily be demonstrated by putting an automotive incandescent lamp in series with a mains incandescent lamp across the mains supply. The automotive lamp will glow while the mains lamp will be almost full brilliance: despite both shipping the same current. In the UK, this was taught at ‘O’ level physics back in ‘79.

  • @justincase8532
    @justincase8532 ปีที่แล้ว

    Excellent demonstration. Thank you. BTW, I may be wrong but you have a South African accent?

  • @prime1971
    @prime1971 9 ปีที่แล้ว

    Excellent looking forward to part 2!

  • @MsLontje
    @MsLontje 8 ปีที่แล้ว +3

    Great teaching. thumbs up!!

  • @tuberlook1
    @tuberlook1 9 ปีที่แล้ว

    Good info in video and the comment section, nice job.

  • @misium
    @misium 4 ปีที่แล้ว

    A lot of details about types and markings of breakers in the first half of the video. "Useful", but the images gets pretty first at 11:15 and the really interesting part is at 15:54.

  • @yaghiyahbrenner8902
    @yaghiyahbrenner8902 9 ปีที่แล้ว +3

    When I was young I had a nasty shock from a AC to DC 9V adaptor, direct from a 220VAC @ 20A) I remember the period I held on due to the muscles in my hand contracting was for approximately 8 seconds, It was a disaster, I manage to let go (I don't know how) After that, I could not use my hand for a whole day. I've never shocked again, and hopefully wont have an experience like that again. its no joke safety first, always use a fuse and common sense.

  • @tekknorat
    @tekknorat 6 ปีที่แล้ว

    Great video and explanation. Now, I 'd need to know how to install these things, for example, I need to make a separate line for all kinds of outside appliances, a line to my garage and other buildings outside the house, but I want to put one of these breakers on that line at the house, so if I need to mingle with the wires, I can switch that off, not the main breakers and leave the house without electricity, just these, and safely work on the wirings there, so what kind of CB would I need if I have an incoming line with two wires, one is obviously L and the other is N. Is it enough with a single pole breaker for this situation?

  • @Elektronik-1
    @Elektronik-1 9 ปีที่แล้ว +3

    You should measure the voltage across the circuit breaker...

  • @LeeandBuzz
    @LeeandBuzz 6 ปีที่แล้ว

    Brilliant video and very well explained, thanks

  • @timramich
    @timramich 9 ปีที่แล้ว

    I cringe when people talk about a certain amount of current that it takes to cause a person to be injured. Voltage is the primary thing that does it. It takes voltage to overcome the resistance of the body and cause the current to flow. You can hold onto a battery that can deliver thousands of amps, but if it's only like 1.5 volts, it's not going to harm you. The current that can be delivered from the voltage source is the secondary cause of injury. Think static electricity. In general, there is little current capacity behind common static electricity. It obviously can deliver the voltage to overcome the resistance of the body, and you can feel it travel through you, but it can't deliver the current.

  • @lathiat
    @lathiat 9 ปีที่แล้ว

    Great video, thanks, looking forward to part 2!

  • @sauravvats1995
    @sauravvats1995 9 ปีที่แล้ว

    I wanted to know-
    1)When does the solenoid pushes the lever to release the arm?
    2)Use of solenoid.

    • @Hyratel
      @Hyratel 9 ปีที่แล้ว

      +Saurav Vats in the event of a high (surge) overcurrent state - say, 100A on a 20A breaker - the solenoid gets energized with enough force to release the latch

  • @sanjaysami4315
    @sanjaysami4315 4 ปีที่แล้ว

    Fantastic video !

  • @oBseSsIoNPC
    @oBseSsIoNPC 8 ปีที่แล้ว

    great video, great explanation, but you certainly have a slow reaction time, lol :D

  • @Monkeh616
    @Monkeh616 9 ปีที่แล้ว +2

    I feel I should point out that unless you're running the trip tests through a constant-current dummy load, your voltage setting is irrelevant, as the power supply will be in constant-current mode and only delivering the voltage needed to drive the desired current.
    That said, the voltage won't make any difference to thermal and mechanical trip time anyway.

    • @mjlorton
      @mjlorton  9 ปีที่แล้ว +1

      Monkeh616 So are you saying that if you have a constant current that the voltage has no bearing on the activation of a solenoid?

    • @Monkeh616
      @Monkeh616 9 ปีที่แล้ว +2

      mjlorton As far as I know, the voltage won't make any difference to the solenoid, either. It is the current which generates the magnetic field, just as it is the current which causes heating in the bimetal strip.
      These breakers should operate from practically no voltage (as you would have with a power supply shorted across them in constant-current mode) right up to the point they're incapable of arc suppression. This will not be true of all types, however. AFCIs I believe, certainly GFCI/RCDs, combo devices, devices with programmable tripping characteristics, etc, will require a certain voltage to operate.
      For bonus points, measure the voltage across the breaker at rated current and determine how much power is lost in it.

    • @SeanBZA
      @SeanBZA 9 ปีที่แล้ว

      Monkeh616 Correct, voltage has no part in the trip on ether thermal or instantaneous trip, the only voltage is developed across the breaker internal resistance, but it is the heating from the current that is activating the thermal bimetal time delay on low overload ( what is being tested here) and the high current through the solenoid coil to pull the internal slug across the magnetic field ( the core of those is a lot more complex than a simple solid metal slug, there is a moving pole piece inside that is pulled into the solenoid coil to provide an impulse to trip the breaker, held in place by a weak magnet in the core) on large overloads, where the thermal trip is too slow to clear the fault before the wire overheats.
      That is why there are very few purely thermal breakers in house wiring, they require a thicker cable to withstand this overload condition. Here in South Africa the original thermal only breakers from the 1960's required a 4mm cable to ensure it would have enough thermal overload capacity. With the introduction of the thermal magnetic breaker ( as shown here and almost universal in premise wiring protection) you did not need the thicker cable, as it would provide protection to thinner 2.5mm cabling safely.
      The voltage rating is there for the breaking function, too high a voltage and the arc suppression will not provide adequate arc breaking capacity, which will rtesult in an arc that will self sustain till the breaker burns out and the supply cabling burns off enough that the arc goes out, or an upstream fuse or breaker trips out disconnecting the whole supply. That is why you often have a DC rating so low, as the arc does not tend to go out 2 times per mains cycle, but only when it is either cooled by the arc suppressor cooling off the plasma below the ionisation temperature, or it grows so long that air cooling does that. A nasty demo is to take one of those AC breakers and use a 48V supply from 4 series connected car batteries, where the arc will not extinguish ( though I would not recommend closing the breaker into that but use another larger DC rated switch instead) but will carry on burning even with the breaker opened. I might do a video using a 140A arc welder and a sacrificial 5A DIN breaker, like the ones used, to show that, as I should get a high enough current to make a sustaining arc from that. Going to be fatal for the breaker in any case.

    • @superdau
      @superdau 9 ปีที่แล้ว

      mjlorton
      Yes, that's the whole point of the constant current setting. In an over-current-limit situation the PSU reduces the voltage below the value you set until the current is at the set limit.
      I guess in all your tests the "current" LED was on? This means current is the limiting factor and not voltage. And unless you have a very weird PSU you should have seen the voltage on the display drop (to the same value in all of your tests). PSU normally show the real outpur voltage and not the one set under no load.
      Also how could the voltage make a difference when the current and the resistance stay the same? It's Ohm's law.
      The voltage WILL make a difference though if it's about extinguishing the spark. At higher voltages it will (obviously) take longer, but that's at values way out of that PSU's ranges.

    • @mjlorton
      @mjlorton  9 ปีที่แล้ว

      superdau Yup, thanks for the post. I certainly went down the wrong rabbit hole. I'm going to follow-up with another video covering that mistake.
      Cheers, Martin.

  • @juanluna-nb7kp
    @juanluna-nb7kp 8 ปีที่แล้ว +1

    Awesome information! Thank you!

  • @dipunm
    @dipunm 4 ปีที่แล้ว

    Maybe I missed it, but I thought he said that in certain conditions, the switch will not re-activate the breaker... What condition is that? Is it the spring loaded coil thing? The heat will dissipate so long as the circuit is broken, but what makes the spring coil thing activate?

  • @leppie
    @leppie 9 ปีที่แล้ว

    Off-topic: When you doing a review of the Fluke 867B? (I ask, because I have one, and wondering if you have the same display issue, and for other things I have missed ;p)

  • @sultanalhammadi2910
    @sultanalhammadi2910 2 ปีที่แล้ว

    thanks a lot. Just one question, how the plunger is operated during sudden high overload (referring to time stamp 12:30)?

  • @BakersFinest
    @BakersFinest 7 ปีที่แล้ว

    I'm nit picking here, but when you say "DC 50 Hz 60 Hz" (describing the little black breaker) it might be good to qualify that DC power can't be 50/60Hz for the people who may not know that. It's either DC power, or AC power (at 50/60Hz). Cheers.

  • @chrissithole2410
    @chrissithole2410 ปีที่แล้ว

    best demonstration thank mate

  • @priyankavasam07
    @priyankavasam07 3 ปีที่แล้ว

    great explaination

  • @TheHopemaker
    @TheHopemaker 6 ปีที่แล้ว

    I got a question. Why do they use the 2 metal strips if the solenoid itself can break the circuit way faster than the metals?

  • @nadeem5476
    @nadeem5476 8 ปีที่แล้ว

    Very nice and informative. Thankyou

  • @ScienceSeekho
    @ScienceSeekho 7 ปีที่แล้ว

    In my circuit breaker the copper wire is breaked down ,what may be the problem there's also some black patches on the plastic cover as if it has been short(spark)

  • @osenseijedi
    @osenseijedi 9 ปีที่แล้ว

    For some reasons, that heat bending stuff got me disappointed... I don't know what I was expecting though...
    Does that mean that a circuit breaker that is in a cold place (say a cold Canadian garage in winter) would take longer to break or even not break at all?

  • @ecstaticasom
    @ecstaticasom 6 ปีที่แล้ว

    Really good video

  • @dougpeterson2477
    @dougpeterson2477 7 ปีที่แล้ว

    how would you go about seeing how a motor protecting circuit works. wtnpd 22-551 in a floor 1 1/2 HP scrubber ??

  • @JamesDannySheives
    @JamesDannySheives 9 ปีที่แล้ว

    Thank you! Nice job. What temperature is needed to break the circuit? If the circuit breaker box on the outside of house is in direct sunlight, would that maybe cause circuits to break more often than normal, or is that too low a temperature to have any affect on the thermal strip?

    • @aamygee
      @aamygee 8 ปีที่แล้ว

      i think yes .. i work in lab service in summer season there is increase in mcb fault i observed

  • @abedj1220
    @abedj1220 8 ปีที่แล้ว +1

    very nice video.

  • @victortancheongwee
    @victortancheongwee 2 ปีที่แล้ว

    It is normal for main circuit breaker to be a little hot at time? Mine once in a while trip, I dont think my appliances is shorted as
    it could be reset. I think maybe it is too old, mine house is 25 yrs old, Ty, I may change a new one myself. My electrician in Spore is vy exp,
    want to charge 200$ just to change this MCB which i can get for 20$..
    My MCB are both electromagnetic for short circuit and thermal for overloading.. ABB S202 type2 40A
    God bless you

  • @cuckingfunt9353
    @cuckingfunt9353 8 ปีที่แล้ว +1

    It was a good description until you started talking about the voltage in the circuit.
    The voltage in the circuit has no bearing on the results, (unless you measure across the breaker).
    All you are doing is using the wiring as a resistor. The power supply lowers the potential to limit the current.

  • @vink6163
    @vink6163 6 ปีที่แล้ว

    I've never seen a circuit breaker where the switch remains in the 'on' position after it trips. Is this something that differs between countries? How do you tell which breaker has tripped in a household panel if they are all showing as on?

  • @yueqinggeshimanelectricapp8579
    @yueqinggeshimanelectricapp8579 7 ปีที่แล้ว

    Dear Sir. If your company is stay in South Africa? I know the ONESTO very well. because the manufactory is nearby our manufactory.

  • @michaelkennedy2617
    @michaelkennedy2617 8 ปีที่แล้ว

    Wow that was really helpful!

  • @Monochram
    @Monochram 9 ปีที่แล้ว

    Fantastic video, thanks

  • @ПетяТабуреткин-в7т
    @ПетяТабуреткин-в7т 6 ปีที่แล้ว

    Is it possible to just insert a metal wire across your heart to protect it?

  • @logikgr
    @logikgr 9 ปีที่แล้ว

    Good video.

  • @horus2779
    @horus2779 8 ปีที่แล้ว

    Hi mate, I couldn't find a message box so all I can do is ask you here.
    Myself and a couple of friends grow silver perch in 1000 ltr tanks, is there a device we could get that will monitor a water pump and switch on another water pump when the primary one has died . My friend recently came home to find his fish nearly dead because his water pump had died.. We don't want to use battery backup..

  • @robertcalkjr.8325
    @robertcalkjr.8325 9 ปีที่แล้ว

    Thanks Martin.

  • @nexthacker007
    @nexthacker007 9 ปีที่แล้ว

    great video

  • @Indian-at-heart
    @Indian-at-heart 5 ปีที่แล้ว

    Dude, it was exhaustive for me ! Had you been teaching in MIT ? I will need some reference documents to understand, what you say ! :)

  • @devanshgupta5059
    @devanshgupta5059 7 ปีที่แล้ว

    how is this breakage instantaneous if the bimetal strip needs to get bent all the way for the break to happen

  • @unitedelectrician4334
    @unitedelectrician4334 7 ปีที่แล้ว

    Great video

  • @samd1495
    @samd1495 8 ปีที่แล้ว

    will dried up salt water prevent the breaker from tripping ?

  • @ahmedburgan7118
    @ahmedburgan7118 6 ปีที่แล้ว

    Hi there
    I just want to ask about the circuit breaker if it has input and output or not
    Thanks

  • @tiittalts3944
    @tiittalts3944 9 ปีที่แล้ว

    P=(I^2)*R interesting what is the resistance of bi-mettal, mjlorton ??

  • @zakysmart1
    @zakysmart1 7 ปีที่แล้ว

    thank you for this video

  • @mattshu
    @mattshu 8 ปีที่แล้ว

    I stumbled here and got lost in this video for 20 minutes. I should go back to school for engineering.

    • @mattshu
      @mattshu 7 ปีที่แล้ว

      college is school

  • @tttvn123
    @tttvn123 2 ปีที่แล้ว

    22:13 If you use 50A, after how long the CB will trip?

  • @harshalpanchal883
    @harshalpanchal883 6 ปีที่แล้ว

    nice information thank you.......

  • @abbandabolehbuat4169
    @abbandabolehbuat4169 4 ปีที่แล้ว

    Hi sir..can i use some part of your video for my youtube tutorial video? I will credit your link in my description. Thanks sir.

  • @TheEnneagram
    @TheEnneagram 9 ปีที่แล้ว +2

    About how many times can a circuit breaker trip before it needs to be replaced?

    • @osenseijedi
      @osenseijedi 9 ปีที่แล้ว

      ***** which means that the switch wouldn't hold anymore, right?

    • @flyguille
      @flyguille 9 ปีที่แล้ว +2

      TheEnneagram when the contacts of it get dirty by the arc and then you start noticing it heats more than usual with the normal load. That means the contact having resistence.

    • @enginedesign4871
      @enginedesign4871 8 ปีที่แล้ว

      +TheEnneagram how many times can a circuit breaker break before it breaks?

    • @TheEnneagram
      @TheEnneagram 8 ปีที่แล้ว

      Andrew Geng How many licks does it take to get to the center of a Charm's Blow Pop?

    • @aamygee
      @aamygee 8 ปีที่แล้ว

      chines low quality mcb goes crack with 5 to 8 times it trips and high quality breaker keep working again and again ......life long

  • @bravohoras
    @bravohoras 4 ปีที่แล้ว

    My automatic circuit breaker buzzing whenever i'm turning on my water heater. Is it dangerous or can harm other electronic devices likes phone ar laptop? It buzzing calmly when i'm charging laptop battery but a bit loud when i'm turning on my water heater. What should i do?

  • @michaelhawthorne8696
    @michaelhawthorne8696 9 ปีที่แล้ว

    I was of the understanding that AC Voltage shock will throw you off and DC Voltage shock will clamp you to the fault.

  • @dennisqwertyuiop
    @dennisqwertyuiop 9 ปีที่แล้ว

    good info

  • @YS.
    @YS. 5 ปีที่แล้ว

    voltage on a closed wrench to zero and it is useless to turn it on the power supply

  • @monamona1574
    @monamona1574 7 ปีที่แล้ว

    thanx for useful vedio

  • @afroninjadeluxe
    @afroninjadeluxe 8 ปีที่แล้ว

    23:25 what kind of clamp is that?

  • @sumeshts92
    @sumeshts92 6 ปีที่แล้ว

    Great

  • @tynanroussety917
    @tynanroussety917 7 ปีที่แล้ว

    How could i measure RPM with an optical breaker circuit

  • @dhilboylion8080
    @dhilboylion8080 7 ปีที่แล้ว

    Very cool

  • @mohamedalishafiqueahmed9496
    @mohamedalishafiqueahmed9496 6 ปีที่แล้ว

    it is 1976 i woking in bukatir's group & i found a complain in building belong to Health Club The Floor Wiring have problem of Ac's Wiring Ac's wiring Size problem Thank

  • @viavictoreletrica3527
    @viavictoreletrica3527 ปีที่แล้ว +1

    GOSTEI

  • @VladPayne
    @VladPayne 9 ปีที่แล้ว

    It's almost THAT art of youtube

  • @RCCambodiaOfficial
    @RCCambodiaOfficial 6 ปีที่แล้ว

    good

  • @NsearchOFsunrise
    @NsearchOFsunrise 7 ปีที่แล้ว

    Have you ever seen a main breaker turn off ? Not trip but actually be turned off it's been happening for the last 3 months at random times.....

  • @HungrySandwitch
    @HungrySandwitch 6 ปีที่แล้ว +3

    11:20 is when he takes it apart

  • @roytan7962
    @roytan7962 9 ปีที่แล้ว

    CE is made in PRC

  • @thedogememesproductions6354
    @thedogememesproductions6354 7 ปีที่แล้ว

    Ok i decided to put a ground wire and we fixed it

  • @YinhuWang
    @YinhuWang 7 ปีที่แล้ว +1

    go to 11:15

  • @mohamedalishafiqueahmed9496
    @mohamedalishafiqueahmed9496 6 ปีที่แล้ว

    thank some mcb's have menufecturing male function they do not write the crect informetion technicaly even on of posetion to locete the in emergency on of thank