Gree GMV5 VRF Maintenance - Ⅲ. 7. System high pressure protection E1

แชร์
ฝัง
  • เผยแพร่เมื่อ 9 ก.ย. 2024
  • Ⅲ.Common Troubleshooting and Replacement of Electrical Components
    7.System high pressure protection E1
    ①When E1 appears, please check if the cut-off valves of gas pipe and liquid pipe are fully opened.
    ②When E1appears, power off and then power on,turn on the units.
    ③High ambient temperature in operation.
    ④Pressure sensor is not working properly.
    ⑤High pressure switch is not working properly.If E1 appears after power on but the compressor doesn’s start up, it means the high pressure switch is not working properly.
    ⑥The pipeline is blocked.
    ⑦Excessive refrigerant charging amount. If the above-mentioned causes are excluded please check if the additional refrigerant charging amount is correct.