Liebert NX 480 Shutdown, Startup, Bypass

แชร์
ฝัง
  • เผยแพร่เมื่อ 31 ธ.ค. 2024

ความคิดเห็น • 11

  • @maxastuto
    @maxastuto 2 ปีที่แล้ว +1

    hello, i have a UPS Emerson Liebert model NX10 ( 10kva power ), in February 2002 I changed all the batteries and it worked for about a month. A few days ago it started not working again. I see on the upper strip between the 4 LEDs, 3 are lit green, the third is off. Below, on the other hand, there is a red lit LED that indicates the batteries. The general maintenance technicians do not know what the cause is and the service center is about 1000 km away. could you help me to get an indication of what failure it can be and how to fix it? what needs to be checked?many thanks

    • @jimbev1990
      @jimbev1990  2 ปีที่แล้ว

      Hello Maxastuto. I am a Vertiv (Liebert) customer and I posted this video because I thought the startup/shutdown procedure might be useful to other users of the Liebert NX UPS. I am not qualified to do fault analysis or trouble shooting. Perhaps someone else may have a different suggestion, but my thought is that you contact Vertiv or another support organization with qualified support engineers. I am sorry not to be able to provide a better answer.

  • @SofianeMeziane-m4b
    @SofianeMeziane-m4b 13 วันที่ผ่านมา

    Hi. you have an idea how the NXC 30 KVA inverter ignition steps

    • @jimbev1990
      @jimbev1990  13 วันที่ผ่านมา

      My advice is to locate a copy of the correct manual at vertiv.com. I did a quick search and found this. Perhaps it will help you ??? www.vertiv.com/globalassets/products/critical-power/uninterruptible-power-supplies-ups/liebert-nx-10-30kva-installation-manual.pdf

  • @Mahran97
    @Mahran97 2 ปีที่แล้ว

    Hello, can you help in battey replace fault, i changed the bateeries and still with the fault

    • @jimbev1990
      @jimbev1990  2 ปีที่แล้ว +1

      Sorry. I am a Liebert customer and thought the startup/shutdown procedure might be useful to other users of the Liebert NX UPS. I am not qualified to do fault analysis or trouble shooting. We have our support contract with a qualified support company and they perform our preventive maintenance, diagnostics and repairs. I wish I could be of more help, but my advice is to work with a factory trained engineer to resolve the issue.

    • @mikebachmann4590
      @mikebachmann4590 2 ปีที่แล้ว

      It's the 'end of life' alarm. Set for 5 years. You need the software to reset it.

    • @donnfl
      @donnfl 2 ปีที่แล้ว

      YOu may be able to go intothe setup manual, password 12345.

    • @mikebachmann4590
      @mikebachmann4590 2 ปีที่แล้ว

      @@donnfl Negative ghost rider. You need the software.

    • @joeredman9354
      @joeredman9354 ปีที่แล้ว

      If the fault you are talking about is a "battery maintain" error then that's a reminder to change the batteries. But if you have the wrong version firmware, you'll need to have Liebert come out and upgrade to another version to reset the error.

  • @birdeyeview3901
    @birdeyeview3901 4 ปีที่แล้ว +1

    Switching ON and swithing OFF of 500KVA EMERSON LIBERT NX UPS.
    * Switch ON procedure
    1. Switch ON the UPS input source(UPS input panel)
    2. Switch ON the output breaker Q5
    3. Switch ON the bypass breaker Q2
    4. Switch ON the input breaker Q1
    5. Switch ON the battery charger QF2(neutral) and QF1 respectively.
    * Switch OFF procedure
    1. Switch OFF the battery charger QF1 and QF2(neutral) respectively.
    2. Switch OFF the input breaker Q1.
    3. Switch OFF the bypass breaker Q2.​
    4. Switch OFF the output breaker Q5.
    5. Switch OFF the UPS input source(UPS input panel)
    Please note that before switching ON battery charger all display LED indicators in UPS should be in green condition