How to connect bypass contactor to soft starter
ฝัง
- เผยแพร่เมื่อ 16 ม.ค. 2025
- After motor started, soft starter will quickly cut off the power and automatically turn on the bypass contactor, so that the three-phase electricity directly supplies power to the motor through the contactor. Buy ATO soft starter online: www.ato.com/so...
The missing part of the control terminal in the video: during operation, 7 and 10, 8 and 10 need to be connected.
I’m having intermittent voltage drop out issues to my bypass contactor. Can the internal micro relay fail? Is there a limit for bypass coil resistance?
What does N1 go to
@ATOCOM, I have a sotf starter of 25 hp 37 amp of current at 480 V, for one motor of 25 hp nominal current 27 amp, what voltage of coil contactor do you recommend?
@ATOcom, I have a sotf starter of 25 hp 37 amp of current at 480 V, for one motor of 25 hp nominal current 27 amp, what voltage of coil contactor do you recommend?, I mind contactor for by pass
@@JosePonce-rg4nv If you have a neutral line, you can use a bypass contactor with 277V coil voltage.
So i can connect the bypass wire number 1 back to R? We ate using a generator
You can regard the bypass port (1&2) as a switch. When the startup is completed, the switches 1 and 2 will be turned on. In theory, as long as the load capacity of the terminal does not exceed 250V and 2A, it is OK.
@@ATOcom
It worked. So far so good. Can i use this starter for multiple motors? Also does it have a timer? We're using it to start a 150hp jaw crusher motor. I will keep you posted on it's performance. Hope to be crushing rocks this month.(5/11/2022)
Do your soft starters absolutely need the bypass contactor? I would prefer to avoid it
It must be equipped with a bypass contactor, because the main circuit that has been soft-started will be disconnected after successful startup, thus switching to bypass operation.
tks ❤
Nowhere in your videos on soft starters do you show how to wire the 2 wire connection for start and stop. I am using a remote control to turn on and off the machine so I have a 120VAC output as a signal to the soft start to start or stop. I also cannot find anywhere what signals terminals 1 through 12 are looking for. I have the unit sitting on my bench now and this information is not even in the manual. Also your 2 different videos show different wiring for the terminal 1 and 2 wiring to the bypass relay.
Thank you
I beleive we have everything wired up properly, but when the start mode is completed and contacts close 1 & 2 amperage is rising to motor causing it to humm so we quickly turn it off to avoid issues with motor. very strange.
thanks
How to bypass a contact