Jumper brake it’s on a Carrier while Trane has a terminal along the side of the fan center terminals in the Symbio 700 board,however,the older Trane equipment including new Relia tel would have a landing on the far right side where test screws are found. Fun times Good luck 👍🏽👍🏽
@@llchips7hi sir. If i want wire it to gas furnace what should I do. It already have 120 power. Should I wire NC and C to furnace with fan and R? Thanks
If the control is already powered and you are wiring a furnace to shut off, I would break red going to the thermostat by running it through C and NC. (6,16)
Run 24 through the 6 & 16 to cut power to the board and 8 & 18 to a 90-340 relay to cut the 120v to a motor if necessary. It is necessary to cut power to the motor when residential x-13 units used in commercial locations, because they don't shut down immediately.
Great Job simplifying something that intimidates so many younger techs in the industry!
Jumper brake it’s on a Carrier while Trane has a terminal along the side of the fan center terminals in the Symbio 700 board,however,the older Trane equipment including new Relia tel would have a landing on the far right side where test screws are found. Fun times Good luck 👍🏽👍🏽
Clear and concise. Thank you, sir.
Thank you sir for make this informative video
I’m trying to install this in a air handler
What cables do I connect the green and the white to
You need to shut off the fan. It depends on what unit you have.
In this situation it would be best to kill R going to the thermostat. So if a fire alerts, it will shut off the unit
@@llchips7hi sir. If i want wire it to gas furnace what should I do. It already have 120 power. Should I wire NC and C to furnace with fan and R? Thanks
If the control is already powered and you are wiring a furnace to shut off, I would break red going to the thermostat by running it through C and NC. (6,16)
thank you, it's very helpful
Great info!!!
Thank you so much
Ty
Hi Sir I am looking residential duct smoke detector wiring with 120V .
Best regards.
Run 24 through the 6 & 16 to cut power to the board and 8 & 18 to a 90-340 relay to cut the 120v to a motor if necessary. It is necessary to cut power to the motor when residential x-13 units used in commercial locations, because they don't shut down immediately.
Thanks. Good information.