Hello, how I can reduce sensitive of controller? Because Schneider is very sensitive. If small problems and go on alarms. Switching off condensators. I entered cos 0.99, it is posible to enter 1.05, because I want to over compensation. Is it correct that I entered in 312 invisible Q?
Thank you for your message. We apologize for any inconvenience caused. For technical support or to find answers to your questions, please refer to our support center: www.se.com/ww/en/work/support/support-center.jsp or reach out to a technical expert in your location here: www.se.com/ww/en/work/support/country-selector/contact-us.jsp
Sir I'm using Schneider RT12 APFC controller ...in that I have to enter CT and CK value. We have connected 200/5 Current transform so I'm are entering CT:40 and CK: 0.13 first bank is of 5 kVAr I'm entering correct value??
Dear Mr. Raikar, Greetings from Schneider ! We have assigned your query to the concerned team and they will get back to you shortly. Meanwhile, requesting you to kindly share your contact details so that we can assist you in a better way. Regards, Shweta Jamwal Customer Care Center.
Dear Mr Raikar, Good Day! Please find below details as per your query: C/k value of 0.13 is correct in your case. C/k is the value obtained by dividing first step capacitor power "C" to the Current Transformer Ratio "k". Current Transformer Primary Value is selected in setting so please set 200 only.
Thank you for your message, John Merruel Navida. We apologize for any inconvenience caused. For troubleshooting support or to express your concerns, please reach out to a technical expert in your location here: www.se.com/ww/en/work/support/country-selector/contact-us.jsp
Hello, how I can reduce sensitive of controller? Because Schneider is very sensitive. If small problems and go on alarms. Switching off condensators.
I entered cos 0.99, it is posible to enter 1.05, because I want to over compensation. Is it correct that I entered in 312 invisible Q?
I make this commissioning on load or without load ??
Thank you for your message. We apologize for any inconvenience caused. For technical support or to find answers to your questions, please refer to our support center: www.se.com/ww/en/work/support/support-center.jsp or reach out to a technical expert in your location here: www.se.com/ww/en/work/support/country-selector/contact-us.jsp
Sir I'm using Schneider RT12 APFC controller
...in that I have to enter CT and CK value. We have connected 200/5 Current transform so I'm are entering CT:40 and CK: 0.13 first bank is of 5 kVAr
I'm entering correct value??
Dear Mr. Raikar,
Greetings from Schneider !
We have assigned your query to the concerned team and they will get back to you shortly. Meanwhile, requesting you to kindly share your contact details so that we can assist you in a better way.
Regards,
Shweta Jamwal
Customer Care Center.
Dear Mr Raikar,
Good Day!
Please find below details as per your query:
C/k value of 0.13 is correct in your case. C/k is the value obtained by dividing first step capacitor power "C" to the Current Transformer Ratio "k".
Current Transformer Primary Value is selected in setting so please set 200 only.
Character In the video It's great, I like it a lot $$
Thank you so much!
Nice one
How to eliminate alarm SPL/flty
Thank you for your message, John Merruel Navida. We apologize for any inconvenience caused. For troubleshooting support or to express your concerns, please reach out to a technical expert in your location here: www.se.com/ww/en/work/support/country-selector/contact-us.jsp
How to set this , communication to dcs
Thank you for your message. For technical support or to find answers to your questions, please refer to our support center: spr.ly/6052JeniM.
Tankss
Podrian ponerlo en castellano
th-cam.com/video/EXsrom7FiAc/w-d-xo.html