2.2 KW / 3HP @ 3phase motor _FLC4.70A Current measure / OLR if problem check direct connect mcb

แชร์
ฝัง
  • เผยแพร่เมื่อ 6 มี.ค. 2023
  • 2.2 KW / 3HP @ 3phase motor _FLC4.70A Current measure - per winding /coil(U,V,W(star connection) -2.8Amp to 3.5Amp
    R-3.2Amp,Y-3.2Amp,B-3.5Amp
    Over load Relay (OLR) Trip problem findout =
    1.check motor coil insulation test by mugger(100mega ohm)- (body-coil-100mega ohm)and motor coil(hear motor star connection, show u-v,v-w,use is zero mega ohm)
    2.multimeter use coil resistance (ohm)
    u-v-5ohm,u-w-5ohm,u-w-5ohm -same resistance -good coil, if not same motor coil problem (new coil need)
    3.check free run any jam or noise
    4. check motor supply voltage (RY,YB,RB )
    5.check contractor supply voltage(if chattering)
    6.if problem check direct connect mcb or contactor (olr connection open)
    [Kirloskar Monoblock Pump 3 HP KDS 325++]