REF 615 Communication is established but when I tried to read from the relay, it started reading but suddenly stopped and showed a cancelled message. NB: I'm accessing the relay using PCM 600 2.11
Hello @bharatlalmali8695. To online monitor the application configuration, the complete IED configuration must first be written to the IED. - Only when the application configuration in the IED and PCM600 are the same, the online monitoring starts. - When the IED does not support online monitoring, the button is disabled. - The Work online function is not supported if the split window is enabled.
Hi, In REF615 relay trigger continuously breaker on and breaker service signal in the disturbance record how can we stop continuously triggering, I need one trigger only at the time, kindly give the information,thanks..
@Ilaya Raja it is difficult to answer without seeing the configuration. Please contact your local ABB channel, so they will contact factory customer help for support.
I had connection with new ABB Relay RET670, there is green signal as shown(no any red cross), this means there is sound connection. But when I tried to read for the internal configuration of relay setting in order to check and modify as per our requirments, while using read option or write option, it cant read issuing . It issued :Configure IED first. with remarks Cancelled> is there any configuration still do be done, what exact configuration is it looking for. At some point it "common read/ write menu", it comment section while writing it issued error at application configuration point and then signal matrix error(just flash for very short time which i got by using camera video mode to get what exaclty happened. But I coudnt configure the source of exact problem.
Hi ABB, can you please make a video on how to set the reclosing function (DARREC) of RER615. Also, in the phase and ground directional settings, is changing the curve types requires the change in the parameters (A, B & P)? For Schneider and SEL relays, the curve type does not require the change in parameters except for customized curves. We've done a SCIT, but the actual trip time does not match with the computed. Also, the reclosing function isn't working. Whom can we contact for our technical inquiries? Thank you. Christopher - Philippines
Hi Christopher, Thank you for your suggestion. Please check DARREC Technical notes available on the link abbtm.fi.abb.com/fi//attachments/TechnicalNotes/tech_DARREC_756960_ENc.pdf. If you need support, please, contact ABB Philippines Electrification unit (ph.electrification@abb.com) and they will address your request to the correct person.
@@ABBlearning Thank you for your reply, really appreciate it. Will communicate with ABB Philippines as we implement the technical guidance you gave. Thanks a lot.
Hay ABB I have a problem with relay ABB RET 650.. I used PCM 2.10 600 to connect with relay but the path is not of a legal form.. I need problem solving from you. Thank you
Dear Ilaya, The primary equipment can be controlled via the LHMI with the Open and Close buttons when the protection relay is set to the local-control mode and accessing the control operations is authorized. In 615 series Operation Manual, there is more details about the operating procedures. Regards, ABB Learning
Hello @mothanhattran2032. PCM600 can be freely downloaded from here: new.abb.com/medium-voltage/digital-substations/software-products/protection-and-control-ied-manager-pcm600/pcm600-downloads
@@ILAYARAJAraja, The synchronism and energizing check function SECRSYN checks the condition across the circuit breaker from separate power system parts and gives the permission to close the circuit breaker. SECRSYN includes the functionality of Synchro check and energizing check. In the command mode operation, an external command signal CL_COMMAND, besides the normal closing conditions, is needed for delivering the closing signal. In the command control mode operation, the Synchro check function itself closes the breaker via the SYNC_OK output when the conditions are fulfilled. In this case, the control function block delivers the command signal to close the Synchro check function for the releasing of a closing-signal pulse to the circuit breaker. In 615 series Technical Manual you can find detailed information about the SECRSYN function. Regards, ABB Learning
Hi Sajad, Please check Relion 615 series Modbus Communication Protocol Manual, search.abb.com/library/Download.aspx?DocumentID=1MRS756468&LanguageCode=en&DocumentPartId=&Action=Launch.
Hi..How can I access the application configuration/signal configuration in REU611 through PCM600? I was made to understand that the signal configuration can be accessed in both web HMI and PCM600 as per video in link below:- th-cam.com/video/T1dxW8AS4Yg/w-d-xo.html However I couldn't find the options to get to the application configuration in the PCM600 for 611 IED series. Please help!
Hi Akay, Thanks for your question. Application Configuration tool in PCM600 is not available for 611 series relays. You can use Parameter Setting Tool (Generic logic settings) in PCM600 for signal configuration of 611 series. Like shown in the video, in web HMI there is an easy way for signal configuration in 611 series as well. Regards, ABB Learning
@@nguyenvantung1987 Your correct model is REF615C and not REF615, you need download and install the connectivity package REF615C. Look at drive.google.com/drive/folders/1QhfTuG1FYWrb0OLDNT0SctNMPk1sDnAi?usp=sharing
I am unable to access the WHMI even though it is already ON/activated and have correct IP address. Do you have detailed video tutorial for this?
Hi, can we connect to front port from remote network ? (not same subnet)
REF 615 Communication is established but when I tried to read from the relay, it started reading but suddenly stopped and showed a cancelled message.
NB:
I'm accessing the relay using PCM 600 2.11
Thank you so much!!!
Hello sir, i am not able to use "work online" mode in PCM600. The "work online" tab is showing deactivate, please guide
Hello @bharatlalmali8695. To online monitor the application configuration, the complete IED configuration must first be written to the IED.
- Only when the application configuration in the IED and
PCM600 are the same, the online monitoring starts.
- When the IED does not support online monitoring, the button is disabled.
- The Work online function is not supported if the split window is
enabled.
nice information.thanks bro
Hi, In REF615 relay trigger continuously breaker on and breaker service signal in the disturbance record how can we stop continuously triggering, I need one trigger only at the time, kindly give the information,thanks..
@Ilaya Raja it is difficult to answer without seeing the configuration. Please contact your local ABB channel, so they will contact factory customer help for support.
I had connection with new ABB Relay RET670, there is green signal as shown(no any red cross), this means there is sound connection. But when I tried to read for the internal configuration of relay setting in order to check and modify as per our requirments, while using read option or write option, it cant read issuing . It issued
:Configure IED first. with remarks Cancelled>
is there any configuration still do be done, what exact configuration is it looking for.
At some point it "common read/ write menu", it comment section while writing it issued error at application configuration point and then signal matrix error(just flash for very short time which i got by using camera video mode to get what exaclty happened.
But I coudnt configure the source of exact problem.
Hi Sandes, thank you for your question. Please contact Hitachi ABB Power Grids' Customer Connect Center for support with RET670 IED.
Hi ABB, can you please make a video on how to set the reclosing function (DARREC) of RER615. Also, in the phase and ground directional settings, is changing the curve types requires the change in the parameters (A, B & P)? For Schneider and SEL relays, the curve type does not require the change in parameters except for customized curves. We've done a SCIT, but the actual trip time does not match with the computed. Also, the reclosing function isn't working. Whom can we contact for our technical inquiries? Thank you.
Christopher - Philippines
Hi Christopher,
Thank you for your suggestion.
Please check DARREC Technical notes available on the link abbtm.fi.abb.com/fi//attachments/TechnicalNotes/tech_DARREC_756960_ENc.pdf. If you need support, please, contact ABB Philippines Electrification unit (ph.electrification@abb.com) and they will address your request to the correct person.
@@ABBlearning Thank you for your reply, really appreciate it. Will communicate with ABB Philippines as we implement the technical guidance you gave. Thanks a lot.
Hay ABB
I have a problem with relay ABB RET 650..
I used PCM 2.10 600 to connect with relay but the path is not of a legal form..
I need problem solving from you.
Thank you
Hi Paulina, thank you for your question. Please contact Hitachi ABB Power Grids’ Customer Connect Center for support with RET650 relay.
Good
Menu-control-CBXCBR, this section not getting access to close BREAKER, I need access to close from this section, what I want to do to,
Dear Ilaya,
The primary equipment can be controlled via the LHMI with the Open and Close buttons when the protection relay is set to the local-control mode and accessing the
control operations is authorized. In 615 series Operation Manual, there is more details about the operating procedures.
Regards,
ABB Learning
Where can i find REB670 technical key?
Hi Rohit, thank you for your question. Please contact Hitachi ABB Power Grids' Customer Connect Center for support with REB670 IED.
wrongly said DHPC service instead of DHCP Dynamic Host Configuration Protocol
Hello @ranjithkumar-yn2um. Noted.
Hi guy, Could you tell me How did you do to setup PCM600? I don't find PCM600 driver. Thank you!
PCM600 is available from ABB Library. Create login prior to accessing. www143.abb.com/SoftwareLibrary/Library
Hello @mothanhattran2032. PCM600 can be freely downloaded from here: new.abb.com/medium-voltage/digital-substations/software-products/protection-and-control-ied-manager-pcm600/pcm600-downloads
How to do manual syn enable in REF 615 relay
Hi Ilaya,
Could you please clarify what kind of “syn” you are referring to, so then we can assist you better?
@@ABBlearning manually enable synchronize from the relay itself
@@ILAYARAJAraja,
The synchronism and energizing check function SECRSYN checks the condition across the circuit breaker from separate power system parts and gives the permission to close the circuit breaker. SECRSYN includes the functionality of Synchro check and energizing check.
In the command mode operation, an external command signal CL_COMMAND, besides the normal closing conditions, is needed for delivering the closing signal. In the command control mode operation, the Synchro check function itself closes the breaker via the SYNC_OK output when the conditions are fulfilled. In this case, the control function block delivers the command signal to close the Synchro check function for the releasing of a closing-signal pulse to the circuit breaker.
In 615 series Technical Manual you can find detailed information about the SECRSYN function.
Regards,
ABB Learning
Hello dear
Can help me about point list ref 615 modbus register address mapping.
Hi Sajad,
Please check Relion 615 series Modbus Communication Protocol Manual, search.abb.com/library/Download.aspx?DocumentID=1MRS756468&LanguageCode=en&DocumentPartId=&Action=Launch.
Hi..How can I access the application configuration/signal configuration in REU611 through PCM600? I was made to understand that the signal configuration can be accessed in both web HMI and PCM600 as per video in link below:-
th-cam.com/video/T1dxW8AS4Yg/w-d-xo.html
However I couldn't find the options to get to the application configuration in the PCM600 for 611 IED series. Please help!
Hi Akay,
Thanks for your question.
Application Configuration tool in PCM600 is not available for 611 series relays. You can use Parameter Setting Tool (Generic logic settings) in PCM600 for signal configuration of 611 series. Like shown in the video, in web HMI there is an easy way for signal configuration in 611 series as well.
Regards,
ABB Learning
Hi abb Can I get Arabic subtitles for the video
hi,REF542plus please
Hello, what do you need?
@@M.Elvis_Jacinto hi i need to estract fault record from an ABB REF543 via PCM600
Hello @hiloufalakhdar1065. Plesae contact your local ABB service representative.
hii ABB ,
I need help,Username and password Administrator WHMI REF611 ABB. Factory default password or shall we set it.
Hominhduc- Vietnam's
Thanks.
Hello @H.M.D_support_ABB. WHMI Admin Password: remote0004
what is the password for web ADMINTRATOR in the browser ?
The user and password is: SuperUser
So in case the computer reports the wrong code order and cannot find it, why? Detail to view the below hyperlink , pls
th-cam.com/video/bLww_xg0xM0/w-d-xo.html
@@nguyenvantung1987 Your correct model is REF615C and not REF615, you need download and install the connectivity package REF615C.
Look at drive.google.com/drive/folders/1QhfTuG1FYWrb0OLDNT0SctNMPk1sDnAi?usp=sharing
Hi Abb Can I get Arabic subtitles for the video