I have been following your channel from quite long time. Every video is very informative. I am benefited alot from your video. My humble request make a video on 1. Chemical dosing (matual and automatic) 2. Chilled water pressurisation unit 3. Chilled water line flushing (most needed).
Sir agar load 100% acheive ho geya hai or 100gpm 44 F water secondary pump k through chala geya or 100gpm 44 F decoupler line se primary motor mai a geya than ye 100gpm with 44F and return se 100gpm with 56F mill ke low delta T nahi ho jeya ga?
And sir zaroori nahi k har floor pe aik aik Ahu hon or hum pd sensor top pe lagaty hyn but design requirment agr ahus aik floor pr 2 ya 3 bhi hotay hyn or remaining floor pr 1 ya 2 to dp sensor kahan adjust kerte hyn than how it works out?
Sir first question k reply k liay thanks clear ho gya he, mera second question ye he k Ap nay jasy btya k off load pay jo return air ay gi us ka temperature b 56 rhy ga lakin jo water by pass ho raha he secondary pump say us ka temperature tu 44 hi rhy ga, is terha jb AHU ka retrurn Aur by pass ka water mily ga tu temperature 56 say km ho ker 50 nhi ho jay ga same constant volume system ki terha?
Video me maine explain kiya h k part load pe hmara 3 chiller me se 1 chiller off ho jayega or uske sath sath 1 primary pump v off ho jayega...jaise hi primary pump off hoga us case me bhut hi come amount me CHW bypass hoga jisse CHWR k temperature me bhut minutes difference ayega jiski wajah se baaki ke 2 chiller unload hone shuru jayege jisse k hmari power consumption come ho jayegi..ek chiz mai or add krna chahunga k primary-secondary system me secondary pump ka water flow maximum case me primary pump se zyada hota hai, kyu ke building me bhut sare equipments hote h to secondary loop me zyada GPM chahiye hota hai..isliye water bhut kam amount me bypass hota hai...
Sir Ap nay jis terha video me kaha k jb aik AHU ka 2 way valve close ho ga tu dosry AHU ka b 2 way valve close ho jay ga Aur load kam ho jay ga but mera question ye he k her aik floor ki apni cooling requirement hoti he suppose AHU #1 pay load km hota he tu lazmi tu nhi he k baki AHU ka load b km ho?
Mere kahne ka mtlab hai k jaise jaise floor pe temperature achieve hota jayega waise waise us AHU ka 2-way valve usi ratio me band hota jayega or jisse k ahu k accross water flow kam hota jayega or wo water Bypass line se cross ho kr primary me chala jayega....aisa ko rule nhi h k at a time sare ahu ka valve band hoga..ye understood hai k valve tab band hoga jab room ya floor ka temperature achieve hoga.....I hope ab aapko clear ho gaya hoga... comment kr ke confirm zarur krna.. thank you
Secondary pump ki frequency kam ho jayegi jisaki wjh se secondary pump ka RPM kam hoga or water flow v kam ho jayega jo energy saving ka sabse bada reason h
DPS has two ports, one portt will be connected to Supply line and other one will be connected with Return line to get the pressure difference between supply and return line
excellent video, u said PDS will be installed at high level, why? might i will got required temperature at low level floor, 2ndly if i have industry and all AHU,s will be on one roof horizontally, where i have to install PDS?
Hi, I think we receive the highest pressure at the last ahu either in case of vertically placed or in horizontal placed AHUs, that's why we are installing PDS there.
Good explanation...but what will happen if in case valves of secondary pump circuit are closed and PP is still running? Like, is it possible if there may be no secondary pump?
Sir apna 2 chiller 200tr iska GPM 800 hua but mera questions ye hi ki sir building ka load 50 percent hua toh vsd pump slow hua ab building ko 400gpm chahiye ye decopler line h vsd pump ke inlet and primary pump ke inlet se connect h sir ye samjh nhi aa raha h apna primary pump constent h ye depcopler se 800gpm le lega building 400gpm nhi ja payega sir depouler par automatic valve hona chahiye ki building ka 50 percent load ho toh decoupler valve se 50 percent water bypass ho
Good observation...jab building 50 prcnt pe operate hogi to schematic k according usko 600 GPM chahiye hoga or hamara primary pump 800 GPM delivered krega jisse decoupler se 200 GPM by pass hoga..ek point maine add nhi kiya jo mai add krna chahunga... primary-secondary system me secondary loop me zyada GPM building ko delivered krta hai maximum cases me...agar aap kisi v site pe jao waha dekhna building ka load zyada hoga to secondary pump ka flow rate primary se zyada hota hai to is case me building ko v zyada GMP chahiye hota hai kyu k bhut sare AHU hote hai..to us case me thoda paani bypass hota hai.... decoupler line pe automatic valve nahi lagate hai pani ka flow pump k pressure drop k according hota hai
Video mil jayegi apko....I hope apka doubt clear ho gaya hoga.... primary pump ka pura paani decoupler se suck nhi krega kyu k secondary pump v running condition me hai to wo v paani suck krega or aage building me bhejega... decoupler is chiz ko mind me rakh kr kiya jata hai uske bich ka pressure drop is trh se design kiya jata h k pura paani wapis se primary pump me na aye....
Dear sir, i could not get one point , why allways we put the 2way valve or picv valve on the outlet of the ahu or fcu , can we put it on inlet of fcu/ ahu , and put actuator which operate on temp sensor of return air , if room temp achived then it will close the supply valve to fcu , which is same as if we put picv down stream the fcu
dps be placed in which line as there is both supply and return line,for example 6floor building which floor it be placed.can i have ur mail id i have some doubt to learn can u help me out.
@trick-tech6623 zyada gyani ban jate ho. VFD or VSD k bare me ye video nahi h....ye Video piping system k bare me jisme pump ki speed vary karti h. Speed vary karne k liye VFD or VSD dono ka use Kiya jata h kyu dono ka kaam ek hi hai. Agar VFD k bare me janna hai to dusri video dekh lo.
And sir zaroori nahi k har floor pe aik aik Ahu hon or hum pd sensor top pe lagaty hyn but design requirment agr ahus aik floor pr 2 ya 3 bhi hotay hyn or remaining floor pr 1 ya 2 to dp sensor kahan adjust kerte hyn than how it works out?
Let's have 100 likes for this video
U deserve more like
@@shahidsiddique1432 thanks Shahid Siddiqui
Sir there is more than anything you deserve
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Very very knowledgeable video. 🙏🙇
Thank u so much sir.... Really I loved it.... thanx alot
Sir acche se explain krte ho, main abhi kuch din pahle hi aapke chanel pe aaya hu, or mujhe acchi knowledge mili hai
Thanks for the feedback
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Very good explain boss lot's thanks
Thank you very much sir now i am got secondary pipe line and primary pipe line bypass valve (decouple)🙏
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Very good explain sir thank you.....
Thank you for eloborating so clear and in simple words. Appreciate your efforts, keep doing good work.
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Very good👍👍
Bahut achcha samjhaya aap ne
Very good explain thank-you sir
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Very nice informations.
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Bahut khub sir excellent
Thanks
Very nice Information... your explanation way is very Good
Thanks
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Good 👍
Zbrdst bro ultimate appko professor hona chahye goood knowlage
Very nice explain thanks
I have been following your channel from quite long time. Every video is very informative. I am benefited alot from your video. My humble request make a video on
1. Chemical dosing (matual and automatic)
2. Chilled water pressurisation unit
3. Chilled water line flushing (most needed).
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Nice sir
Best explanation ❤
Glad you think so!
Wow...great....thanks dear
awesome information
Meaning content
Awsome
Excellent explanations sir
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Nice explanation
DP sensors & Temp sensors are liittle bit tricky & technical, explained well though
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Sir agar load 100% acheive ho geya hai or 100gpm 44 F water secondary pump k through chala geya or 100gpm 44 F decoupler line se primary motor mai a geya than ye 100gpm with 44F and return se 100gpm with 56F mill ke low delta T nahi ho jeya ga?
Excellent explain sir
Chlir or cling tawor ka keya cantion rahta hai plz Ripley
Love you sir
Love you too 😘
Nice video
Excellent sir ji
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
And sir zaroori nahi k har floor pe aik aik Ahu hon or hum pd sensor top pe lagaty hyn but design requirment agr ahus aik floor pr 2 ya 3 bhi hotay hyn or remaining floor pr 1 ya 2 to dp sensor kahan adjust kerte hyn than how it works out?
Great Sir
What is the process of calculation of de-coupler pipe size???
Ek size chota le kr connect kr do, part load pe chiller run karega, kabhi bhi 100% water to return lena nhi hai decoupler se.
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Sir first question k reply k liay thanks clear ho gya he, mera second question ye he k Ap nay jasy btya k off load pay jo return air ay gi us ka temperature b 56 rhy ga lakin jo water by pass ho raha he secondary pump say us ka temperature tu 44 hi rhy ga, is terha jb AHU ka retrurn Aur by pass ka water mily ga tu temperature 56 say km ho ker 50 nhi ho jay ga same constant volume system ki terha?
Video me maine explain kiya h k part load pe hmara 3 chiller me se 1 chiller off ho jayega or uske sath sath 1 primary pump v off ho jayega...jaise hi primary pump off hoga us case me bhut hi come amount me CHW bypass hoga jisse CHWR k temperature me bhut minutes difference ayega jiski wajah se baaki ke 2 chiller unload hone shuru jayege jisse k hmari power consumption come ho jayegi..ek chiz mai or add krna chahunga k primary-secondary system me secondary pump ka water flow maximum case me primary pump se zyada hota hai, kyu ke building me bhut sare equipments hote h to secondary loop me zyada GPM chahiye hota hai..isliye water bhut kam amount me bypass hota hai...
HVAC World thank you sir for your explanation
Sir, Primary pump kaise bnd hoga wo to without vfd hai
Kya manual off krege
Sir Ap nay jis terha video me kaha k jb aik AHU ka 2 way valve close ho ga tu dosry AHU ka b 2 way valve close ho jay ga Aur load kam ho jay ga but mera question ye he k her aik floor ki apni cooling requirement hoti he suppose AHU #1 pay load km hota he tu lazmi tu nhi he k baki AHU ka load b km ho?
Mere kahne ka mtlab hai k jaise jaise floor pe temperature achieve hota jayega waise waise us AHU ka 2-way valve usi ratio me band hota jayega or jisse k ahu k accross water flow kam hota jayega or wo water Bypass line se cross ho kr primary me chala jayega....aisa ko rule nhi h k at a time sare ahu ka valve band hoga..ye understood hai k valve tab band hoga jab room ya floor ka temperature achieve hoga.....I hope ab aapko clear ho gaya hoga... comment kr ke confirm zarur krna.. thank you
HVAC World G thanks
Sir jb load km hoga decopler line mai jayega to kya secondary pupm ki frequency km hogi ya same speed pe chalega
Secondary pump ki frequency kam ho jayegi jisaki wjh se secondary pump ka RPM kam hoga or water flow v kam ho jayega jo energy saving ka sabse bada reason h
@@HVACWorld sir agr water flow km hoga to primary pump k liye bhi water suction km hoga kya
Nahi...wo decoupler line se water suck kr lega
Ok thnku sir
dps which line it be placed,as there is 2 rises supply return.which floor it be placed if it is 6 floor building,
DPS has two ports, one portt will be connected to Supply line and other one will be connected with Return line to get the pressure difference between supply and return line
Hmra jo primary pump ha wo b vfd sa control hota ha.. sir.
Secondary pump nhi hoga usme
Dono hain sir
excellent video, u said PDS will be installed at high level, why? might i will got required temperature at low level floor, 2ndly if i have industry and all AHU,s will be on one roof horizontally, where i have to install PDS?
Hi, I think we receive the highest pressure at the last ahu either in case of vertically placed or in horizontal placed AHUs, that's why we are installing PDS there.
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Excellent very informative , just tell me what is roll of thermoste in the room , and it is linked to return air sensor ? Please.
May Allah bless you ,
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Sorry sir , I missed your live session today.
Excellent explanation..
No problem... thanks
Sir bms systems ke bare m bataiye
Would it be possible to create the chiller selection for various applications, such as commercial and residential, as well?
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Love you bro
Thanks
Why Ur installing modulating valve at the chiller outlet, on off valve is enough
It is on/ Off type
Good explanation...but what will happen if in case valves of secondary pump circuit are closed and PP is still running? Like, is it possible if there may be no secondary pump?
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Sir DPT return ka pressure kaise sense karta hai wo to supply me laga hai
I will explain you in video
Thanks sir Actually,My course is about to finish on 30August,If you can explain before 30 August I will be grateful for you.Thanks
30 August se pahle video mil jayegi with practical demonstration
Thanks sir❤️
Is there any English Version for ur valuable lectures ?
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Primary pumb kaha laga hota hai aur secdary pumb plz answer
Sir apna 2 chiller 200tr
iska GPM 800 hua but mera questions ye hi ki sir building ka load 50 percent hua toh vsd pump slow hua ab building ko 400gpm chahiye ye decopler line h vsd pump ke inlet and primary pump ke inlet se connect h sir ye samjh nhi aa raha h apna primary pump constent h ye depcopler se 800gpm le lega building 400gpm nhi ja payega sir depouler par automatic valve hona chahiye ki building ka 50 percent load ho toh decoupler valve se 50 percent water bypass ho
Good observation...jab building 50 prcnt pe operate hogi to schematic k according usko 600 GPM chahiye hoga or hamara primary pump 800 GPM delivered krega jisse decoupler se 200 GPM by pass hoga..ek point maine add nhi kiya jo mai add krna chahunga... primary-secondary system me secondary loop me zyada GPM building ko delivered krta hai maximum cases me...agar aap kisi v site pe jao waha dekhna building ka load zyada hoga to secondary pump ka flow rate primary se zyada hota hai to is case me building ko v zyada GMP chahiye hota hai kyu k bhut sare AHU hote hai..to us case me thoda paani bypass hota hai.... decoupler line pe automatic valve nahi lagate hai pani ka flow pump k pressure drop k according hota hai
@@HVACWorld sir chiller opreating kaise karte h bata dijiye step by step
Video mil jayegi apko....I hope apka doubt clear ho gaya hoga.... primary pump ka pura paani decoupler se suck nhi krega kyu k secondary pump v running condition me hai to wo v paani suck krega or aage building me bhejega... decoupler is chiz ko mind me rakh kr kiya jata hai uske bich ka pressure drop is trh se design kiya jata h k pura paani wapis se primary pump me na aye....
@@HVACWorld sir doubt clear ho gaya
Thanks
Hot well and cold well kya hotabhai sir... Or hot well se connect kya hota hai primary pump or secondary pump
Dear sir, i could not get one point , why allways we put the 2way valve or picv valve on the outlet of the ahu or fcu , can we put it on inlet of fcu/ ahu , and put actuator which operate on temp sensor of return air , if room temp achived then it will close the supply valve to fcu , which is same as if we put picv down stream the fcu
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
In vpf system where the water goes when system is return at part load
Can we have 2 sets (arrays) of pumps in the secondary side? (If there are 2 different types of loads with very different pressure drops)
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
Sir achutor kese manual open close karte hai ek bar bataye plz video me🙏🙏🙏
600 tr ka ek hi chiller ho sakta hai kya?
Zyada v ho sakta h
Humidity temperature KV Ritesh Himalaya temperature Ben 10
ye balancing valve Q lga rhe hai two way valve ke baad .iska kya opration hai
Is it possible to get a ladder diagram
Sir ji mujhe HVAC se koi diploma karna hai kon sa karu
HVAC in diploma nahi hota hai.... Diploma in Refrigeration and air conditioning se hota hai
K3 metalizer kae bar me kuchh batai sir ji apana number dijiye
Need to primary and secondary pump commissioning video upload (Mumbai)
Bhai to is system Mai bypass open hi rkhna hota hai
Sir ji vfd se load kam kyu ho raha hai
Pahle 100 % me chal raha tha abhi 40% me chal raha hai kyu
100% kab to or 40% kab hua???
Sir can you explain me how we calculate GPM
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
dps be placed in which line as there is both supply and return line,for example 6floor building which floor it be placed.can i have ur mail id i have some doubt to learn can u help me out.
If 6th floor is your furthest point, Install it on 6th floor
*5th floor
@@HVACWorld dps is placed in which line as there is 2 lines supply and return
TFA me kb se CHW water jane lga 😂
Hello sir
Hiii
Confusing.
100 TR ka AHU 😂
Isse zyada TR ka hota h
Please explain.. lot of respects Stay blessed
Sir i want your email id please if you feel easy. Because your channel have made my interest in HVAC.
th-cam.com/video/KQEh6t7pdCw/w-d-xo.htmlsi=gvbqOfQpDHeg804C
English please 😢
Bhai VFD Hota hai VSD Nahi to hai yaar correction kijiye pahle vedio ko
Vfd means variable frequency drive
Vsd means variable speed drive.
Bro plz enhance your knowledge before blaming someone.
@trick-tech6623 zyada gyani ban jate ho. VFD or VSD k bare me ye video nahi h....ye Video piping system k bare me jisme pump ki speed vary karti h. Speed vary karne k liye VFD or VSD dono ka use Kiya jata h kyu dono ka kaam ek hi hai. Agar VFD k bare me janna hai to dusri video dekh lo.
And sir zaroori nahi k har floor pe aik aik Ahu hon or hum pd sensor top pe lagaty hyn but design requirment agr ahus aik floor pr 2 ya 3 bhi hotay hyn or remaining floor pr 1 ya 2 to dp sensor kahan adjust kerte hyn than how it works out?