CT POLARITY || WHY CT STAR POINT IS ALWAYS FORMED TOWARDS PROTECTED OBJECT SIDE || PART-1

แชร์
ฝัง
  • เผยแพร่เมื่อ 18 ต.ค. 2024
  • Speaker information: Pankaj Kumar Jha
    Manager, Power Grid Corporation of India Ltd.
    (Power System Engineer with more than Ten (10) years of industrial experiences.)
    The concept of CT polarity is explained in detail in this video. Why CT star point is always formed towards protected object side??. The concept is explained through use of application example in Distance Protection Relay.
    Please click on the below link for watching the same video in English.
    • CT POLARITY || WHY CT ...
    We need your support...Why?
    An incredible amount of time and effort is needed to develop high-quality video tutorials. Each video takes approximately 6-8 hours to complete which includes learning the concept myself, brainstorming creative ways to teach and explain the concepts, creating the presentations, video recording, and editing. Your support truly makes all the difference. So, Please like👍🏻, comment and share this video with your friends and keep watching this channel for more such videos in future.
    #Lightningminds #pankajkumarjha

ความคิดเห็น • 68

  • @abdulrahuman9513
    @abdulrahuman9513 ปีที่แล้ว +2

    Your are very great teacher sir 🎉

  • @ajayyadav-xq7yv
    @ajayyadav-xq7yv 2 ปีที่แล้ว +1

    Well explained, this doubt finally got cleared after 2 years. Thanks you very much.

  • @patakotisrinivas1918
    @patakotisrinivas1918 ปีที่แล้ว

    Awesome explanation sir 👏 👍 👌...

  • @surendrakverma555
    @surendrakverma555 ปีที่แล้ว

    Very good. Thanks 🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏

  • @sharadkumarbhel
    @sharadkumarbhel 2 ปีที่แล้ว +1

    Well done pankaj ji...you have explained the concepts very simply... Actually you know where the listeners may be having doubts ..........Keep posting

  • @sharafatali731
    @sharafatali731 2 ปีที่แล้ว +1

    Thank you sir. Watching your videos is the best use of internet for me.

  • @unplannedjourney649
    @unplannedjourney649 2 ปีที่แล้ว +1

    Thank you sir 🙏

  • @yadavparvind6710
    @yadavparvind6710 2 ปีที่แล้ว

    Thanks sir ...very good video..

  • @rudraiti7922
    @rudraiti7922 ปีที่แล้ว

    Bahut accha samjhaya sir apne 🎉

  • @electricalomvlog7229
    @electricalomvlog7229 9 หลายเดือนก่อน

    Well explained sir

  • @aftabraj1865
    @aftabraj1865 3 ปีที่แล้ว

    Very great explanation

  • @techreviews8133
    @techreviews8133 3 หลายเดือนก่อน

    Super explanation sir👍👍

  • @ranjansahu2362
    @ranjansahu2362 2 ปีที่แล้ว

    So good sir n very simple explanation thank you sir

  • @ashishvitekar3474
    @ashishvitekar3474 ปีที่แล้ว

    Very nice explain and very informative video's keep it up.
    But my one doubt about why Internal relay coil don't pick up when ct current enters through star neutral point and also how the same coil pick up when CT current enter through phase end...
    Please clear my confusion/doubt.
    Thank you very much.

  • @ratnesh12100
    @ratnesh12100 ปีที่แล้ว

    Ultimate video, sir. You are genuinely doing great work to educate us free of cost. Lot of people having great knowledge but they don't think to deliver free of cost.. solute sir..

  • @anjanaghosh5444
    @anjanaghosh5444 2 ปีที่แล้ว

    Thank you sir

  • @pawanyadav-rp2nb
    @pawanyadav-rp2nb ปีที่แล้ว

    Thank you very much sir for sharing your experience and knowledge with us in such a great manner....I have one question if star point is reversed and current enter first from neutral side the it will go in all phase instead of R phase as mentioned then relay how will decide that fault in which phase

  • @arghyamukherjee8583
    @arghyamukherjee8583 2 ปีที่แล้ว

    Plz share the link this concept in case of transformer. Great sir. 1 year child can understand. 🙏🙏🙏

  • @muhammadqasimnoor3799
    @muhammadqasimnoor3799 2 ปีที่แล้ว +1

    Sir, while setting the relay we usually tell it where the star point is formed. Why do we have to specify that setting? Doesn't it automatically adjusts its perspective of sensing current so that it shouldn't matter where we have formed the star point?

  • @rodeopriya
    @rodeopriya ปีที่แล้ว +1

    Good explanation. Also plz mention the importance of pole discrepancy relay and it's setting.
    This is a basic video but mention Co ordination with other end cb auto reclosing.

  • @chandanmishra2624
    @chandanmishra2624 10 หลายเดือนก่อน

    Great sir,sir plz make a video in rotor earth fault scheme based on injection module

  • @swaransingh1690
    @swaransingh1690 3 ปีที่แล้ว

    Sir thanks for your hard work.

  • @RahulRai-gc1dv
    @RahulRai-gc1dv 2 ปีที่แล้ว +1

    Well explained ......👌

  • @adityanarayandash8668
    @adityanarayandash8668 2 หลายเดือนก่อน

    Tq sir❤

  • @rnamdeo4201
    @rnamdeo4201 ปีที่แล้ว

    Good

  • @marchedravi6301
    @marchedravi6301 2 หลายเดือนก่อน

    Sir, how can we analyse while running condition , if we formed the CT star point at the opposite side of the object

  • @burhanulmajeed1862
    @burhanulmajeed1862 ปีที่แล้ว +1

    The direction of the fault cannot be calculated on the basis of current alone since it is a sinusoidal wave. We need a polarizing quantity like phase voltage or sequence voltage and see the angle between the current and voltage to determine the direction of fault. CT polarity is not sufficient

  • @tuhinsubhradey
    @tuhinsubhradey ปีที่แล้ว

    Sir, What is the purpose of CT star point earthing? Kindly explain. Thanks.

  • @ZYXYZLF
    @ZYXYZLF 3 ปีที่แล้ว

    Namaskaar
    Really helpful to understand CT connections in the right way. I hope in the coming days you will post more videos about protection.

    • @LIGHTNINGMINDS_PANKAJKUMARJHA
      @LIGHTNINGMINDS_PANKAJKUMARJHA  3 ปีที่แล้ว

      Thank you for your valuable feedback.... I will definitely upload videos on protection system... Stay tuned for more updates.

  • @santanu69
    @santanu69 หลายเดือนก่อน

    Sir in a reverse fault which relay sence..
    Is it a non directional fault
    I try to say forward fault/directional fault
    And reverse fault/non Directional fault is it right sir

  • @himanshupatel8277
    @himanshupatel8277 9 หลายเดือนก่อน

    Sir relay m b newtral CT hota hai na sir please explain with the newtral CT of current direction

  • @deepikaved8182
    @deepikaved8182 3 ปีที่แล้ว

    Nice sir

  • @aeerdkptcl4017
    @aeerdkptcl4017 2 ปีที่แล้ว +1

    Sir any videos on DC ground

    • @LIGHTNINGMINDS_PANKAJKUMARJHA
      @LIGHTNINGMINDS_PANKAJKUMARJHA  2 ปีที่แล้ว +1

      Not uploaded till now but I will surely upload some video on DCEF, problem and rectification

  • @JitenderKumar-xp4hv
    @JitenderKumar-xp4hv 3 ปีที่แล้ว

    Sir
    Your videos are very nice and imparting good knowledge to viewers. These are more enrich than some slides.
    One more thing sir your voice is similar to Javed Akhtar sir…

  • @JitenderKumar-xp4hv
    @JitenderKumar-xp4hv 3 ปีที่แล้ว

    Sir pls keep posting other videos on different concept of power system protection.
    Jitender kumar JE SS Bhiwadi

  • @samratbhowmick8202
    @samratbhowmick8202 ปีที่แล้ว

    SIR, Please explain the CT CONNECTION FOR TEED PROTECTION in 5CT SCHEME

  • @electricalomvlog7229
    @electricalomvlog7229 9 หลายเดือนก่อน

    Sir , please give link this second session link

  • @sameerankit2000
    @sameerankit2000 2 ปีที่แล้ว

    CT ke P1 aur P2 terminal kidhar ke side rakhe ye kaise decide kare.

  • @satya7077
    @satya7077 3 ปีที่แล้ว

    Nice explanation sir... In next video pls explain how a relay summation or subtraction the tie bay & line bay current for metering or protection purpose...

    • @LIGHTNINGMINDS_PANKAJKUMARJHA
      @LIGHTNINGMINDS_PANKAJKUMARJHA  3 ปีที่แล้ว +1

      Thank you for your feedback.... I will explain this topic next week.... Tomorrow, I will upload the part-2 of CT Polarity.... The focus will be on application example with Differential Protection Relay.

  • @puneetsrivastava9764
    @puneetsrivastava9764 2 ปีที่แล้ว

    Sir beech beech main app topic ke andar alag topic kyu dal dete ho bht confusion ho gya hai

  • @saubhagyamaharana3922
    @saubhagyamaharana3922 3 ปีที่แล้ว

    Sir,
    If we make CT star point towards the protected object, then why we go for using voltage (CVT/PT) reference for ensuring direction as forward or reverse. i.e for polarisation.

    • @ajayyadav-xq7yv
      @ajayyadav-xq7yv 2 ปีที่แล้ว

      Upar se gya bhai thoda explain karo

  • @electricalomvlog7229
    @electricalomvlog7229 9 หลายเดือนก่อน

    Sir You have come at meerut Substation

    • @LIGHTNINGMINDS_PANKAJKUMARJHA
      @LIGHTNINGMINDS_PANKAJKUMARJHA  9 หลายเดือนก่อน

      मेरठ में तो ग्यारह साल रहा हूँ मैं।

  • @MadanSingh-un9ym
    @MadanSingh-un9ym ปีที่แล้ว

    Sir ais substation testing cb cvt wt LA iso ips tup power Trasfarmar video

  • @arghyamukherjee8583
    @arghyamukherjee8583 2 ปีที่แล้ว

    Sir plz share same concept in case of REF protection.

    • @LIGHTNINGMINDS_PANKAJKUMARJHA
      @LIGHTNINGMINDS_PANKAJKUMARJHA  2 ปีที่แล้ว

      I will upload a video on REF protection shortly. Stay Tuned.

    • @arghyamukherjee8583
      @arghyamukherjee8583 2 ปีที่แล้ว

      @@LIGHTNINGMINDS_PANKAJKUMARJHA thanks sir for your support.

    • @arghyamukherjee8583
      @arghyamukherjee8583 2 ปีที่แล้ว

      @@LIGHTNINGMINDS_PANKAJKUMARJHA may i talk with you by phone later . if u hv no problm.

  • @electricalomvlog7229
    @electricalomvlog7229 9 หลายเดือนก่อน

    Sir i m working at 765 kv meerut gis

  • @naman785
    @naman785 3 ปีที่แล้ว

    Wrong explanation

    • @sharadkumarbhel
      @sharadkumarbhel 2 ปีที่แล้ว

      You should also tell what's wrong.....

  • @electricalomvlog7229
    @electricalomvlog7229 9 หลายเดือนก่อน

    Well explained sir

  • @badshahibrahim8475
    @badshahibrahim8475 6 หลายเดือนก่อน

    Thanks sir ❤