Hello i have a question I also use smart load on my deye 6kw inverter I put my conditions for 50% 55% for the battery and the 1000w for PV For the on condition it is doing alright (when pv is higher than 1000w and lithium battery it kicks on) but for the off condition it only kicks on when the battery is below 50% and ignores the PV condition Can you explain that to me please
It swithes On when both parameters are met. It switches off when 1 parameter is not met >1min. It swithes back on after the battery has charged & both are met again. Your geyser's kW should preferably be lower than the PV setting, or you will cycle your battery a lot!
See manual: 1. Wire as an OUTPUT onto GEN input 2. Set SMART LOAD settings in GEN setup 3. Parameters set to switch output ON: a. Solar Watts must be reached b. Battery SOC% must be reached BOTH MUST BE REACHED TO SWITCH ON. To be done by an electrician!!!
Excellent setup on your geysers...
Hello i have a question
I also use smart load on my deye 6kw inverter
I put my conditions for 50% 55% for the battery and the 1000w for PV
For the on condition it is doing alright (when pv is higher than 1000w and lithium battery it kicks on) but for the off condition it only kicks on when the battery is below 50% and ignores the PV condition
Can you explain that to me please
It swithes On when both parameters are met.
It switches off when 1 parameter is not met >1min.
It swithes back on after the battery has charged & both are met again.
Your geyser's kW should preferably be lower than the PV setting, or you will cycle your battery a lot!
What does this Smart text mean?
How do I get smart load to work please 😊
See manual:
1. Wire as an OUTPUT onto GEN input
2. Set SMART LOAD settings in GEN setup
3. Parameters set to switch output ON:
a. Solar Watts must be reached
b. Battery SOC% must be reached
BOTH MUST BE REACHED TO SWITCH ON.
To be done by an electrician!!!
@@bolandsystems2024 what about setup when there is no option in menu solar watt. There is only bat On and Off?