Hi! I need help. In DTC mode, the motor must be equipped with an encoder and must be connected to the inverter or only in necessary cases must an encoder be attached to the motor. Thaks!
Hi. We use DTC mode for motor identification run, but we don't use encoder but Id run is performed perfectly. So, I don't think encoder is necessarily be connected to motor.
@@bishantkumar12589 Yes! I also think that it is only in special cases with certain applications that an encoder needs to be connected. in inverter default mode is DTC mode so i think it is suitable for most motor control applications without encoder.
ID run k liye DTC mode must hai, iske baad scalar mode daal sakte hai, no problem with that. WF k liy scalar mode chalega sir 👍 DTC mode bahut kam place pe critically use hota hai.
check parameter - 20.12 : must be - ON for acs880,,, Check setting of parameter 20.12 Run enable 1. Switch signal on (e.g. in the fieldbus Control Word) or check wiring of selected source.
Most of The application are run in DTC mode. But scalar control is nothing but a V/ F control . In DTC mode motor will get the better protection also energy consumption is less. So ID run is must required for DTC(direct torque control) control.
Why standstill !! Go for Normal ID run . If Motor shaft can be decouple from load. It will always better to get the Motor Characteristics Value by VFD during the Motor Identification Run In "Normal(Rotary)" mode. One thing to do better is to Perform A Power recycling if possible ! Or Control board Boot . (Parameter-96.08 )control board boot changing the value of this parameter to 1 reboots the control unit (without requiring a power off/on cycle of the complete drive module).the value reverts to 0 automatically.note: this parameter cannot be changed while the drive is running.
@@bishantkumar12589 ok understood। But standstill recommend when motor shaft decoupling from load is not possible or a huge hard job. Otherwise to take Normal ID run is always better for critical applications.
See As per manual "" Standstill ID run. The motor is injected with DC current. With an AC induction (asynchronous) motor, the motor shaft is not rotated. With a permanent magnet motor or synchronous reluctance motor, the shaft can rotate up to half a revolution. Note: A standstill ID run should be selected only if the Normal, Reduced or Advanced ID run is not possible due to the restrictions caused by the connected mechanics (eg. with lift or crane applications).
Check the cable. There are 2 types of cable. Both doesn't fit with each other. Check the connection port. Mismatch of port and connecting lead causes this issue. Or else. Replace the CDP
Superb 👌
Hi! I need help. In DTC mode, the motor must be equipped with an encoder and must be connected to the inverter or only in necessary cases must an encoder be attached to the motor. Thaks!
Hi. We use DTC mode for motor identification run, but we don't use encoder but Id run is performed perfectly.
So, I don't think encoder is necessarily be connected to motor.
@@bishantkumar12589 Yes! I also think that it is only in special cases with certain applications that an encoder needs to be connected. in inverter default mode is DTC mode so i think it is suitable for most motor control applications without encoder.
@@ch.industrialelectricity5625 Yes. Even you can select scalar mode if operation doesn't need very high precision.
Why we use or required to use id run parameter
Thankyou sir 🙏
Welcome sir. Please support the channel, subscribe and share 🙏
When parameters set ther anye auto twining option this drive which parameters no select??? Explane pleas next vidio
Okay
Sir Dcs 880 ke bare me v video baniye please
Okay sir. ASAP
Acs 880 control wiring par video banayiye Sir please
Soon sir
ID run complet hone ke bad DTC ya Scaler rakhna padega?
Weigh feeder ka Drive main Scaler rakha hai service engineer ne, isko DTC kadna padega?
ID run k liye DTC mode must hai, iske baad scalar mode daal sakte hai, no problem with that.
WF k liy scalar mode chalega sir 👍
DTC mode bahut kam place pe critically use hota hai.
@@bishantkumar12589 Thanks
@@5G... wlcm
hi
what that problem in my case what you think ? drive says "Run enable missing "
no run enable signal received
check parameter - 20.12 : must be - ON for acs880,,,
Check setting of parameter 20.12 Run
enable 1. Switch signal on (e.g. in the
fieldbus Control Word) or check wiring of
selected source.
hm i tryed open 20.12 setting but there is so many options did'nt understand what to choose
@@tomasmacius7023 select - ON for that
Abb acs 880 dtc mode m hi chalte hai kya sir
Nai. DTC must nai h, aap aaram se scalar mode me chala sakte ho.
Kindly share this TH-cam channel with your electrical team 🙏🏼
Ok sr but motor running mode torque negative shown on screen and control word hex 77 show kr change kaise kre
I am more share this vedio
Sir please make the video Dcs 880
Okay sir
Sir acs 880 me Encoder by aur circuits me kaise lete espar bhi video banayiyega please
Okay 👍
Hello brother... No display issue in ACS880.. now ready smps section, but I saw rating ID mismatch 5093.
Can u help me ?? Please
Rating has to be same brother else drive will not start
Vfd se speed Kum jada kesey krrte hai 🙏🙏🙏🙏🙏
Analog input pe speed depend karta h. Ya phir potentiometer se kar sakte hai
Hi bro thank u
Welcome sir
Sir How to check Motor Running Hours.VFD ACS880 . Please Reply
Pl check Parameter 05.04
Sir mere ko Eot crane ne acs 880 vfd lagani hai agar aapke pas drawing aur parameter pdf ho to bhej dijiye please
800 ka details I can arrange, abhi 880 install nai hua h yaha
Sir ID run ke bad local me kaise run karte par bhi video banayiye
Great
Thank you so much sir 😊 kindly share with your Electrical team 🙏🏽
sir please I need help I changed the main fan cooling, acs880
but the warning message is still on display A581
You have to reset the fan working time using laptop. I have made a video regarding it for ACS 800. You can check. It will be useful
thanks sir,
please i want n purchase remote for ACQ 80 solar pump Drive ,
where can available
Sir. Right now I don't have any idea. I'll ask abb vendor once
👌
After I'd run 99.04 Parmentier necessary to change scalar
No sir. Keep it as dtc only
Most of The application are run in DTC mode.
But scalar control is nothing but a V/ F control .
In DTC mode motor will get the better protection also energy consumption is less.
So ID run is must required for DTC(direct torque control) control.
Thanks
TQ.
I am getting AE8C warning CODE IN ACS880 HMI,CHANGED The battery CR2032 ,3V of HMI but warning still persists..What to do..Kindly help.
I'll check sir. Pl wait
Why standstill !! Go for Normal ID run . If Motor shaft can be decouple from load.
It will always better to get the Motor Characteristics Value by VFD during the Motor Identification Run In "Normal(Rotary)" mode.
One thing to do better is to Perform A Power recycling if possible ! Or Control board Boot . (Parameter-96.08 )control board boot changing the value of this parameter to 1 reboots the control unit (without requiring a power off/on cycle of the complete drive module).the value reverts to 0 automatically.note: this parameter cannot be changed while the drive is running.
But sir. As per MANUAL, standstill is recommended
@@bishantkumar12589 ok understood। But standstill recommend when motor shaft decoupling from load is not possible or a huge hard job.
Otherwise to take Normal ID run is always better for critical applications.
See As per manual
"" Standstill ID run.
The motor is injected with DC current. With an AC induction (asynchronous) motor, the motor shaft is not rotated. With a permanent magnet motor or synchronous reluctance motor, the shaft can rotate up to half a revolution. Note: A standstill ID run should be selected only if the Normal, Reduced or Advanced ID run is not possible due to the restrictions caused by the connected mechanics (eg. with lift or crane applications).
@@Sansangeetgeet08 ok sir. Thank you
BAHUT ASSA VI
TQ
Sir.. how to running hours show on display
Pl wait. I'll check and inform
Bro plz tell basic data of drive
Sure sir, soon. Many videos are available on this channel, ▶️ pl check ✅ you may find some useful ones
Sir abb Acs 580 Ka fault number 5093 ha
Rating ID mismatch fault hai aapka. Drive k hardware ka information match nai ho raha h drive k stored memory se.
Acs 550 current limt parameters?
Parameter : 20.03
Check parameter 20, that's Limit - 2003
By 2003 speed decreases
When current increase certain limit speed decrease
@@flyingzero4840 no such relationship
880 me standstil & 800 me reduce kiun ?
Terms are difference h Dost.
Standstill and Reduced are totally different options
Sir Disply nòt show any problem solve solution
Check the cable. There are 2 types of cable. Both doesn't fit with each other.
Check the connection port. Mismatch of port and connecting lead causes this issue.
Or else. Replace the CDP
What is id run?
Motor identification run. Drive get to know about the motor details.
Check my channel, u will find seperate video about it.
ID run ka meaning
Identification RUN
Thank u sir
Welcome