Ji puchna yah tha hamare pass ach 580 drive hai kya yah hybrid hai kya yah solar aur grid se at a time share karti hai iski setting kaise karen jab ham grade pay lagate Hain to yah Sara current grade se leta hai solar se nahin leta
I have a ACS580 VFD drive. I am facing a problem with auxiliary fan. The fan burned after 3-4 days. And after replace the fan, auxiliary fan fault continuous occurring. I have replaced the control card but not solved. Please help me
One of my VFDs is running with a fixed frequency 50Hz and it was running smoothly but nowadays the frequency becoming less than the fixed frequency(35Hz) suddenly. What is the cause for behaving like that?
ramp to stop means - drive will take some time (20 seconds) to stop the motor after giving STOP command. And: stop to coast is Emergency OFF, means to suddenly stop the motor
Hi brother , now since acs550 is absolute i need to replace it with acs 580. but in acs550 the frequency references (1103) i selected is 1. which is the similar parameter in ACS 580 ?
Informationfull video
Thank you sir. Please share with Electrical People
Osm video Good and useful information dear.
There's a relay provided for FAULT purpose only, RO3 . Incase for fault, it'll get activated
@@bishantkumar12589 ok bro thanks for sharing your knowledge.
What is the difference between motor control mode scaler and vector ?
If u want very precise control, use vector or DTC.
For normal control - scaler is okay.
Drop ur mail id - I'll forward the document.
Ji puchna yah tha hamare pass ach 580 drive hai kya yah hybrid hai kya yah solar aur grid se at a time share karti hai iski setting kaise karen jab ham grade pay lagate Hain to yah Sara current grade se leta hai solar se nahin leta
Power supply me switch over laga lo aap
I have a ACS580 VFD drive. I am facing a problem with auxiliary fan. The fan burned after 3-4 days. And after replace the fan, auxiliary fan fault continuous occurring. I have replaced the control card but not solved. Please help me
Pl share the Fault details. i.e. Fault number
One of my VFDs is running with a fixed frequency 50Hz and it was running smoothly but nowadays the frequency becoming less than the fixed frequency(35Hz) suddenly. What is the cause for behaving like that?
FOR ABB 580 ?
@@bishantkumar12589 Yes
Remote mode mei frequency change drive se karna hei karna hei sir edit karne nahi allow karra parameter kaunsa hei
Remote matlab Control room ya field ?
sir High temperature fault 4E04 how to fix this problem?
Check the status of cooling fan
Hi
Can you pls tell me the difference between v2.04.00 and v2.04.04 in acs580 drives
These are different versions of firmware software/program used in drives.
Ye kaam HVAC technician ko Janna chahiye ya chiller technician ko
HVAC 👍
Good sir
TQ
Hey....
Can you please explain the difference between stop to coast and ramp to stop ?
ramp to stop means - drive will take some time (20 seconds) to stop the motor after giving STOP command.
And: stop to coast is Emergency OFF, means to suddenly stop the motor
DI assigned karna start and run command ka leya ..any video ??
ACS 580 kar k search Karo aap mere playlist me. Aur v useful videos h
Drive me rmp kaise kam jyada kre hai use btao plz
Control/PLC se 4-20 mA se speed change hota hai. Aur local mode me HMI panel se kar sakte hai
Do you mentioned how to multiple speed options. Through Digital input
Yes it will be there, for digit input parameter
Speed up down via push button k liye parameters kya hai
Digital input use karte hai. Next video me full details batata hu. Be connected with channel
Hlo sir I have problem that wiring earth fault in abb can u say how to reset itt
Fault no ??? Name ??
Sir abb Acs 580 drive rating fault kasy jay ga
Nai jaega sir, motor rating hamesha Kam hona chahiye drive ki rating se.
Sir mere drive me 5091 fault code aa rha drive start nhi ho rha hai kya problem ho sakta hai
Safe torque off ka issue hai.
Check safety circuit connection. Yellow color ka ek slot rehta hai control board me. Wo loose hua hoga. Check that once.
Drive me DC voltage ke bareme kuch bata do.
Okay, uska proper content dekh raha hu.
th-cam.com/video/VGLz2Pp8yBU/w-d-xo.html
Please check this link sir
Hi brother , now since acs550 is absolute i need to replace it with acs 580. but in acs550 the frequency references (1103) i selected is 1. which is the similar parameter in ACS 580 ?
Hi brother. Check for parameter 22 - speed reference selection:
22.11 for Ext1 speed ref1
22.18 for Ext2 speed ref1
BHAI KOI PARAMETER KAM KA HAI BHI YA NAHI???
Hai na bhai.
I want send video inverter for you ?
ok
Dcs 800 dubble drive synchronisation ka video
Ok brother, I'll upload in sometime after getting complete details
D c under voltage falt acs580 how to relase
Check for - input supply - missing input phase, blown fuse Or fault in the rectifier bridge
Also. Check motor and power cable first
Nice sir
TQ sr
Sir ACS 850 me brake slip 603 fault aa rha h EOT CRME LGA H Kuch solution h to help kijiye
Iska idea nai h sir mujhe.
Vdf display showing check connections on PLC showing vdf 2 is trip mode
How send my video to you ? This video for abb acs580 i have problem
Tell the problem here. I'll help
sir please send me your whatsapp no
@@prakashaditya7151 sir, pl tell the issue.
Sir, ach580 vfd me bypass wiring me output phase lose error dikha raha hai Iss ku kiss parameter me jakar edit parameter karna Hai
31 me 19 no pramert ko no answer kr dena
Sir k am ka decribe nehi ha....
K am ??? Parameter number batana
ABB parameter check connection error
th-cam.com/video/HIYO2EVyw2o/w-d-xo.html
Earth fault kaise thik kare sir
Motor and power cable thik hai ?
Pdf kesa milega sir
www.google.com/url?sa=t&source=web&rct=j&opi=89978449&url=library.e.abb.com/public/052c19b4002f45cf908d536363a39bb4/ASCD2216x_en.pdf&ved=2ahUKEwjAwa6CwuqIAxVkk1YBHV2SG1cQFnoECAcQAQ&usg=AOvVaw0v8HVeeMUL-8lrJznJbEjF
mujhe abb acs510 me language change karna hai chines se english karna hai
Parameter 9901 ... Pl check.
Pucture is not shown parameter name that is picture is not properly
Increase resolution
Hello
Yes
@@bishantkumar12589 Dear i need to your help to New inverter pararmeters settings give me your what's up num.
2310 fault as rha hai..
Simple case of OVERCURRENT. Check for over load on equipment. Also current limit in the parameters
Sir ap ka no mil sakta hai kya
Yahi msg kar do bhai.
@@bishantkumar12589 kuchh knowledge lena tha sir
@@jitendramarkosatyavan9571 can ask here