Electrical Disconnection Times Why they matter

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 พ.ย. 2024

ความคิดเห็น • 66

  • @learnelectrics4402
    @learnelectrics4402  3 ปีที่แล้ว +3

    SEE ALL - To view a list of all our LearnElectrics videos, click on the link below.
    There are many videos on many electrical topics including Installation, Part P, 18th Edition, Testing, Certification, Lighting, Sockets, Ring Circuits and much more.
    th-cam.com/channels/YaJQnpO4XAp0yCgqzMkmfA.html

  • @no_short_circuit
    @no_short_circuit 3 ปีที่แล้ว +7

    As an adult learner this explanation is just what I need. Clear and simple, thanks very much.

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      Super feedback. Really appreciated. We try to keep to one topic, one video; we find people absorb it better - any age. Thank you very much. Dave.

  • @jmohammad3762
    @jmohammad3762 3 ปีที่แล้ว +5

    Another great video by Learn Electrics. Going through all the e-learning libray which is very helpful.

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว +1

      Excellent stuff. Never stop learning, it all adds up to a lot of knowledge after a few months

    • @jmohammad3762
      @jmohammad3762 3 ปีที่แล้ว

      @@learnelectrics4402 Could you please clarify if the supply is a 3 phase system and is feeding a 3 phase circuit would the disconnection time be 0.2 seconds

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      It depends what your voltage to earth is, if it is TN or TT , what the load is, and if it is a final circuit or distribution circuit. Go over the video again and check those four points. Thanks for watching. Dave.

  • @jeffreybrown6597
    @jeffreybrown6597 3 ปีที่แล้ว +1

    Your link worked, Bux, and I love how this is simply and concisely laid out!

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      Thanks Jeff, glad you like the format. Pass on the link, it will really help.
      Type in LearnElectrics all one word into TH-cam search bar to access all our videos.
      Bux

  • @nabilchauffage
    @nabilchauffage ปีที่แล้ว

    I appreciate your explanation, it's the best I've ever heard

  • @eliteelektriker6655
    @eliteelektriker6655 2 ปีที่แล้ว

    This is explaind so simpel and understanable it’s just great, thank you vert much from Denmark 👍🏻

    • @learnelectrics4402
      @learnelectrics4402  2 ปีที่แล้ว

      Happy to help. Thanks for the great feedback, appreciated. Dave.

  • @andrewforsyth4799
    @andrewforsyth4799 ปีที่แล้ว

    Excellent again helps me reinforce past learning thanks

    • @learnelectrics4402
      @learnelectrics4402  ปีที่แล้ว

      That's good to know, and thanks for watching. Dave.

  • @markandrews8437
    @markandrews8437 3 ปีที่แล้ว

    That was very interesting totally forgot about 400 and 440 volts followed this step by step with the regs book out 😔 sad I know keep them coming and thanks for sharing

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      We can't all remember everything all the time. So glad we could prod some long forgotten memory. lots more to come. Thanks. Dave.

  • @BAYUMBE
    @BAYUMBE 3 ปีที่แล้ว

    Very great presentation. Thank you Dave for your time.

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      Super feedback Omar. Thank you so much. Lots more to come.
      Dave

  • @ashokpatel2700
    @ashokpatel2700 3 ปีที่แล้ว

    Thank you for posting. There is a Typo in the table shown at 2min 25secs . Last Column heading.

  • @electricalstuff259
    @electricalstuff259 2 ปีที่แล้ว

    In your example about a 440v 3-phase supply that requires 0.2s disconnection time, what table do we look in to determine what the Zs should be for circuits on this installation?

    • @learnelectrics4402
      @learnelectrics4402  2 ปีที่แล้ว

      If its a type B breaker, the Type B tables, the same as single phase. Type C tables for Type C etc. The same tables that are used in the video. Note that the disconnection time comes down to 0.1 seconds in the tables so easily achieves 0.2 seconds for the breaker.

    • @electricalstuff259
      @electricalstuff259 2 ปีที่แล้ว

      @@learnelectrics4402 Sorry i don't understand what you mean - what table does it say that in? All the tables i see say 0.4s or 5s max disconnection time so where would you search (and know to search there just by reading the regs) to find 0.2s times?
      ie, i open the book, i look at Table 41.1, i see 0.2s for 230->400v, i now go searching for the table that tells me the max EFLI measurement for circuit breakers with Uo of 400v, to give compliance for the 0.2s breaking time.
      How do i know where to look and where is the information?

  • @Hossin-x3i
    @Hossin-x3i 3 หลายเดือนก่อน

    Excellent..
    .very useful

  • @paulneary703
    @paulneary703 3 ปีที่แล้ว

    a distrubution circuit feeding an out building 16mm swa on 50A MCB will that have disconnection time of 5seconds and would that need to be a type D as table 41.3 only gives 5sec disconnection times on type D? also fixed appliances above 32A, so a cooker clipped direct on 6mm with 40mcb will that be 5 seconds as well? many thanks great videos!

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      Paul, the 5 seconds is a maximum. There is nothing wrong with a type C or B. They will achieve disconnection in less than 5 secs (less than 0.4 in fact) and this complies with the requirements of the Regs. Have a look at the top right charts on p370/371 in the Wiring Regs. These devices achieve 0.1 second for final and distribution circuits.
      If only fixed appliances yes 5 seconds, but again, most MCBs will achieve less than 0.4 seconds anyway. Good questions. Keep watching.

    • @paulneary703
      @paulneary703 3 ปีที่แล้ว

      @@learnelectrics4402 thanks for that while I understand 5s is maximum what would you write down on schedule of test results for circuits mentioned above 0.4 or 5s ? Thanks 🙏

  • @dennisfowler7873
    @dennisfowler7873 3 ปีที่แล้ว

    Is a type C circuit breaker recommend for a distribution circuit

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      We used to fit type C in industrial distribution boards as they are a little less sensitive thatn the B types and then Type B for the final circuit. Just make sure the Zs readings are good.

  • @afzalmakh9561
    @afzalmakh9561 3 ปีที่แล้ว

    A very well explained. Thank you sir

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      You are very welcome Afzal. Thanks for the great comment. Lots more to come. Dave.

  • @usmanellahi5753
    @usmanellahi5753 2 ปีที่แล้ว

    God bless you 👍👍👍😊

  • @Dibbo1979
    @Dibbo1979 3 ปีที่แล้ว

    Great video mate👍🏻

  • @alancooper7018
    @alancooper7018 2 ปีที่แล้ว

    Didn’t word my previous question well. I thought table 41.3 applied to TN systems and not TT as well?

    • @learnelectrics4402
      @learnelectrics4402  2 ปีที่แล้ว +1

      Alan, the point I was trying to make was that you can use Table 41.3 to make a close estimate to what the internal wiring R1+R2 of a TT system should be by subtracting 0.35 ohms from the Zs in T41.3.
      I've seen some installs where the R1+R2 was stupidly high because the installer thought they could keep adding on up to 200 ohms. I suppose when the lights go dim they will know something is wrong.
      Thanks for the feedback and for watching the channel. Dave.

  • @MS-Patriot2
    @MS-Patriot2 3 ปีที่แล้ว

    Did the 80% rule for measured Zs come about to accommodate that Uo is often > 230V or is it to allow for less than perfect terminations and probing when taking a reading? Hang on I think I’ve found it. BS7671 tables 41.2 -41.4 give max Zs at 70 degrees C. We usually measure at around 20 degrees, where electrical resistance is deemed to be 0.8 of the tabulated value.

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      That's correct Mike, we lower the resistance starting point so that at &0 degrees it does not exceed the tabulated value in the Regs book.

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      70 degrees

  • @WILL-fu6jk
    @WILL-fu6jk 3 ปีที่แล้ว

    So the maximum disconnection time is the maximum amount of time that a circuit can be disconnected for until a danger is apparent ?

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว +1

      No. Watch the video again and you will see that there is a danger there all the time. After the maximum disconnect time you may have a dead body, before that, a healthy adult should survive. That is why we want the fuse to blow before max disconnect time. Danger is always present. Keep watching, keep learning, it will all drop into place.

    • @WILL-fu6jk
      @WILL-fu6jk 3 ปีที่แล้ว

      @@learnelectrics4402 Now I understand. New subject to me so the concept “maximum disconnection time” I haven’t heard before.
      I understand now that there is a maximum disconnection time for specific types of circuits. If this time has passed and the fuse hasn’t cut the circuit then your trouble. I assumed this Was something to do with a circuit being disconnected and thus a maximum disconnection time was then present.

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      That's it Will. If we can disconnect the circuit in less than 0.4 seconds there is a good chance the person survives.
      Keep learning, keep watching the videos and it will begin to make sense. After more than 40 years, I'm still learning. love it. It's a great trade to be in. Dave.

  • @SeanyyBoy_
    @SeanyyBoy_ 11 หลายเดือนก่อน

    so a 40a cooker has a disconnection time of 5s?

    • @learnelectrics4402
      @learnelectrics4402  11 หลายเดือนก่อน +1

      For the breaker, yes, but don't forget about the RCD which gives 0.3 seconds or less. Dave.

    • @SeanyyBoy_
      @SeanyyBoy_ 11 หลายเดือนก่อน

      @learnelectrics4402 brilliant, though now I need to learn more regs as I was under the impression they didnt necessarily need to be on RCD's (down to method of installation, though they're usually run in the fabric of the building, hence requiring one)

  • @asdfghjkl52472
    @asdfghjkl52472 8 หลายเดือนก่อน

    whats the difference between maximum disconnection time and the actual disconnection time? ta

    • @learnelectrics4402
      @learnelectrics4402  8 หลายเดือนก่อน

      Max disconnect time is the time suggested by the regulations. The breaker must disconnect before this time given a certain fault current. Actual is ... actual. The time for that actual device in front of you. For a correctly designed circuit, the actual will never be more than the maximum. have a look at this video.
      th-cam.com/video/QWr-ilqW67A/w-d-xo.html
      Hope this helps.

    • @asdfghjkl52472
      @asdfghjkl52472 8 หลายเดือนก่อน

      @@learnelectrics4402thanks that’s really helpful actually

  • @Khanjan-si8me
    @Khanjan-si8me 3 ปีที่แล้ว

    Can you please do one video a but IPX7 OR IPX4

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      We have a video on IP codes see the link below.
      th-cam.com/video/bWJ_xZIpuN0/w-d-xo.html
      There are nearly 60 videos on our channel and we are adding to them all the time.
      To get access to them all, click on subscribe or type in LearnElectrics all one word into the search bar.

    • @Khanjan-si8me
      @Khanjan-si8me 3 ปีที่แล้ว

      Can you please do video on maximum demand please..🙏

    • @Khanjan-si8me
      @Khanjan-si8me 3 ปีที่แล้ว

      @@learnelectrics4402
      Can you please do video on maximum demand please..🙏

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว +1

      There is a video on Diversity coming up very soon.

  • @Hossin-x3i
    @Hossin-x3i 2 หลายเดือนก่อน

    Example 2 answer is 0.2 but you write it 0.4 but you say 0.2 but write wrong answer ..
    Thanks alot

    • @learnelectrics4402
      @learnelectrics4402  2 หลายเดือนก่อน

      Yes, this is a typo, it should of course be 0.2. I may republish this video. Meanwhile, this proves that you are on the ball, and I appreciate that, thank you. Dave.

  • @j9spirit407
    @j9spirit407 3 ปีที่แล้ว

    TT systems you circled 0.2 but the answer you put 0.4 above. Example 2

    • @learnelectrics4402
      @learnelectrics4402  3 ปีที่แล้ว

      You are right, we did. We will alter that. The answer is 0.2 seconds. Thank you.
      Hopefully it didn't distract you too much. Dave.

  • @souljimmy1
    @souljimmy1 2 ปีที่แล้ว

    Hi 👋 dave " have you blocked me 🤔i keep trying to comment on your vids " but it says this site won't allow your comment????

    • @learnelectrics4402
      @learnelectrics4402  2 ปีที่แล้ว +1

      No, not blocked at all and your comment has just come through. i am replying to it.
      let's hope its ok now. Dave.

    • @souljimmy1
      @souljimmy1 2 ปีที่แล้ว

      @@learnelectrics4402 OK thanks" just sent off for my 18th addition on site guide 😀 so I can do your class work 📘🖋💼🤭