Walk-In Cooler Warm and Compressor Is HOT

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ก.ค. 2020
  • This walk in cooler was warm and took some investigating to find all the problems that were wrong. The compressor would not run for long even after cleaning the coil.
    💥 Facebook - / hvacrsurvival
    💥 Email- hvacrsurvival@gmail.com
    💥 Want to help support the channel? paypal.me/RickDirmeyer
    💥 WANT TO SUPPORT THE CHANNEL BY PURCHASING THE TOOLS I USE? kit.co/hvacrsurvival
    💥 Amazon Store: www.amazon.com/ref=as_li_ss_t...
    💥 Anything not listed in my kits can be purchased through my amazon store using the link above if you would like to support my channel without costing you a penny more.
    💥 My crimper www.cleavelandtool.com/Rachet-...
    Warning Notice Disclaimer - Video content listed on the channel HVAC*R Survival is for entertainment purposes only and not meant to be a substitute for not contacting a competent HVAC/R PROFESSIONAL. Do not attempt anything said or seen on my videos, The tasks that are shown are dangerous and deadly without proper training.
    This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission. HVAC/R Survival is a participant in the Amazon Services LLC Associates Program.
  • บันเทิง

ความคิดเห็น • 118

  • @nickcampbell8096
    @nickcampbell8096 4 ปีที่แล้ว +5

    Good video Rick, that was an interesting one. I learned the hard way with strapping ladders. When I first started working the wind blew my ladder off and it hit someone’s car. I was lucky it did not hit a person. Now I strap my ladder every time no matter what.

  • @hassanaljazaeri5436
    @hassanaljazaeri5436 4 ปีที่แล้ว +5

    Good video I never thought of replacing the fan

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +5

      It took me awhile to figure it out. The amperage was over but I blamed that on the capacitors originally. The oily motors were what justified the replacement for me. Thanks 4 the feedback 👍👍

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 ปีที่แล้ว +2

    Those new fans are definitely spinning much faster than before

  • @steve19841117
    @steve19841117 4 ปีที่แล้ว +1

    box hot cause lowside high and lowside high cause the highside high . that is the point . thank you Rick

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      Yep, I sometimes forget the basics just like everyone 😏

  • @curioushvacguy6876
    @curioushvacguy6876 4 ปีที่แล้ว +1

    Great Video Rick

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Thanks Curious ZZ top guy 🤣. My true dispatcher at work asked me who the ZZ top guy was from last week's live show 🤣🤣.... I said that's the guy I keep telling he needs to come to work for us 😎😎.

    • @anythingchannel6159
      @anythingchannel6159 หลายเดือนก่อน

      @@HVACRSurvival sorry to msg here but can you tell me what’s different between a19aba-45 and a19aba-45c?
      A tech came and replaced it and saw that the model # doesn’t match but said they’re same.

  • @calebburns4346
    @calebburns4346 4 ปีที่แล้ว +7

    Even with the frames per second the old motors still looked slow. When you swapped em the new ones were moving much faster

  • @evasmechanical3902
    @evasmechanical3902 4 ปีที่แล้ว +2

    Great video Rick, i agree with water access on roof. I guess they worry someone will leave it on.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Lol. It's all about money. How much they can save at first but cost a lot more later 😠

  • @williamnussey9884
    @williamnussey9884 4 ปีที่แล้ว +1

    Good job.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Thank you 👍👍. Sorry for the slow response, these comments someone's get hidden.

  • @donnierobertson3088
    @donnierobertson3088 4 ปีที่แล้ว +1

    Nice job and video

  • @samuelaranda157
    @samuelaranda157 4 ปีที่แล้ว +1

    Great explanation of your trouble shooting

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      I try to work my way through the usual problems and just eliminate one by one. I appreciate the viewership and feedback 👍👍

    • @samuelaranda157
      @samuelaranda157 4 ปีที่แล้ว

      HVACR Survival great. I have been watching your video and other. I had emergency brain surgery from a hematoma. I have not been working for a year. I go back to work August 1. I had to do physical therapy and occupational therapy. I only have 3 years to retire full pension from the Union here in California. I had to learn how to walk again. I got a clean bill of health. I am lucky my employer wants me back. They said I can do Teck support and Project management to I retire.. I use to work for York/JCI chiller division and start up . This trade has taken me all over the world and met some of the most brilliant people . I am going to miss it when I retire. Your video has helped me and other videos from others helping me feel confident I still have my HVAC chops. Thank you for helping me feel confident

  • @shine-cg9uf
    @shine-cg9uf 4 ปีที่แล้ว +1

    Great video. Enjoy the process of diagnosis

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I'm glad your getting something out of these, that makes it all worth it for me 👍👍

  • @gas_man1565
    @gas_man1565 4 ปีที่แล้ว +3

    Good catch. sometimes the motors fool you. i carry a pressure washer that sucks water from a bucket so i dont have to depend on a water source for a nice cleaning. I do agree Buildings should all have water sources on the roof. Good job keep the videos coming.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I have a worx sprayer and a 120v pump motor, but with the weather breaking and the coil looking clean enough I didn't figure it would make that much more of a difference. Thanks for the view and feedback 👍👍

  • @heavydiesel
    @heavydiesel 4 ปีที่แล้ว +3

    If you wind the suction valve in to drop the suction pressure down to what it would be with a normal room temp, it'll give you more of an idea how the condenser is coping.
    Good call on the new motors!

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I have done that for compressors that are pulling over RLA, but haven't tried it in this situation 👍👍. I'll try it next time.

  • @tonydelgrego2906
    @tonydelgrego2906 4 ปีที่แล้ว +1

    Great video
    You have a good approach when trouble shooting a unit. I could see the difference in the fan speed when you changed them.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      unfortunately I noticed that while at home editing the video😁. Even with 60 fps the new motors were spinning much faster because you couldn't see them spinning in slow motion. (To the naked eye they looked the same.) Thanks for taking the time to check it out and leaving in a comment 👍👍

  • @crforfreedom7407
    @crforfreedom7407 4 ปีที่แล้ว +2

    Great video Rick! They never taught us how to diagnose a headmaster. Great stuff!!!
    I got a set of those dial gauges awhile back after I saw you use them: Great for low loss and instant response for pump downs and the like. Love em. Like my Fieldpiece too, but these definitely have their place!
    Smiled at the ghost of Jim Pettinato there with the nitrogen, good move! WELL DONE!!!

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +2

      I like them gauges because I keep them in my service bag. I think it's time to buy some new ones though, they're getting a little out of whack 😁

  • @Ted_E_Bear
    @Ted_E_Bear 4 ปีที่แล้ว +2

    Thanks for the great video !!

  • @randymack1782
    @randymack1782 4 ปีที่แล้ว +1

    great video, anything that helps me learn troubleshooting is great, &this was unusual.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      That's great to hear 👍👍 Thanks 4 watching them and I always appreciate the feedback.

  • @HughesManHVAC
    @HughesManHVAC 4 ปีที่แล้ว +1

    Excellent video!

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      I appreciate the view 👍👍

  • @Brisket9392
    @Brisket9392 2 ปีที่แล้ว +2

    Maybe add a tachometer to your kit. 1550rpm is the usual spec. Those likely were running closer to 800-1000rpm.

    • @Franklinveterinarycenter1of4
      @Franklinveterinarycenter1of4 11 หลายเดือนก่อน +1

      get a 4000 rpm.......that way, you can use it on small engines that generally run around 3000. Hercules HF 6 to 99,000 RPM with reflective tape.........or use HVAC reflective duct tape.

  • @xelaju8
    @xelaju8 4 ปีที่แล้ว +1

    Nice video. Thanks for sharing.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      My pleasure. I appreciate you taking the time to watch and leave me feedback👍👍

  • @sharky5570
    @sharky5570 4 ปีที่แล้ว +2

    Good stuff Rick.. my co workers are at the Toledo Amazon working in your neck of the woods

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      About 90 min away 👍👍. Thanks for checking out the video. 🤜🤛

  • @courtne-the-great7961
    @courtne-the-great7961 4 ปีที่แล้ว +1

    Very good video.

  • @georgeokeeffe3284
    @georgeokeeffe3284 4 ปีที่แล้ว +1

    Well Done 👍🏻 Great Vid 👌🏻😉

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Thanks George, I'm glad you enjoyed it 👍👍

  • @FireandFrostHVAC
    @FireandFrostHVAC 4 ปีที่แล้ว +2

    Interesting call. I think this was a good example of a lot of little things adding up to a bigger problem. Weak condenser fan motors, dirty condenser, a big load that the unit is trying to pull down, and a high ambient. I was thinking with those storm clouds rolling in the machine was probably dealing with a high Rh as well. Did you check for a temp difference across the filter dryer? That could increase your head too. I think the headmaster was operating properly. Good video, thanks.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Yea, it took a while but I finally got it. Thanks for checking it out!

  • @theangrytechnician6649
    @theangrytechnician6649 2 ปีที่แล้ว +1

    Been saying for years that if you have to have a light an outlet (NJ) by the time nits for service, why not water? Great video!

    • @HVACRSurvival
      @HVACRSurvival  2 ปีที่แล้ว +1

      I 💯 agree. But those types of rules would make sense, so hell with that🤦‍♂️😏

  • @TheLenaweeTrekker
    @TheLenaweeTrekker 4 ปีที่แล้ว +2

    I had a 20 door RIF go down. Unfortunately, the headmaster was in total bypass mode on the condenser. That was not a fun call.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      That's what I figured was happening at first. That sucks big time when it does.

  • @lawnmoose
    @lawnmoose 4 ปีที่แล้ว +2

    TOP NOTCH!

  • @trebrehenuf
    @trebrehenuf 4 ปีที่แล้ว +1

    Always wanted to try pressurizing pump sprayer with nitrogen , with safety relief of course.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Electric pump is a lot easier but either should work.

  • @courtne-the-great7961
    @courtne-the-great7961 4 ปีที่แล้ว +4

    The oil on the motor did not come from the motor.... I would spray the coils with chemicals and water to get them clean. Also I think you have oil migration too. Get that oil back to the compressor after the blocked evaporator and condenser coils are cleaned. Moving the oil takes time....

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I prefer washing the coils out any day over blowing them out, but the back door was bolted shut and I couldn't get it open and the drive-thru window was way up front so it would have made a heck of a mess. Thanks for the feedback 👍👍

    • @gas_man1565
      @gas_man1565 4 ปีที่แล้ว +2

      running hoses thru the drive thru window isnt a good option! It wasnt like the coil was greased up. Blowing with nitrogen is the only other way. Like i said in my response, i do have a pressure washer that sucks water thru a bucket.

  • @hvacknowledgechannel1621
    @hvacknowledgechannel1621 4 ปีที่แล้ว +1

    Gud vdo fan running

  • @ralphgiampietro85
    @ralphgiampietro85 4 ปีที่แล้ว +2

    At first glance the rotation on the fans seemed to have the blades backwards

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I'm shooting video at 60 frames a second so it slows down motion sometimes.

  • @deanmohamed7575
    @deanmohamed7575 4 ปีที่แล้ว +1

    Good one. Finally someone besides me has no water on the roof. They never make it easy for the techs. They will make it easy peasy for everyone else. Those new fans made a big difference, you can see the speed on the video. Can you post a link to your RPM tool?

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I'll see if I can find the link on Amazon and post the link.

    • @MrVanillaCappuccino
      @MrVanillaCappuccino 4 ปีที่แล้ว +1

      @@HVACRSurvival I'd like to see that rpm tool as well? I've never even heard of one

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      It's a tachometer. I'll get you a link for it.

  • @hvac01453
    @hvac01453 4 ปีที่แล้ว +1

    That’s odd, I have a walk-in freezer that was just like that. I washed the coil down first, replaced the headmaster too because it wasn’t cooling off even with water being sprayed on it he coil ( it should have crashed. ). Figured it was bypassing hot gas to the receiver just enough to make sure he head go high and nuisance trip me.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Just when you think you have it all figured out they can throw you for a loop 😁👍👍

  • @YuShudNoe
    @YuShudNoe 4 ปีที่แล้ว +2

    We need those clouds here in Arizona right now 😫😫😫

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      It's been very dry here lately. I recorded this a month ago.

  • @chainoflakesrefrigerationa2906
    @chainoflakesrefrigerationa2906 ปีที่แล้ว +1

    I have had a couple units do the same thing, fans seemed to checked out ok. I wonder if my issues were the same you had.

    • @HVACRSurvival
      @HVACRSurvival  ปีที่แล้ว

      Hard to tell but it's possible.

  • @harrydickson4575
    @harrydickson4575 4 ปีที่แล้ว +1

    👍👍👍

  • @chrisrouleau693
    @chrisrouleau693 4 ปีที่แล้ว +1

    Hi Rick great video just curious of how long that service call took you thanks

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I don't remember for sure but probably 2.5-3hrs with drive time.

  • @CDX825
    @CDX825 4 ปีที่แล้ว +1

    Did you come up with anything on the bosch unit? I can't find the video now? Wanted to report back with the findings on mine. The super heat was anywhere from 4 to 12 degrees depending on compressor RPM. Inside humidity is running anywhere from 53 to 62 percent.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      The supplier is trying to help get the system corrected so I removed the video. They ordered a adjustable TXV but that got delayed in a shipping issue so I don't have anything to report. I'm going to see if the correct superheat helps first before pressing for larger remedy's.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      If you would please, email me what you found and if it is working now at hvacrsurvival@gmail.com

  • @keehn20
    @keehn20 4 ปีที่แล้ว +1

    Lol gosh I hate when its like that.

  • @jerrywhite410
    @jerrywhite410 4 ปีที่แล้ว +1

    Dunno about that one.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      It was a weird one, I haven't had to go back and that was last month.

  • @sterlingarcher46
    @sterlingarcher46 4 ปีที่แล้ว +1

    What a difference a fan makes🎶 ... 22 little psiiiiii 🎶 😅

  • @RJMaker
    @RJMaker 4 ปีที่แล้ว +1

    Those clouds looked very angry..

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I got soaked when I tried getting inside because they locked the door because the high winds kept causing it to open 😁

  • @Eddy63
    @Eddy63 4 ปีที่แล้ว +1

    Good vid Slick Rick but I wouldn't let a little ole tinkle shower slow me down ... Lol ... Good stuff ...

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      I'm a pretty little flower, I didn't want to get wet 🤣🤛.

    • @Eddy63
      @Eddy63 4 ปีที่แล้ว

      @@HVACRSurvival Lol

    • @throttlebottle5906
      @throttlebottle5906 4 ปีที่แล้ว +1

      tinkle showers love to send sudden large deadly fire-bolts at you and I'd not want to be the tallest object on a roof, further that by touching fairly well grounded metallic equipment lol

  • @sterlingarcher46
    @sterlingarcher46 4 ปีที่แล้ว +1

    Hey , you know what they say : blows before hoses ... Sorry that was pretty bad ...

  • @austonlandhero3415
    @austonlandhero3415 3 ปีที่แล้ว +1

    What would cause a walk in freezer to run high head pressure besides condenser

    • @HVACRSurvival
      @HVACRSurvival  3 ปีที่แล้ว

      High load, suction goes up so will the head.

  • @joestinson7195
    @joestinson7195 4 ปีที่แล้ว +1

    what was the outcome on the bosch unit

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      I'm waiting for an adjustable TXV, I'm giving the supplier an opportunity to get the system running correctly. Once I have a remedy or hit a block wall I will let everyone know what worked or didn't work.

  • @DigitalIP
    @DigitalIP 4 ปีที่แล้ว +1

    Could someone direct me to a decent yet non expensive 20x20x5 MERV 11 Filter for a Goodman unit? with how much they tend to cost i'm trying to make sure i dont get the wrong one even if its the right size :/
    Getting to be about time for the new unit to need the filter replaced

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      Lowe's or Amazon. Merv 8 will work fine too.

  • @pepsicolachao4537
    @pepsicolachao4537 4 ปีที่แล้ว +1

    Sometimes, something could lead to an interesting thing like the fans aren’t spinning fast enough.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      Definitely was not my first thought. It seemed like they were moving enough air. Thanks 4 the feedback 👍👍

    • @pepsicolachao4537
      @pepsicolachao4537 4 ปีที่แล้ว

      Also like the preview of what the video would be like.

  • @JDT738126
    @JDT738126 3 ปีที่แล้ว +1

    Did you happen to take an amp draw on those new motors?

    • @HVACRSurvival
      @HVACRSurvival  3 ปีที่แล้ว

      Yes it's right at its maximum amperage. Haven't had a problem with these motors yet.

    • @HVACRSurvival
      @HVACRSurvival  3 ปีที่แล้ว

      @UCyj66snU6-HG39GgYj_uIgQ correct, if you pull over the rating of the motor you could go off on thermal. This extra heat can lead to the breakdown of the insulation that protects the windings of the motor.

  • @JasonM35
    @JasonM35 4 ปีที่แล้ว +2

    I’d have cleaned the evaporator as well

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว +1

      What I did is more than most will do. Sometimes I'll use a garden hose or my pump sprayer but didn't see a reason to under the conditions. Thanks 4 watching 👍👍

  • @throttlebottle5906
    @throttlebottle5906 4 ปีที่แล้ว +1

    2uF cap, 6% tolerance is only 0.12, so below 1.88uF = bad and will change motor rpm too much, even if you allow 10% tolerance that's 1.6uF at lowest. simply too much for such small motors.
    don't forget the lower value caps have very tight leeway to be within tolerance.

    • @HVACRSurvival
      @HVACRSurvival  4 ปีที่แล้ว

      Exactly, and the oil on the motor was not from the birds and the worms😁, that was my other reasoning for not just changing the capacitor. 👍👍

    • @throttlebottle5906
      @throttlebottle5906 4 ปีที่แล้ว

      @@HVACRSurvival yeah, probably cooked the grease out from running hot and age

  • @Floridaman457
    @Floridaman457 2 ปีที่แล้ว +1

    “Spigot” not spickot 🥴

  • @steveblake8766
    @steveblake8766 4 ปีที่แล้ว +1

    #252 Thumbs uP

  • @marcopolo8096
    @marcopolo8096 4 ปีที่แล้ว +1

    Grammar police here. HVAC units never work good, never ever.
    HVAC units that are functioning properly can work well.
    From the internet:
    What is the difference between well and good?
    The rule of thumb is that good is an adjective and well is an adverb. Good modifies a noun; something can be or seem good. ... All you need to remember when you are pondering whether good or well is best for your sentence is that good modifies a person, place, or thing, whereas well modifies an action.

  • @alessichris07
    @alessichris07 4 ปีที่แล้ว +1

    👍👍👍