Todays repairs
เข้าร่วมเมื่อ 30 มี.ค. 2023
Todays repairs is all about, sharing the daily repairs on equipment, from HVAC repairs, Refrigeration repairs, brake jobs to t.v repairs.
Starting the condenser fan motors Hoffman Control
Wired in LiL Popper, testing Hoffman control to see if it will work
มุมมอง: 0
วีดีโอ
Seasons 4 Condenser fans not coming on
ชั่วโมงที่ผ่านมา
Seasons 4 Condenser fan motors not coming on and all 4 scroll compressors tripped on high pressure. Found only 9-10 volts going to the Hoffmann control for the condenser fan motors. Voltage going to Hoffmann control was to low, needs to be 24 volts. Had 24 volts going to the top of the fuse and only 9-10 volts coming out. Installed a 5 amp Lil Popper to take the place of the fuse for now. Had t...
Changing hot gas solenoid parts
มุมมอง 407 ชั่วโมงที่ผ่านมา
Multi deck meat case not going into hot gas defrost, all Iced up and in alarm. Had to rebuild the hot gas solenoid. for some reason it would not open up when the solenoid was energized. Rebuilt it and it was fine.
Evaporator Tripping Breaker
มุมมอง 297 ชั่วโมงที่ผ่านมา
Grocery Freezer Evaporator tripping breaker. Found wire rubbed through motor and took out the circuit breaker. Reset the breaker but the fans did not come on. It blew the wire apart. Had to splice the wires back together.
Frozen Food Anti sweats not working
มุมมอง 477 ชั่วโมงที่ผ่านมา
Frozen food 5 doors anti sweats not working. The circuit breaker was tripped. Found wires shorted out in race way. Nothing like working with wiring that's in water.
Changing Powerlink breaker 1
มุมมอง 33619 ชั่วโมงที่ผ่านมา
Changing a Powerlink breaker for electric defrost.
Grocery Freezer Noisy Evap
มุมมอง 30วันที่ผ่านมา
Grocery freezer evaporator making noise. Broken fan blade and mounting holes. Made a repair using fender washers.
Blown Condenser Fan Motor
มุมมอง 1714 วันที่ผ่านมา
Received a service call for a Continental 3 door freezer in alarm. Found a bad 208-230 volt condenser fan motor. I replaced it with a rescue motor that is good from 115 volt - 230 volts. Worked perfect. Had to pack the compressor with ice to cool it down. It was as hot as a firecracker.
Traulsen Evaporator Leak
มุมมอง 2514 วันที่ผ่านมา
Traulsen 3 door freezer. Low on refrigerant, not making temperature. Found leak on evaporator coil. Using an H10 leak detector. Will have to replace the evaporator coil.
Blown solenoid coil
มุมมอง 37314 วันที่ผ่านมา
Frozen Food line up running warm and in alarm. Cases were iced up and suction solenoid coil blown. Had to shut down Rack and control circuit to change out solenoid coil.
Welding a uboat
มุมมอง 18414 วันที่ผ่านมา
U boat welds were broken. I didn't have a very good ground. That's why the rod was sticking to the u boat. Not easy welding why holding a phone.
Motor bolts coming out of motor
มุมมอง 4514 วันที่ผ่านมา
Doing a preventative maintenance check on an air handler, and found two broken bolts that were coming out of the motor. Could have been a catastrophic failure. Installed two new 1/4" threaded rods to keep motor together.
Liquid Line Core Drier Plugged Up
มุมมอง 14128 วันที่ผ่านมา
Need to change out liquid line core drier, not feed enough refrigerant do to be plugged
comparing an old Amprobe to a newer Fluke
มุมมอง 18หลายเดือนก่อน
comparing an old Amprobe to a newer Fluke
Video1 Traulsen Freezer Tripping Circuit Breaker
มุมมอง 57หลายเดือนก่อน
Video1 Traulsen Freezer Tripping Circuit Breaker
Frozen food door Anti sweat heater not working
มุมมอง 78หลายเดือนก่อน
Frozen food door Anti sweat heater not working
Hi, I also have an Ardco door. I overadjusted the door closer ratchet mechanism (the thing which goes on top of the rod) and I am unsure if I broke something. I recently took off the door and when I flipped the door upside down the rod was able to slide out from the channel. Do I need to buy a replacement part or if I pry the metal channel would I be able to reassemble the rod back into place? Thank you so much!
Hello, most likely you broke the torsion rod. You can buy a replacement kit with all of the pieces you need to rebuild the door. When you receive the new torsion rod you will have to cut it to the length that you want. If you gently take the aluminum off, you will be able to get to all of the parts inside the channel. When putting the aluminum back, I use either a pair of channel locks with tape wrapped around the jaws as not to scratch the door or a pair of channel locks for doing toilets and plumbing (no teethe) some guys can just snap it back into place, I need to use the channel locks. If you have the numbers off of the door, I believe the company is Dover Food Retail. Hope this helps. Thankyou
its agood circuit
that hurt watching you go over paint like that
Your right, I should have cleaned it up first, that would have been the right thing to do. Thanks for watching.
What technique!
I should have cleaned it up and made a better ground, the rod wouldn't have stuck as much. I had refrigeration issues I had to get to. Thanks for watching
I find that it works better to lower the level. If it hits 99, there’s too much signal. Topping out under 99 then allows you to see a nuanced difference between proximate breakers, which dials the accuracy in.
Thank you for the tech tip. I will try it on a lower level.
Great video, to the point!
Bought one of these units as well. Great for underground circuits in concrete floors, and outside in the dirt. 👍👍👍👍
350 lol
Yes I know, you can buy these for around 250.00, Unfortunately, the company I work for had to buy it through Grainger, they charged us $350.00. It pays to shop around if you can.
Great video, short, straight to the point, solution at the end, beautiful
Thank you, I try to keep the videos short. Hopefully someone can learn something from them. No reason to do a video that last a half an hour. Thank you
@@todaysrepairs long form are a good time if you can maintain the same quality as your short, james butler well and septic has great videos long and short, hes a great story teller
That looks to be for a York.
It maybe a York, it actually came out of an Octagon Main Unit for a supermarket. United Refrigeration could not match anything up. Octagon went out of business years ago. Thank you
Nice flashlight, what brand?
It is a Klien rechargeable. It also has a laser pointer built into it. Thank you
Nice
Thanks
Opposite end bearing floats should have come out with rotor.
You are 100% correct, most of the time lower bearing comes out with the rotor and I replace both
Bad opposite end shaft, bearing should be there, quick metal is your friend.