Add Detail HIU
Add Detail HIU
  • 20
  • 55 480

วีดีโอ

Latest Model Danfoss FlatStation 7 Series DS IV HIU Installation | HIU Upgrade | HIU Replacement
มุมมอง 1.2Kปีที่แล้ว
Latest Model Danfoss FlatStation 7 Series DS IV Fully Insulated HIU Installation. Drained down the heating system and removed the existing HIU. Installed an inline scale reducer on the cold water supply to the unit. Insulated heating pipes around HIU. Cold flushed the heating system and dosed with Adey MC1 corrosion inhibitor and MC10 Biocide. Tested, fully commissioned Danfoss HIU and handed o...
Danfoss HIU Expansion Vessel Replacement: Danfoss Gemina Termix HIU Red Expansion Vessel CIMM 12L
มุมมอง 29Kปีที่แล้ว
Danfoss Gemina Termix HIU CIMM 12L replacement. The expansion vessel started to malfunction, and HIU stopped functioning correctly.
Caleffi HIU Service - Caleffi SATK32 Indirect HIU annual maintenance service
มุมมอง 1.5Kปีที่แล้ว
Caleffi SATK32 Indirect HIU annual maintenance service also includes a water quality test for the heating system’s inhibitor, corrosion and pH levels. Calleffi HIU services in London.
HIU Service and Repair: KVM-CONHEAT HIU maintenance
มุมมอง 1.9K2 ปีที่แล้ว
KVM-CONHEAT HIU service and repair. Includes new thermostatic head installation, a couple of new washers on leaking joints, HIU maintenance service and water quality tested with ADEY ProCheck to confirm inhibitor, corrosion, and pH levels.
HIU Service - Duty Point HIU service
มุมมอง 5312 ปีที่แล้ว
Duty Point HIU service in east London, including water quality test with ADEY ProCheck to confirm inhibitor, corrosion, and pH levels.
HIU Heat Meter Installation London
มุมมอง 7242 ปีที่แล้ว
Supply and install a new Sharky heat meter with radio output inside KVM-CONHEAT HIU.
Danfoss HIU IHPT 90° Valve Replacement
มุมมอง 1.4K2 ปีที่แล้ว
Leaking Danfoss HIU IHPT 90° Valve Replacement in south west London.
HIU (Heat Interface Unit) Installation: Hiper II twin plate HIU 80kW DHW
มุมมอง 1.1K2 ปีที่แล้ว
Hiper II twin plate HIU 80kW DHW with stand-off wall brackets installation in two bedroom apartment in southeast London.
HIU (Heat Interface Unit) replacement video
มุมมอง 1.5K2 ปีที่แล้ว
HIU (Heat Interface Unit) replacement. Evinox Energy HIU removal and Caleffi SATK32 installation in a two-bedroom apartment.
Radiance HIU Repair
มุมมอง 1732 ปีที่แล้ว
Supplied 🚚 and replaced 👨‍🔧Radiance HIU pump and flow switch for hot water.
HIU Group Booking Services in London
มุมมอง 553 ปีที่แล้ว
An HIU, or “heating interface unit”, fulfils essentially the same role as a traditional gas boiler but without gas. However, it is used as a part of a communal heating network in multi-unit apartment blocks. HIUs require annual servicing as with any other heating system to keep it running at optimum efficiency. The group booking method not only saves you money but also helps to reduce our carbo...
Danfoss VVX-I-2-1 HIU - replacement of IHPT valve.
มุมมอง 2.1K3 ปีที่แล้ว
HIU repair, Danfoss VVX-I-2-1 Heat Interface Unit - replacement of IHPT valve.
HIU Installation - HIU Replacement London
มุมมอง 8K3 ปีที่แล้ว
HIU Installation - HIU Replacement London
HIU heat exchanger service in London.
มุมมอง 3983 ปีที่แล้ว
HIU heat exchanger service in London.
HIU REPAIR THERMOSTATIC CONTROL VALVE REPLACEMENT
มุมมอง 4223 ปีที่แล้ว
HIU REPAIR THERMOSTATIC CONTROL VALVE REPLACEMENT
Danfoss HIU (Heat Interface Unit) IHPT Controller for Domestic Hot Water
มุมมอง 3.3K3 ปีที่แล้ว
Danfoss HIU (Heat Interface Unit) IHPT Controller for Domestic Hot Water

ความคิดเห็น

  • @nayakanand
    @nayakanand หลายเดือนก่อน

    Thanks for the video, I tried to replace but the water keeps dripping from the filter connection, any suggestions

    • @adddetailhiu8556
      @adddetailhiu8556 หลายเดือนก่อน

      @@nayakanand If the filter washer is new and the face of the joints have been thoroughly cleaned then maybe just need tightening

    • @nayakanand
      @nayakanand หลายเดือนก่อน

      @adddetailhiu8556 that connection is filter and not washer... I have tightened it as much as I can.. don't want to use more force as it might damage the thread right?

  • @davelaye7003
    @davelaye7003 4 หลายเดือนก่อน

    wow, what a video

  • @barryhughes4903
    @barryhughes4903 9 หลายเดือนก่อน

    Hi, Hope you don't mind me querying. We've just fitted a large number of of Danfoss HIUs on a scheme in Ireland, we've had a few instances of the Danfoss VMT valves pin sticking inside, once you wiggle them in and out with pliers or press them a few times they go again, Every seen anything like that.

  • @kirkzer594
    @kirkzer594 11 หลายเดือนก่อน

    What was wrong with the old one? I'm not a fan of Evinox HIUs but would not replace it.

  • @josephsim2256
    @josephsim2256 11 หลายเดือนก่อน

    Quality

  • @wayno5851
    @wayno5851 ปีที่แล้ว

    I noticed they have a 180 model two, I’m wondering if you could just undo the screws on the body and spin the heads?

    • @adddetailhiu8556
      @adddetailhiu8556 ปีที่แล้ว

      We were advised by the manufacturer that there are no repair kits for this specific valve at the moment, so we don’t take it apart and only offer a new replacement. Wouldn’t be able to say if it can be altered in any way.

    • @wayno5851
      @wayno5851 ปีที่แล้ว

      @@adddetailhiu8556 it’s an expensive repair when replacing the IHPT at roughly £450.00 parts only…then there’s labour to add

  • @BuzzingBites
    @BuzzingBites ปีที่แล้ว

    I have one at my flat. I have running hot water but no heat. The pressure and pump works fine, only thing I notice that when I turn on the heating the heat exchanger for heat is not warm. Are you able to help explain why that would be.

    • @adddetailhiu8556
      @adddetailhiu8556 ปีที่แล้ว

      Could be either TWA-230v actuator or RAVK controller zone valve pins stuck in closed position or differential pressure valve seized but would have to go through elimination sequence to find out.

  • @stevo091
    @stevo091 ปีที่แล้ว

    Hi good video. Still trying to get used tothe one I have in my flat. Cannot find the pressure switch 😱

    • @adddetailhiu8556
      @adddetailhiu8556 ปีที่แล้ว

      There is no secondary heating pressure switch for this specific unit.

  • @MrJonnyboymagic
    @MrJonnyboymagic ปีที่แล้ว

    Dont suppose you want to work on one of thes in the Republic of Ireland by any chance?😊

  • @jasonwhittle5008
    @jasonwhittle5008 ปีที่แล้ว

    Great install 😊👍

  • @hvacgas5292
    @hvacgas5292 2 ปีที่แล้ว

    Wht is ihpt valve

    • @adddetailhiu8556
      @adddetailhiu8556 2 ปีที่แล้ว

      It is a flow-compensated temperature controller, type IHPT. Simply I would say it controls domestic hot water temperature by regulating district heating flow through the heat plate exchanger. When hot water tap is opened IHPT valve opens, thermostat senses DHW temperature coming out of the heat plate exchanger and starts to control temperature.

  • @hvacgas5292
    @hvacgas5292 2 ปีที่แล้ว

    👍Great work.

  • @rickylin3214
    @rickylin3214 3 ปีที่แล้ว

    What does that do. Does that control DHW temperature