Dear SN Technical, Mere pass aik tube well par abb ka 18.5kw ka solar vfd drive Laga hua h, main is vfd ke output power ko 1km dor aik aur 20hp Ki motor chalana chahta hn. Kiya aisa hosakta h.
Please check the voltage drop calculation , you have calculated by % of full load current which not correct.Voltage drop for single phase = 2 x full load current x (R cos θ x X sin θ ) x length / 1000Voltage drop for three phase = square root 3 x full load current x (R cos θ x X sin θ ) x length / 1000 Voltage drop for DC = 2 x full load current x R x length / 1000 Please refrain to post wrong concepts...
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52, 7/64, 7/72, 7/83 I am from Pakistan wazirabad 00923226602165
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52, 7/64, 7/72, 7/83 I am from Pakistan wazirabad 00923226602165
Sir single phase motor 3hp ki hai or aluminum ki cable ka running 350ft hai or volt 230 dekha ta hai chalu krne se pahle but motor chalu krne ki bad 176 volt dekhata hai or motor 22.5 amp pr chalrahi hai
मुझे केवल आप इतना बताये कि दस hpकी मोटर मे ओवरलोड कानटरेकटर कितने apm की लगाये न:2 कितन् amp की mcb लगाये न : 3 कितने amp का star लगाये न: 4 कितने amp का delta लगाये न: 4 कितने amp का mein लगाये और न: 5 copper wire की fitting कितने mm मे करे men सरकारी लाइन supply ते alluminium की की आती है उसके बाद copper wire की fitting होती है तो यह कितने mm करे thanks for regard
correct me if im wrong since i dont understand your language, from the size wiring aluminum you used 6A as denominator , coz that was 3ph,415V from given i gez must divide at 4A to get 4mm² to be exact for a 10hp motor.
सर आप बहुत ही अच्छे वीडियो बनाते हो आपको बहुत-बहुत धन्यवाद सर इस केबल में आप यह बताया नहीं सर ऐसे की 100 भीट पर और 500 भिट पर कितने एमएम पर कितने कितने को केबल लगानी चाहिए जैसे कि जैसे जैसे दूरी बढ़ती जाती है उसका कैलकुलेशन कैसे करना चाहिए उसके बारे में बताइए सर9925243939 आपका इलेक्ट्रिक ग्रुप हो तो मुझे
100 miter se jyada hoga to kaise pata Karen Kitna mota tar lagega suppose 150 metre distance hoga aur motor 2hp hai. Main sabji mein Pani dene ke liye Ghar se dur mein motor chalana Chahta hai isliye poochha
@@devmakwana1244 If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52, 7/64, 7/72, 7/83 I am from Pakistan wazirabad 00923226602165
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52, 7/64, 7/72, 7/83 I am from Pakistan wazirabad 00923226602165
Current rating of wire is not proportional/ linear to. Sq. mm. Please be careful. Tested data is available of websites / packing cartons of major manufacturers like havells, RR, polycab etc.
correct me if im wrong since i dont understand your language, from the size wiring aluminum you used 6A as denominator , coz that was 3ph,415V from given i gez must divide at 4A to get 4mm² to be exact for a 10hp motor.
Good video..... Very simple and clear explanation. Thanks.
सर आप जैसा कोई वीडियो बनाता ही नहीं इलेक्ट्रिकल के मामले में और सब लगते हैं ट्रिक बताने i
Bahut aacha.ser ji.
Good explanation...
Bhai app 3or2 phace motor Canection ka video iss tara practical karke dikha sakte ho to please apke channel par ddo😊😊😅😅😊
Information tiptop hai bro thank you
Sir ji
Very nice experiment.
Good explanation
Sir
Very usefully experiment
Aluminium me aap 1/6× 13.837 kiya hai wahan pe 1/4×13.837 hoga kya
Nice information sir thanks..
I am waiting for your next video how to select fuse rating sfu size; OL Relay selection contactor selection
Sir please provide information about breaker, magnetic contactor, and overload relay standerd size available in Market.
Tq for write it in English brother.
Good job
Great sir .pl make dg set. Penal capacitor .changer. how to work and how to operate .kindly make vedio and sent.
Dear SN Technical,
Mere pass aik tube well par abb ka 18.5kw ka solar vfd drive Laga hua h, main is vfd ke output power ko 1km dor aik aur 20hp Ki motor chalana chahta hn. Kiya aisa hosakta h.
Sir is par ek vidio aur banaiye badi motor jaise 100 kw ya 200 kw ke liye armerd cable aur unarmed cable me kitne ams tak load de sakte hai
Brother super aap ek WhatsApp group banavo
1.5 hp ki motor me kitney mm ki wire lagaye or 150 meter ki duri ha
Kya hum single phase submersible pump ko vfd se chala sakte hai kya (vfd 220 volt 3phase)
Sir 1000 watts 230 v heater 500 degree C me Nichrome wire ka SWG nikal ne ka formula boliyega please.
Copper wire me duri badhte jae to current capacity kitni kam hoti jaegi 700meter tk bataiye pls.
Please check the voltage drop calculation , you have calculated by % of full load current which not correct.Voltage drop for single phase = 2 x full load current x (R cos θ x X sin θ ) x length / 1000Voltage drop for three phase = square root 3 x full load current x (R cos θ x X sin θ ) x length / 1000 Voltage drop for DC = 2 x full load current x R x length / 1000 Please refrain to post wrong concepts...
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52,
7/64,
7/72,
7/83
I am from Pakistan wazirabad 00923226602165
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52,
7/64,
7/72,
7/83
I am from Pakistan wazirabad 00923226602165
@@Mrakbarbashir can we run 800feet bore with single phase current 3hp single phase 35 stages texmo motor of taking 730 depth pipe
Hlo sr 1.5 hp ki motor me kitney mm ki wire lagaye or 150 meter ki duri ha
Sir mere pass 7mm ki coper cable thee tw mene usko 2hp motor me lagwa di koi dikkat hoga ya nahi....?????
What about spikes and high starting current ?
Sir mare pass ek 3hp ke 1fage motor hai aur woh chalane se hi voltage 250 se Kam ke 150 ho jata hai sir mah kiya karu?
Super👌👌
Gud
Sir single phase motor 3hp ki hai or aluminum ki cable ka running 350ft hai or volt 230 dekha ta hai chalu krne se pahle but motor chalu krne ki bad 176 volt dekhata hai or motor 22.5 amp pr chalrahi hai
2.5 square mm 3 core 500 fit 2 hp ke liye kuda rahega???
Thanks brother
Nice vidio
मुझे केवल आप इतना बताये कि दस hpकी मोटर मे ओवरलोड कानटरेकटर कितने apm की लगाये न:2 कितन् amp की mcb लगाये न : 3 कितने amp का star लगाये न: 4 कितने amp का delta लगाये न: 4 कितने amp का mein लगाये और न: 5 copper wire की fitting कितने mm मे करे men सरकारी लाइन supply ते alluminium की की आती है उसके बाद copper wire की fitting होती है तो यह कितने mm करे thanks for regard
Sir, 1sq mm copper cable take 2.5 amp and aluminium cable take 1.5 amp is it right or wrong pls tell
Ryt
sir temperature factor ke uper vi ek video banaye
really helpful chapter
Thanks
correct me if im wrong since i dont understand your language, from the size wiring aluminum you used 6A as denominator , coz that was 3ph,415V from given i gez must divide at 4A to get 4mm² to be exact for a 10hp motor.
सर आप बहुत ही अच्छे वीडियो बनाते हो आपको बहुत-बहुत धन्यवाद सर इस केबल में आप यह बताया नहीं सर ऐसे की 100 भीट पर और 500 भिट पर कितने एमएम पर कितने कितने को केबल लगानी चाहिए जैसे कि जैसे जैसे दूरी बढ़ती जाती है उसका कैलकुलेशन कैसे करना चाहिए उसके बारे में बताइए सर9925243939 आपका इलेक्ट्रिक ग्रुप हो तो मुझे
Sir 3hp , 650 depth ,single phase
4mm cable daal de, kya full load 12 amp aa rha h
100 miter se jyada hoga to kaise pata Karen Kitna mota tar lagega suppose 150 metre distance hoga aur motor 2hp hai. Main sabji mein Pani dene ke liye Ghar se dur mein motor chalana Chahta hai isliye poochha
Which size cable required in star delta motor?
great
Super
10hp aquatex motor ko supply cable kitna mm Chahiye
sir three phase me to voltage drop 5 hots he kya Mene ek वीडियो में देखा था
Thanks sir
thenk yuk sir
Why motor efficiency not added in single phase
20hp 3phas motor ke liye kitne mm ki wire lagega
How distance matter for cable selection if for my case distance is 800 ft.
How to you select 1 sq mm 6amps 3phase 1 sq.mm 4 amps?
Copper ki cable 1.5 sq mm ki 15 amp tak le skti h sir
Le skti h but uski life utni nhi rhegi
Vo jld damage ho skti h
@@SNTECHNICAL
To sir cable ki current ka chart share kro
sir 75KW ki motor me 70 SQmm ka cable use kiya h but calculation me ye aa hi nii rha h..
For three phase voltage drop is 5% and fot single phase voltage drop 2%...
why used efficiency in power formula?
1hp submersible pump keliye Kitna SQM Ka cable Chahiye
1.5
Nice
Thank you sir
Why you add 2% voltage drop.
I think You should subtract because 2% loss of voltage
how can you say that 1sq cable can bear 6 amp current?describe technically
Sir ji
HVAC KA THURASA KNOWLEDGE DIJIYE PLEASE
Good
Sir 1 mm√ 12 amp load diye jatiha
Is it correct 1.5 sq.mm&!=6amp
Single phase motor 2 hp motor full load. 3.5
Sir aluminium is better counductor than copper
Sir 35 sq mm se upar ki cable ka farmula bataiye
Cable current rating ki table share kr do
Sir Voltage drop section is not clear.
Mashallah sir
Actually standard rating for 1hp 5 to 6.5 amp current .....
Please sar jaldi se yah video Jo bol raha hai na us video ko jaldi
2 2.5% how where you getting
One time u see bro
Voltage drop minus karna hoga , aapne add kiya hai
If distance is more than 100 metres than what we will do
Check the ideal chart.
If distance increases current carrying capacity decrease proportionally
@@devmakwana1244
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52,
7/64,
7/72,
7/83
I am from Pakistan wazirabad 00923226602165
If there is 1300 hundred feet length and we have to run 5 h.p moter so which wire would be better for me 7/52,
7/64,
7/72,
7/83
I am from Pakistan wazirabad 00923226602165
Contactor size btao sir
5 hp ??
copper ka bhi 6 amp pakda aur aluminium ka bhi..last may apne mistake kiya.
thik karo
Current rating of wire is not proportional/ linear to. Sq. mm. Please be careful. Tested data is available of websites / packing cartons of major manufacturers like havells, RR, polycab etc.
3 phase main voltage drop 5 % hota hai
Aap jo hello friend bolte hai o trika change kare, es se mujhe bahot gusaa aata hai
Sir
Kuchh wrong lag rha hai
200fit distant
I am using 6mm sq for 2 hp single phase motor ata chakki machine,
3 ph, 10 hp का calculation नही निकला
Bhai full details dia Karo nahin to video Nahin banaya Karo aap method sahi nahin hai motor jal jayega
6 amp is not standard current for 1mm sq brief according to the ICE
Vai please apka numbar do please ak help chahiye
Bakwaaas video aadi se jada video sirf amp niklme lagayi bki khud assume kiya huya amp. Bhai koi formula btaayo kaise select kre
Very long definition...!!!
English language
Pvc
This is wrong 👍👍
Nice
correct me if im wrong since i dont understand your language, from the size wiring aluminum you used 6A as denominator , coz that was 3ph,415V from given i gez must divide at 4A to get 4mm² to be exact for a 10hp motor.