@@civilworld Sir my building height is 19m each height floor to floor is 3.800 my wind speed is 39 my ans is 8.76kn it's right or wrong and my category is 3 class b
May be my calculation was wrong in some of the steps because I am not having scientific calculator so Don’t bother about that,follow the procedure. That’s enough for this practical subject. And verify only with checks if it is satisfied then okay
Nice explanation sir
Nice sir
Sir, Design of steel and RCC classes Cheppara
Design of steel cheppanu. RCC cheppaledhu
Sir k2 value 10 meter 0.084 and 15 also were is in 875
available in code book. if there is any errors please follow the procedure
@@civilworld Sir my building height is 19m each height floor to floor is 3.800 my wind speed is 39 my ans is 8.76kn it's right or wrong and my category is 3 class b
8.76 Kn is basic wind pressure
what if i want to calculate for 2.3 m height
You have to refer IS 875 code book as I specified in the video
Refer IS 875 code
Sir from which code k2 values are taken out? Is from IS 875 ?
Yes Refer IS 875 part 3.
@@civilworld okay Sir!
Thank you
@@divyarani7114 All the best 👍
why do I punch with my calculator and the values don't match yours where'as am just punching what you've written
May be my calculation was wrong in some of the steps because I am not having scientific calculator so Don’t bother about that,follow the procedure. That’s enough for this practical subject. And verify only with checks if it is satisfied then okay
@@civilworld okay.. thanks
@@mfonfudaniel6581 All the best