IMPROVE "F3" ERROR AC SPLIT DAIKIN INVERTER 1 PK

แชร์
ฝัง
  • เผยแพร่เมื่อ 24 ส.ค. 2024
  • "F3" error on split ac with an inverter due to the error of the exhaust pipe temperature in the outdoor. (outdoor thermistor sensor) there are 3 types of discharge pipe sensor, reverse pipe sensor, outdoor temperature sensor, of the three types of sensors that read the outdoor working temperature and provide a signal to the inverter module.
    "F3" error can be caused by lack of freon, outdoor thermistor sensor is damaged / misread temperature, electronic expansion valve is broken, body valve expansion is broken, pcb inverter module is error / damaged.
    Here I use a capillary pipe to replace the damaged valve expansion. Sy, don't recommend friends to replace it with capillary pipes, but so far there are no problems for its use, the AC still wants to cool at low, med, high comp speed.
    Hopefully this will be useful for all my friends and if there are feedback or comments please write below the comments column.
    Don't forget to like and subscribe, friends - thanks.

ความคิดเห็น • 302

  • @berbagitau1019
    @berbagitau1019 8 หลายเดือนก่อน +1

    Ilmu yg bermanfaat..semoga tmbh mju dah berkembang

  • @bahribahri228
    @bahribahri228 3 ปีที่แล้ว +2

    Trimakasih mas bagi bagi ilmu TUHAN BERKATI AMIN

  • @ahmadjamil8818
    @ahmadjamil8818 3 หลายเดือนก่อน

    Wah ini mah teknisi ac yg udah pro..ngerti cara kerja komponen ac..

  • @siagaopspoldasumbar5579
    @siagaopspoldasumbar5579 4 ปีที่แล้ว +26

    sekedar masukan bli... gak baik bagi kompresor ac inverter klo ekspansinya diganti dengan kapiler. karena desain ac inverter harus menggunakan katup ekspansi dimana fungsi ekspansi adalah selain pengganti kapiler pada sirkulasi freon tetapi juga menjaga tekanan pada pipa tekan dan pipa hisap agar berada pada tekanan yang seharusnya. karena ac inverter kompresornya bekerja secara variabel. maksudnya ketika kompresor berjalan pada medium speed maka ekspansi akan menyempit dan apa bila kompresor berjalan pada high speed maka ekspansi akan melebar agar perbandingan tekanan tetap pada takaran yang semestinya. jika diganti dengan kapiler maka penyempitan pada sirkulasi freon akan terjadi secara flat (tetap). alhasil kompresor pada kecepatan rendah sirkulasi freon akan mendekati loss di kapilernya yang mengakibatkan tidak terjadinya pengabutan freon dikapilernya dan tidak mengahasilkan dingin dan jika diukur tekanan pada pipa tekan pada kompresor akan turun dan tekanan pada pipa hisap akan naik dari yang semestinya. sementara jika kompresor berjalan pada high speed atau kecepatan tinggi maka tekanan pada pipa tekan kompresor akan naik tinggi sedangkan pada pipa hisap akan rendah dari yang semestinya, walau pada kecepatan high speed ac akan menghasilkan dingin tetapi akan mengakibatkan kompresor dipaksa bekerja diatas batas kemampuan semestinya untuk memompa dikarnakan debit aliran freon yang diterima kapiler sudah di atas yang semestinya. ini akan membuat kompresor tidak akan bertahan lama.... saran untuk ac inverter jika ekspansinya rusak, alangkah baiknya diganti dengan ekspansi yang baru ketimbang diganti dengan kapiler... karena ac inverter tidak sama dengan ac non inverter.. atau jika suku cadang tidak ada di daerah sekitar tempat tinggal atau terlalu mahal maka opsi kedua lebih baik ac nya dijadikan non iverter dulu baru di ganti dengan kapiler...

    • @alvinarmianto2792
      @alvinarmianto2792 4 ปีที่แล้ว

      Mantapss mAs sarannya masuk akan dan Kerennn

    • @riyadigepeng1828
      @riyadigepeng1828 4 ปีที่แล้ว

      Kalau inverter daikin eror L5 solusinya apa bos ku?

    • @deniindarto2989
      @deniindarto2989 4 ปีที่แล้ว +1

      ciri" katup exspansi rusak gimna ya bang ?

    • @fianissa983
      @fianissa983 4 ปีที่แล้ว +2

      punya saya di ganti kapiler sudah 3 tahun ke skrg ga masalah ampere normal,mau ganti katup ekspansi waktu itu harganya selangit.

    • @amirherisusanto8669
      @amirherisusanto8669 2 ปีที่แล้ว

      Ter merubah kompresor inverter 3phase menjadi manual, apa kah cukup coneksi S,C,R L,N, dan kapasitor?

  • @bahribahri228
    @bahribahri228 2 ปีที่แล้ว +1

    Trimakasih mas bagi bagi ilmu saya trimasih banyak

  • @iyanservice0556
    @iyanservice0556 5 ปีที่แล้ว +1

    Okee mass terimasih atass videonya,, saya bertahun2 benam AC daikin inverter..
    Kedip2 jg luar dlm,, saya bongkar2 vcb nya..
    Gak jg

    • @aripazu3716
      @aripazu3716 4 ปีที่แล้ว

      Coba mas kabel2 kontrolnya mungkin ada yg gak kenceng, sy jg ngalamin pusing n ribet.

  • @jovanoriechie8129
    @jovanoriechie8129 3 ปีที่แล้ว +2

    Bli sy subcribe.., semoga sewaktu2 bisa share ilmu utk problem yg belum pernah sy atasi. Thxs

    • @jovanoriechie8129
      @jovanoriechie8129 3 ปีที่แล้ว

      Bli., boleh minta kontak WA untuk tanya2 soal AC. Terima kasih

  • @alphaservice191
    @alphaservice191 2 ปีที่แล้ว

    Mantab kang,salam dingin dari indarung padang,terimakasih

  • @sugengsugeng9471
    @sugengsugeng9471 4 ปีที่แล้ว +1

    mantab nas,nambah wawasan

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Terimakasi mas sugeng

    • @imanueljulian6495
      @imanueljulian6495 4 ปีที่แล้ว

      Made arsa..mau tanya, itu tadi motorized coil nya tidak dipasang ? Ndak pengaruh pada pcb outdoor..terimakasih

  • @bahribahri228
    @bahribahri228 3 ปีที่แล้ว +2

    Trimakasih mas nambah sy ilmu sekali lagi trimakasih

  • @vivo1269
    @vivo1269 2 ปีที่แล้ว +1

    Bos Sayaa Mau Tanya daikin split duct 2.5 Pk..Fan outdooor nyala tapi compresskr Ga manggil..walaau indoor nyalaah.di cek remot kode error ga terdetek

  • @otangsetiawan5780
    @otangsetiawan5780 9 หลายเดือนก่อน +1

    bang kalo sudah ganti ke kapiler apakah future Low watt nya masih bisa berfungsi atau gk?

  • @irilhandoko1856
    @irilhandoko1856 4 ปีที่แล้ว +1

    Mantab made .......

  • @fajarnugroho646
    @fajarnugroho646 5 ปีที่แล้ว

    Salam dari bali...ikut belajar bli

  • @joeteknik4556
    @joeteknik4556 2 ปีที่แล้ว +1

    Udah nyoba ini kelemahannya ko multi split, ga bisa 1 indoor aja yg menyala, harus 2 2 nya menyala karena freon mengalir ke indoor yg lainya jg.

  • @setia7723
    @setia7723 หลายเดือนก่อน

    kalau ga ada masalah f3 apakah ac bisa lebih dingin daei eev ke kapiler

  • @ariefyenny9959
    @ariefyenny9959 3 ปีที่แล้ว +1

    Ok. Baik

  • @sugiyono0661
    @sugiyono0661 5 ปีที่แล้ว +1

    Ok makasih

  • @oscarrj.mataniari1658
    @oscarrj.mataniari1658 4 ปีที่แล้ว

    Bli... mau tanya donk..sy lg service ac.. Metk LG, inverter 1 PK.. problennya, saat dinyalakan pertama, putaran compressor low ( 2,4 amper..sesudah 2 menit hidup, puteran compressor naik dan ampelr menjadi 3.4 amper..sesudah 2 menit kwmudian, puteran naik lagi jadi 5-6 amper..hampir 3x yg teryera di nameplate (name plate 3.3 amp).. apa penyebabnya bli..trimkasih.salam dingin dari tangerang

  • @kikikiki3941
    @kikikiki3941 3 ปีที่แล้ว

    Trimakasih 👍👍

  • @zarifin46somayasulimanzari44
    @zarifin46somayasulimanzari44 4 ปีที่แล้ว +3

    Om mau nanya nih AC Daikin 1pk invater saat di nyalahin di lampu indor nya kedap kedip lalu berapa menit AC nya mati lalu dinyalahin lagi tetap gak lm mati lg tp pake kode pan ttp menyalah pas kita kasih kode cool AC nya mati lg dan kira² apaan nya yg jd travel om.?🙏 Mksh sblm nya om.🙏

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      cek kode error di remote

    • @zarifin46somayasulimanzari44
      @zarifin46somayasulimanzari44 4 ปีที่แล้ว

      Kode error' nya U4 om itu kira² apanya ya om.? Trabel nya komponen indor apa Autdor nya om.??

  • @muhamadsaddam3845
    @muhamadsaddam3845 2 ปีที่แล้ว +1

    Kalw katup exspansi d ganti dengan pipa kapiler, sensor.y delepas aja apa di pasang gan.

  • @nazacom2152
    @nazacom2152 4 หลายเดือนก่อน

    Thnkyu sob... itu Ac brp PK ya, dan brp panjang kapiler nya..? 🙏👍

  • @tigasekawan321
    @tigasekawan321 2 ปีที่แล้ว +1

    dingin sih mungkin bisa maksimal,tapi pemakain itu kuat berapa jam???
    karena dikasus yg hampir sama seperti ac ini pemakain yg saya uju ini hanya bertahan kurang lebih 5-6 jam setelah itu ac kembali ngetri lagi.
    mohon bimbingannya....

    • @madearsa93
      @madearsa93  2 ปีที่แล้ว +1

      Cek termistor nya bisa jadi rusak.

  • @Dhirzky
    @Dhirzky 4 ปีที่แล้ว +1

    Bli, tanya AC DAIKIN 1/2 PK SMILE INVERTER saya ketika di hidupkan 2mnt outdoor mati dan indoor tetap running setelahny LED power berkedip indikasi error' L5? Mohon bimbingannya?

    • @suyonouton9169
      @suyonouton9169 4 ปีที่แล้ว

      Jika diganti pipa kapirel gitu kira"berbahaya ga,dan brpa lama bisa tahan

    • @Dhirzky
      @Dhirzky 4 ปีที่แล้ว

      @@suyonouton9169 kalo masih 3 tahun mending manggil service resmi. Masih free

  • @iqbalagustina8440
    @iqbalagustina8440 4 ปีที่แล้ว +1

    Kalo untuk ac 1.stngah pk pake pipa kapiler ukuran berapa

  • @ubn4046
    @ubn4046 3 ปีที่แล้ว +1

    Cara kerja anda sudah saya kerjakan ac suda ok tapi aneh nya setelah 3 hari ac daikin inverter 1pk kumat lagi yaitu out door mati lagi freon r.410a nya kondisi ok ga bocor.

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว +1

      Error f3 adalah kesalahan kontrol suhu deteksi pd thermistor pipa discharge.
      Bnyk faktor yg menyebabkan error f3 , bisa karena 3 sensor thermistor pd outdoor yg rusak, kebocoran freon, bisa juga pcb outdoor itu yg rusak. Perlu menganalisa kerusakan pd error f3 tidak semua kerusakan pd body expansi dan eletronic expansinya yg sudah di rubah dgn pipa kapiler.
      Perhatikan panas suhu pd pipa discharge kompresor.
      Perhatikan tekanan freon dan ampere pd saat start kompresor hingga running kompressor di posisi ngegas putaran tinggi, apakah ampere mengikuti kerja kompresor pada putaran bawah dan putaran atas tidak melebihi ampere yg di tentukan di putaran tinggi sampai 4,5 A, dan tekanan freon perhatikan pada jarum manifol dari putaran bawah kompresor stabil turun jarum manifol di 170-180psi hingga putaran tinggi di tekanan 140-150psi. Untuk ac freon r32 atau r410a

  • @saifulbakhari2105
    @saifulbakhari2105 3 ปีที่แล้ว +1

    Error f3 .ekpansi valvenya di ganti kapilr. Untuk 2pk panjang berapa diameter berapa. Lalu selenoid nya dicabut atao di biarkan saja. Terimakasih.

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว

      2pk ukuran kapiler 80mm panjang 60cm , motorize expansi di cabut.

  • @hlathein5558
    @hlathein5558 4 ปีที่แล้ว

    Thank you sir

  • @sarudiandika7567
    @sarudiandika7567 4 ปีที่แล้ว +1

    Sahabat thenik info .
    AC emperter Daikin 1 pk
    Tdk eror ..
    Permasalahannya
    Compresor .hidup dlm watu pling lama 5 menit ..setelah dlm 5 MIT mati lgi tu compresor .nunggu smpi 20 mnt .baru bisa hidup .treus mati lgi ....aph tu kerusakannxa

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Blum bisa di simpulkan apa kerusakannya, karena kurang detail pengecekan posisi outdoor ac hidup ampere berapa? Tekanan freon berapa? Sudah dpt cleaning ac indoor dan outdoor?
      Ada indikasi kode errornya apa? Trims

    • @filzafarzana2166
      @filzafarzana2166 3 ปีที่แล้ว

      @@madearsa93 lo ac 1 1/5 ukran kapiler brp kh

  • @heruhasriadi6185
    @heruhasriadi6185 5 ปีที่แล้ว +2

    Kenapa gak ekspansinya aja yg diperbaiki, kan bisa di bersihkan pake r11

  • @masukgenk3903
    @masukgenk3903 3 ปีที่แล้ว

    Bli,
    Sepertinya kasusnya mirip dgn ac saya,
    Indoor tidak mau dingin, ketika baru ON, lalu outdoornya harus di semprot air dulu baru mau dingin indoornya,
    Apakah kasus demikian masalahnya di katup expansi jg?
    Kode error di remot ac tidak terdeteksi

  • @azenkmaulana2229
    @azenkmaulana2229 5 ปีที่แล้ว

    Tquuuuu.. Brother !

  • @ben096
    @ben096 4 ปีที่แล้ว +2

    Tak boleh modified expenses valve begitu ,AC sudah hilang digital thermal energy control kalau Di ganti dengan capillaries. Warranty dari Daikin langsung void Di modified begitu .

    • @aditianugraha4712
      @aditianugraha4712 4 ปีที่แล้ว +2

      Betul sekali otomatis system tidak akan bekerja dengan baik, di kemudian hari akan ada error tambahan

  • @warsobaru7309
    @warsobaru7309 3 ปีที่แล้ว +1

    Maaf bos, kl koder error' H6 ac Daikin inverter 1pk, kira2 ada kerusakan di komponen bagian mana bos..?🙏

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว

      Bisa modul pcb outdoor, dan bisa juga kompresor.

  • @torjackkaratan6081
    @torjackkaratan6081 3 ปีที่แล้ว

    After your modification sir.. In several week or months no have problem afyer you change expansion valve to capillary? Tnx for your response..

  • @andieazhiez5934
    @andieazhiez5934 หลายเดือนก่อน

    Untuk AC 1/5 PK pipa kalilernya ukuran berapa yah?

  • @berbagitau1019
    @berbagitau1019 8 หลายเดือนก่อน

    Gan..klau utk 1/2 pk menggunakan pipa kapiler ukuran brapa?

  • @midasumiarsa5911
    @midasumiarsa5911 5 ปีที่แล้ว +2

    Pas AC Daikin Inverter 1PK saya krna F3. Terima service AC bli? Ada kontak yang bisa di hubungi?

    • @agustitimurti4814
      @agustitimurti4814 4 ปีที่แล้ว

      Ada ..alamat nya di mana biar kita datangi .. khusus Medan ya .. 🙏

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      081 999 021 433 daerah denpasar - bali

  • @agusrevolusi1329
    @agusrevolusi1329 11 หลายเดือนก่อน

    Pak eror u4 inverter daikin yg kerusakannya bagian apa ya.trim ksh.

  • @rendi.m.u1968
    @rendi.m.u1968 4 ปีที่แล้ว +1

    AC inverter lebih ribet perbaikinya.
    Kalau bisa di ganti aja mas jangan di rubah rubah gitu GK baik.🙏😁

    • @Anadisty
      @Anadisty 2 ปีที่แล้ว +1

      Kalo punya uang banyak gpp bang main ganti" aja tapi kalo masih bisa diakalin dengan nominal yg kecil kn gak salah juga

  • @A_dhit_a_m_a
    @A_dhit_a_m_a 4 ปีที่แล้ว +1

    AC punya saya sensor yg diluarnya putus kayaknya bagian dalamnya, soalnya kegencet tutup atas. Waktu AC abis di cuci tidak memperhatikan ternyata kabel sensornya kegencet.
    Untuk menggantinya gimana ya? Atau bisakah kabelnya disambung? Saya belum coba liat daleman kabelnya seperti apa.

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Pd outdoor ac sensor thermis putus ?

    • @A_dhit_a_m_a
      @A_dhit_a_m_a 4 ปีที่แล้ว

      Iya, thermistor yg ada dibagian luar belakang AC sepertinya putus bagian dalam kabelnya, soalnya kegencet tutup atas casing outdoor. Itu kabel isinya tembaga atau apa ya? Kalo tembaga bisa disambung kan?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Ow, iya bisa di sambung kabel thermisnya.

  • @ariefudien7034
    @ariefudien7034 3 ปีที่แล้ว

    apakah untuk ac samsung ,bisa juga di kasi seperti daikin

  • @joeteknik4556
    @joeteknik4556 3 ปีที่แล้ว

    Mau tanya bli... Klo Daikin multi split bisa kah diganti kapiler jg? Soalnya ada 2 katup ekspansi/selenoid Valve.

  • @ahmadaircon7818
    @ahmadaircon7818 3 ปีที่แล้ว

    Bagaimana bisa tentu kan mana satu yg rosak..? Sensor? Eev atau pcb

  • @adicahyadi5803
    @adicahyadi5803 2 ปีที่แล้ว

    Metaken pak de..kenapa tdk d vacum ya? R32 kan wajib vcum..apalagi itu invrter. Kmudian apa pipa kapiler bisa mengatur volume gas spt elektronik expnsi valp? Apa masih bisa hemat listrik klo sudah di modif spt nike?ampure masih belajar pak made.. 🙏

    • @madearsa93
      @madearsa93  2 ปีที่แล้ว

      Divacum lebih baiknya...! Daya listrik masih hemat seperti biasa hanya saja jika seting low watt di remote dingin nya agak kurang sedikit seperti biasanya.

  • @ubn4046
    @ubn4046 3 ปีที่แล้ว

    Bahkan pipa ac nya saya ganti baru 5m & sblm di isi freon nya saya vaccum dulu tapi yg saya bingung setelah 3 hari ac nya mati lagi 🤔

  • @almerkev
    @almerkev ปีที่แล้ว

    Halo mas, mau bertanya nih. Ac inverter daikin 1pk saya ada masalah di sensor magnet valve nya, kalau di pasang.. outdoornya mati, namun kalo di copot, outdoor nya nyala. Sudah beli magnet valve baru, namun tidak ada perubahan.. mau di copot tapi takut nantinya akan rusak merembet. Nah ada saran, pipa nya diganti menjadi kapiler.. apakah aman mas?

    • @arapaimagold8088
      @arapaimagold8088 ปีที่แล้ว +1

      AC kalau pakai EEV, maka di pcb akan ada IC stepper untuk ngatur EEVnya. Itu juga harus anda ganti.

  • @dominicxavier7384
    @dominicxavier7384 5 ปีที่แล้ว +2

    Setelah di ganti kapilernya.ekspansi elektronik nya di ke mana kan yah mas?

    • @madearsa93
      @madearsa93  5 ปีที่แล้ว

      Saya lepas, kalo dia protek di pasang aja pinggirin taruhnya

    • @hadipurwanto9447
      @hadipurwanto9447 3 ปีที่แล้ว

      Made Arsa...
      Di lepas tanpa di jemper..? Atau di jemper..?

    • @theremacoofficial7045
      @theremacoofficial7045 2 ปีที่แล้ว

      Maksudnya socket nya dilepas dari pcb ya bli, atau socket tetap terpasang di pcb

  • @fikrihudagrab571
    @fikrihudagrab571 7 หลายเดือนก่อน

    Bli ac invrter saya set d suhu 24 mau dingin, ketika suhu sudah tercapai kan dia kerja nya melambat, tapi setela itu gamau naik lagi kerja nyq. Kenapa ya? Kalo di mtiin kemudian nyalain kembali dia mau dngin lagi

    • @setia7723
      @setia7723 5 หลายเดือนก่อน

      yah suhu ruangan sudah tercapai kalau naik lagi kompresor hidup lagi inverter itu harusnya di ruang tidur tidak disarankan di tempat ruang kelurga bisa tapi harus rapat ruangan agar kompresor tidak gas terus

    • @setia7723
      @setia7723 5 หลายเดือนก่อน

      tekanan brp psi daikin bukan

  • @Ariefindragunawan
    @Ariefindragunawan 4 ปีที่แล้ว

    Bang mau tanya nih..ac sya daikin inverter 1/2 pk..habis ganti pipa elbow indoor gara2 bocor..usia ac baru 1 stngah thun..setelah seleasai servis..dah berjalan hampir sebulan lebih..dingin mash kurang nyess..tekanan freon normal di cek kode eror remote ga gak ada yg eror..dinginyya kurang nyess..aer pembuangan embun ac normal bgt klo di suhu 25..tpi klo di turun ke 24 atau 23 sma aja gak ada perubahan dinginya..malah aer pembuangan embun mlah jadi agak lambat..padahal sebelumny di suhu 25 aja dah dingin banget sebelum penggantian pipa elbowny...kira2 apa ya solusiny..
    Mhon penjelasany..

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Bisa jadi pada saat perbaikan kebocoran, sirkulasi pipa ac kurang dibersihkan dan tidak di vacuum, kurangnya tekanan freon, sirkulasi pipa pendinginan terhambat sedikit buntu jadi pendingin tidak normal kurang dingin.

    • @Ariefindragunawan
      @Ariefindragunawan 4 ปีที่แล้ว

      Secara prosdur di vacum..tpi yah gtu saya suruh cek kembali tekanan freon sma besar ampereny smpe skrg teknisiny blm dtng2 jg krmh..

  • @alfakrisbiantoro6718
    @alfakrisbiantoro6718 3 ปีที่แล้ว

    Untuk info harganya bang . . .share dong harganya . . Dapet kasus sama untuk daikin inverter 1 pk model lama

  • @yulisudarwanto7341
    @yulisudarwanto7341 5 ปีที่แล้ว

    @made arsa ada nomer
    g bisa di hibungi mas.mau tanya ilmu nya dan sedikit curhat tentang permalahan ac inverter 1 pk.saya baru belajar dari 0

  • @mrdiycool2062
    @mrdiycool2062 4 ปีที่แล้ว

    Udah subcribe mas

  • @agunghidayatullah1320
    @agunghidayatullah1320 ปีที่แล้ว

    Bli Untuk pastikan body expansi rusak/bagus bgaimana caranya ya bli?

  • @ediprayitno6946
    @ediprayitno6946 2 ปีที่แล้ว

    Minta skema expasi valvenya om 6 kabel mana yg negati dan positifnya

  • @fachmishahab2872
    @fachmishahab2872 4 ปีที่แล้ว

    Persis sama spt AC Daikin 1 PK inverter saya.F3 error...kmd ..dibersihkan karat2 pd sensor2 itu....berhasil...kmd dingin...namun cuma bertahan 3 bulan...kmd F3 error lagi....kl begini apa solusinya Mas?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Ganti body expansi valve dan elektronic expansi nya kemungkinan rusak.

  • @MELLKY_Si.AnakPejuangReceh
    @MELLKY_Si.AnakPejuangReceh 5 ปีที่แล้ว +1

    Ac sy g bisa dingin apa s bang..

  • @kayanbaztard13
    @kayanbaztard13 3 ปีที่แล้ว +1

    Klo untuk ac ukuran 1,5pk brapa ukuran pipa kapiler dan panjangnya bli? 🙏
    Ampura kari pemula.

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว +1

      Biasanya di gunakan ukuran 0,70mm panjang 60cm

    • @kayanbaztard13
      @kayanbaztard13 3 ปีที่แล้ว

      @@madearsa93 oke, suksma bli 🙏

  • @user-ng1qc6xc9e
    @user-ng1qc6xc9e ปีที่แล้ว

    Terlalu cepat vidio di tekanan freon bos.jd gsk jelas tekenannya.

  • @zonatriono3612
    @zonatriono3612 2 ปีที่แล้ว

    kl untuk daikin 2pk ukuran dan panjangnya brp ya hu

  • @yogatanaka5544
    @yogatanaka5544 4 ปีที่แล้ว +1

    Utk area jakarta ada? Saya kena f3 juga

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Saya lokasi di bali mas

  • @ardypermadi2310
    @ardypermadi2310 5 ปีที่แล้ว +1

    Pernah nangani error u2 bli AC seperti itu,jd klu di mode low watt ac jalan normal.tp klu di mode normal outdoornya mati hidup....

    • @ardypermadi2310
      @ardypermadi2310 5 ปีที่แล้ว +1

      @@madearsa93 sudah pernah tp hasilnya sama cek teg input 220 normal,system kelistrikan jg normal pakai 4 kabel standart pemasangan daikin,kompressor jg tdk short. blm di cek bagian modulnya karena tdk punya skemanya.

    • @ardypermadi2310
      @ardypermadi2310 5 ปีที่แล้ว +1

      @@madearsa93 oke terima kasih banyak bli made atas ilmunya,coba saya pelajari dl system kerjanya besok 🙏

    • @nobieanynomous2424
      @nobieanynomous2424 5 ปีที่แล้ว +1

      Ardy Permadi
      biasanya u2 modul pcb outdoornya bermasalah.. cek sekring, kapasitor, biasanya kapasitor dc nya itu bang

    • @masmincoolteknik8033
      @masmincoolteknik8033 5 ปีที่แล้ว +2

      Pcb noise filter dan fan motor outdorr

    • @raihanraqqilla3186
      @raihanraqqilla3186 4 ปีที่แล้ว +1

      @@masmincoolteknik8033 ganti kapasitor VDC di outdoor

  • @wisnunaiu2777
    @wisnunaiu2777 5 ปีที่แล้ว

    ijin bertanya master. jika ac matot apa bisa cek kode erornya?

  • @Tonysiswadi
    @Tonysiswadi 5 ปีที่แล้ว +2

    Kalo kapiler daikin 0,5 pk berapa mili ukuranya ya gan

    • @Tonysiswadi
      @Tonysiswadi 5 ปีที่แล้ว +1

      R32

    • @carleswijaya1818
      @carleswijaya1818 5 ปีที่แล้ว

      Bagaimana ac 1pk sharp tidak dingin,kompresor mati hidup,kipas jalan.ac dibeli sudah ada 5thn.thanks sebelumnya,bagaimana memperbaikinya.

  • @TheRonggo
    @TheRonggo 5 ปีที่แล้ว

    kalau pakai ekpansi valve berarti gak pakai pipa capiler bos ?

  • @faisalsiregar6409
    @faisalsiregar6409 3 ปีที่แล้ว

    Bagaimana kita tau kalau expansi valevnya rusak. Dilihat dari fisik atau ada bunyi2 atau bagaimana pak.

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว

      Di cek lewat manifold tekanan freon dan ampere nya. Kompresor hidup seiring jalan putaran speed kompresor tekanan freon turun sampai habis dan ampere kompresor tinggi melebihi batas ampere dan overload.

  • @andyziian5767
    @andyziian5767 3 ปีที่แล้ว

    Colek.. suhu made Dulu...

  • @rudalsqud926
    @rudalsqud926 3 ปีที่แล้ว +1

    Apa setiap kode error F3 seperti ini kerusakannya?.. mohon infonya, terima kasih

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว

      Penyebab error F3 bnyk indikasi bisa dari kebocoran freon, expansi valve rusak, elektronik expansi rusak, sensor thermis discahrge rusak, pcb outdoor rusak. Harus di cek dulu dan di pastikan di bagian mana yg rusak.

  • @wijoyochannel
    @wijoyochannel 3 ปีที่แล้ว

    pipa kapiler 0,54 ini diameter luar apa diameter dalam ya om?

  • @hobyserviceabalabal7670
    @hobyserviceabalabal7670 3 ปีที่แล้ว +1

    kalo error E6 biasanya kompresor macet apa modulnya bli

  • @budiarimbawa334
    @budiarimbawa334 2 ปีที่แล้ว

    Mau nanya bli
    Ac daikin inverter stengah pk waktu ac hidup
    DinginNya hanya mau 15 menit
    Stelah itu compresor tambah panas jarum manipol naik terus dan
    Amper di compresor naik terus
    Stelah itu dinginNya hilang
    Kira "dimana rusakNya bli tolong solusinya bli,,🙏

  • @redmi4a782
    @redmi4a782 4 ปีที่แล้ว +1

    Itu dinginya bisa maksimal ga bro?? TRIms infonya

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว +1

      Bisa, normal dingin seperti biasa.., tapi kalo disetting low watt di remote agak kurang dingin karena kompresor pada low speed di putaran bawah, fungsi katup expansi sudah tidak ada jadi loss konstan menggunakan kapiler, jika kompresor ngegas pd putaran atas dinginnya normal seperti biasa.

  • @dentalexschanelmotovlog4044
    @dentalexschanelmotovlog4044 5 ปีที่แล้ว +1

    Klw e5 knp gan?dan cara mngatasinya

  • @wahyuardian9729
    @wahyuardian9729 5 ปีที่แล้ว

    Itu kira kira bermasalahny apa ya om kalau termistor out sm exvansi dg error f3

    • @wahyuardian9729
      @wahyuardian9729 5 ปีที่แล้ว

      Apakah ciri ciriny kompressor panas atau kompressor dingin

  • @skychins107
    @skychins107 4 ปีที่แล้ว

    sore gan,saya mau nanya nih,ac daikin inverter 1pk saya kalau dihidupin pada suhu 24'c 1jam kemudian suhu dinginnya ilang,tp kalau stel suhu 16'c bisa sampe 3jam baru hilang suhu dinginnya,tp indoor tetap hidup,kalau dimatiin pake remote n hidupin balik tetap gak mau dingin,tp kalau matiin kontak listrik dan pasang balik lalu dihidupin baru bisa dingin kembali.tp masalah tetap 1jam kemudian suhu dingin ilang lagi.kenapa ya kira2 n apa kerusakannya.tq

    • @skychins107
      @skychins107 4 ปีที่แล้ว

      kelupaan,gak ada kode errornya,semua bagus stel sam00

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Sudah dapat di cleaning indoor dan outdoor

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Cek kode error pada saat ac error atau tidak dingin.

    • @nsixfamily6420
      @nsixfamily6420 2 ปีที่แล้ว

      @@madearsa93
      Ini juga sama dengan AC saya daikin inverter 15 menit setelah jalan dinginya hilang

  • @andirizaldi2427
    @andirizaldi2427 5 ปีที่แล้ว

    Apakah inverternya ttp berfungsi dgn normal?

  • @whoiam1070
    @whoiam1070 5 ปีที่แล้ว

    ukuran kapiler dan panjang buat 2pk inverter brapa mas

  • @antowijaya1585
    @antowijaya1585 5 ปีที่แล้ว

    Bang klo panasonic inverter gak mau dingin knpa ya,,,freon 170 amper 1,4,,,itu ac nya 3/4 pk

  • @dominicxavier7384
    @dominicxavier7384 4 ปีที่แล้ว

    Bli.yang mau saya tanyakan?
    Itu expansi nya di copot.tidak pakei atau gimana yah🙏

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Expansi di lepas di ganti dengan kapiler

  • @komangkariasa4761
    @komangkariasa4761 2 ปีที่แล้ว

    Pak mau tanya apa expansi nya dicabut dari vcbnya atau dibiarin ?

  • @haurakhansa7875
    @haurakhansa7875 5 ปีที่แล้ว

    Luar biasa,,,,,berkah dan bermanfaat,,saya punya problem,Ac Daikin Tipe RKD 25GVM4, 1 pk,outdoor nyala,kompresor nyala,tapi sebentar dingin,sebentar hilang,,dinginnya cuman 1 menit,kemudian dingin lagi,,hilang lagi,dan seterusnya,apa penyebabnya ya mas? terima kasih,,,,,

  • @budiartotenosa5433
    @budiartotenosa5433 4 ปีที่แล้ว

    Kalah profesor jepang sm oi😄

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Hahaha, maaf sy juga baru belajar, memang bisa di gunakan ganti dengan kapiler bisa normal kembali, munkin pd setingan low watt agak kurang dingin sedikit tp tidak terlalu signifikan, dr pengalaman sy pribadi.

  • @lingkanpradana
    @lingkanpradana 4 ปีที่แล้ว +1

    Pak itu klo diganti expansionya persis aslinya apa tidak ada djual?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Ada yg jual di dealer nya harga lumayan

    • @lingkanpradana
      @lingkanpradana 4 ปีที่แล้ว +1

      @@madearsa93 boleh info dealer mna kebetulan saya tinggal dijimbaran, daikin mana, kisaran brp harganya?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Service center daikin di buluh indah harga sekitar 800an komplit body exvansi sm elektronic expansi nya.

    • @lingkanpradana
      @lingkanpradana 4 ปีที่แล้ว +1

      @@madearsa93 oke makasih infonya pak sukses selalu

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      @@lingkanpradana iya sm2, trimksih kmbli.

  • @agnisinatria3520
    @agnisinatria3520 3 ปีที่แล้ว

    Mungkin maksudnya "fix" atau "repair"

  • @komangkariasa4761
    @komangkariasa4761 2 ปีที่แล้ว

    Maaf maksudnya controlnya di lepas atau dibiarin ?

  • @anaketv
    @anaketv 4 ปีที่แล้ว

    Saya service ac
    Kata orang servicenya beli part dan harganya mahal
    Nah saya di kasih saran modif, jadi dari mesin yg diluar itu ada kabel sama sklar bell..
    Disuruh manual katanya biar ada freonnya, karna mesin yg diluar rusak otomatisnya jadi di buat manual gitu pake saklar
    Nah apa ya namanya alat nya itu yg mahal katanya..?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Maksudnya ? Pcb outdoor modul inverter.

    • @anaketv
      @anaketv 4 ปีที่แล้ว

      @@madearsa93 mungkin itu ya

    • @anaketv
      @anaketv 4 ปีที่แล้ว

      @@madearsa93 tapi gak paham saya begituan

    • @anaketv
      @anaketv 4 ปีที่แล้ว

      Jadi selama ini saya ya kalo gak dingin saya tekan sklar bell itu, langsung dingin.. Nanti gak dingin lagi saya tekan lagi dingin lagi

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      @@anaketv ini ac biasa bukan inverter ?
      Munkin maksudnya yg rusak modul pcb indoor ac jadi gak bisa auto kontak power ke power ke outdoor, jadi di ganti manual hidupin dengan saklar.

  • @acchannel1057
    @acchannel1057 2 ปีที่แล้ว

    Saya ngikuti cara anda, tapi tetap ngeblink lampunya, masih ga ON

  • @sitinurjanah7944
    @sitinurjanah7944 5 ปีที่แล้ว

    Om klo autdornya mati hidup apa nya ya..ngk sampe 1 menit mati autdornya..punya saya daikin inverter 1pk r32

    • @sitinurjanah7944
      @sitinurjanah7944 5 ปีที่แล้ว

      @@madearsa93 sapa cari kode dri remott ngk ada yang eror..aneh mas

    • @sitinurjanah7944
      @sitinurjanah7944 5 ปีที่แล้ว

      @@madearsa93 iya mas..kode nya eror di L5..motor kompresor nya.mksh ilmu nya mas

  • @donyilham7285
    @donyilham7285 4 ปีที่แล้ว

    Mau tanya dr jember jawa timur ,van hidup yg jalur konpresor mati hidup sebentar itu kira2 dari apa ya mas....

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Ac apa bos

    • @donyilham7285
      @donyilham7285 4 ปีที่แล้ว

      @@madearsa93 ac daikin 2pk inverter

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Cek kode error nya apa

    • @donyilham7285
      @donyilham7285 4 ปีที่แล้ว

      @@madearsa93 code eror 6h

    • @donyilham7285
      @donyilham7285 4 ปีที่แล้ว

      Mas made posisi daerah mana

  • @ipl5348
    @ipl5348 4 ปีที่แล้ว

    Apa tandanya,dan bagaimana cara megetahui klo expansi palep xg rusak boss ku

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Ampere naik, tekanan freon turun drastis

  • @putuagus999
    @putuagus999 2 ปีที่แล้ว

    gmn cara kerja expansi valve itu?...trs posisi expansi valve di outdoor di mananya?

    • @arapaimagold8088
      @arapaimagold8088 ปีที่แล้ว

      Ngatur besaran sirkulasi freon. Lihat di bagian belakang kompre kalau Daikin. Ada benda bulat dengan magnet di dalam. Itu EEVnya.

    • @CakraLithium-jm7uy
      @CakraLithium-jm7uy 7 หลายเดือนก่อน

      @@arapaimagold8088 kalau dibersihin atau diganti masih error berart pcbnya donk itu kan nyambung pcb yah,

  • @mochanwar8044
    @mochanwar8044 ปีที่แล้ว

    Maaf
    Kenapa ga di vacum ya

  • @satriasatria3894
    @satriasatria3894 3 ปีที่แล้ว +1

    Kenapa gk di ganti baru ekspensinya aja bang

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว

      Iya benar ganti expansi lebih bagus, ini cara alternatif tanpa expansi memungkinkan ac masih bisa bekerja dengan baik.

    • @satriasatria3894
      @satriasatria3894 2 ปีที่แล้ว

      Iya tapi lowat nya jadi hilang bang

  • @as_siam1209
    @as_siam1209 3 ปีที่แล้ว

    apakah gk pengaruh di modul nya kalo gk pakai electronic expansion

    • @madearsa93
      @madearsa93  3 ปีที่แล้ว

      Gk ada masalah, aman

    • @as_siam1209
      @as_siam1209 3 ปีที่แล้ว

      @@madearsa93 jadi apakah tidak muncul kode eror lagi setelah melepas komponen ter sebut.. dan di terapkan di ac non inverter misal panasonic dan merk ac lainya..

  • @sbs_herry_prass6434
    @sbs_herry_prass6434 4 ปีที่แล้ว

    Saya punya ac daikin inverter eroor u4 belum saya pasang unit outdoor nya saya nyalain indoor nya saja saya cek pakai remot u4

    • @sbs_herry_prass6434
      @sbs_herry_prass6434 4 ปีที่แล้ว

      Kira2 apanya ya om,apakah tes ac inverter harus pakai freeon juga supaya gak muncuk eroor u4

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว +1

      @@sbs_herry_prass6434 instalasi kabek indoor ke outdoor harus terkoneksi.

    • @sbs_herry_prass6434
      @sbs_herry_prass6434 4 ปีที่แล้ว

      Tapi tanpa freoon bisa gak gan?/ selang flexibelnya tidak si pasang?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว +1

      @@sbs_herry_prass6434 pipa ac tidak terpasang, modul akan protek indikasi error pada saat nyala

    • @sbs_herry_prass6434
      @sbs_herry_prass6434 4 ปีที่แล้ว

      Baik sangat bermanfaat dan terimakasih

  • @meethos
    @meethos 4 ปีที่แล้ว

    Bli made izin tanya , untuk kode error F6, Sudah pernah menqngabi kah?

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Error F6 kontrol Tekanan Tinggi dalam Pendinginan
      Metode
      Pendeteksian
      Kode Error
      Kontrol tekanan tinggi (Operasi berhenti, penurunan frekuensi, dll) diaktifkan dalam operasi
      pendinginan jika suhu dirasakan oleh Termistor Penukar Panas outdoor melebihi batas.
      Kondisi Keputusan Error
       Suhu dirasakan oleh Termistor Penukar Panas outdoor naik di atas 60 ° C.
       Kesalahan menjadi jelas ketika suhu turun di bawah sekitar 55 ° C.
      Dugaan Penyebab
       Ruang instalasi tidak cukup besar.
       Heat Exchanger outdoor Kotor
       Fan motor outdoor rusak
       Stop valve rusak
       Katup ekspansi elektronik atau kumparan rusak
       Termistor Penukar Panas outdoor
       PCB Unit Outdoor rusak

    • @bintankuchiha3374
      @bintankuchiha3374 ปีที่แล้ว

      Ngatasinnya gmn?

  • @bobx1473
    @bobx1473 4 ปีที่แล้ว

    👍 grande

  • @anakrumahan4172
    @anakrumahan4172 4 ปีที่แล้ว

    Bli made, kalau kerusakan U0 apa yang harus dicek ya? Saya baca di web artinya tersumbat atau expansion valve. Mohon bisa dibantu spesifiknya bli

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      U0 = kekurangan freon, ada kebocoran freon.

    • @anakrumahan4172
      @anakrumahan4172 4 ปีที่แล้ว

      @@madearsa93 freon sudah dicek nggak bocor bli, tekanan malah di 120. Ampere stabil, tekanan stabil, ac nggak dingin kadang suka mati dan lampu indikator kedip

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Ac daikin inverter ? Cek kode error sudah tepat ? Ac sudah dapat di cleaning indoor dan outdoor ?

    • @anakrumahan4172
      @anakrumahan4172 4 ปีที่แล้ว

      @@madearsa93 baru indoor bli, kode sudah bener berkali2 cek dapetnya U0. Nanti akan coba saya turunin outdoornya biar keliatan dan saya flush. Kemarin karena freon mau habis, jadinya tukang ac ngisi posisi tabung freon dibalik, takut gram2nya masuk bli. Apakah bisa dari situ penyebabnya bli? Karena setelah diisi freonnya selang 4 hari kejadian seperti ini bli

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      Freon jenis apa

  • @mk_technical
    @mk_technical 4 ปีที่แล้ว +1

    Klau error nya E6 knpa ya bang

    • @madearsa93
      @madearsa93  4 ปีที่แล้ว

      E6 : kompresor mengunci
      Cb reset dulu matikan power listrik 1menit kemudian hidupkan kembali, jika kesalahan error berulang, cek bisa karena voltase listrik melebihi 220-230v, expansi valve rusak, modul pcb outdoor rusak, terakhir kompresor rusak.