Sir can I ask about the package unit I have here zamil PNY300H model I check all the power supply from the PCB to the circuit breaker it’s ok the compressor 1 have 40amp and the number 2 compressor have 20amp only I already changed the high pressure switch and the low pressure switch but it’s still running 20amp what will be the trouble thank you for the answer in advance
Fan empire 2.5 Compressor empire. 20-22 Blower motor. 7.5 1 ghanta chalne ke bad boower motor chalta hi compressor aue fan bad hojata hi p c b me Jo 4 light 🚨 error batata hai
सर सेम मशीन है प्रॉब्लम ये है की रीस्टार्ट करने पर सबकुछ सही चल रहा है लेकिन् फिर दूसरे दिन सब बंद पड़ जाता है। अंदर मे जो स्क्रीन है उसमे कुछ भी सो नहीं करता है क्या प्रॉब्लम हो सकती है।
First of all, check the wire of the thermostat, if the wire is correct then check R C&G in thermostat 24 voltage if c,g 24 voltage does not come, then replace the thermostat..
I see this type blover motor good information knowledge improving video
Nice explanation good job easy way for new technicians
Zamil high volr checking tirpinv loss contacting trasfofmer main displaying not showing thrmostaris maing good cforme trasformer good bad checking outin after 24v comeing good metr checking fus sllchecing hp lp checkingreays ok
Thanks sir good example all step
Thank you sir very helpful video❤
Aap geneus ho ustad ji❤
👍👍👍👍 bahut hard sir 👍
Very very nice brow Allah bese you
Bro Allah bless you
Thank you sir bahut khoob hai
Mashallah mashallah thankyou sir ❤
Great job sir thanks
Excellent👌
Good job bro
Very nice sir
So good information sir ji but one video candinsor fan motor highi amps who is soulation please one video candinsor fan motor highi amps
Power frst fuse trsfrmer checking
Nice 👍
Good ❤expalen sar
Super
Badhiya tha guru
Thank you so much sir
Sir VMM trip ka bareme explain kariye
❤
Bhai aap Kahan se ho
❤❤❤
Sir york package ka fan overload switch trip aa rha h kaise thik kr skte h?
Sir can I ask about the package unit I have here zamil PNY300H model I check all the power supply from the PCB to the circuit breaker it’s ok the compressor 1 have 40amp and the number 2 compressor have 20amp only I already changed the high pressure switch and the low pressure switch but it’s still running 20amp what will be the trouble thank you for the answer in advance
How many amperes is written on the sticker?
Is the same ampere written for both the compressors?
@@Hvactechnician12 each compressor should be 40 each but it’s running only 20amp
@@Hvactechnician12 number 1 compressor run good 40amp but the number 2 compressor start and run good in 10 minutes it will go down to 20amp
What is the rated ampere on the unit name plate sticker and need to be checked something like, what is the standing pressure and actual pressure
15 ton Samsung ka paikej ac p 3 error aa raha hai Kya problem hoga
Her Roz resit kerna phrta hi is Barey me bathey
Good example
Sir hmary ps unit error 6 da raha hai...Compressor ON nai hota hai
Sir york ka package h LP lockout problem kyo aa rha h or kse remove kre?
Power off kr ke on krye. fir gas and filter blower motor speed and belt loose ye sb check krye
Assalam walekum Amjad Bhai zamil package unit PCB me 4 light 🚨 bilk ho raha hai
Fan empire 2.5
Compressor empire. 20-22
Blower motor. 7.5
1 ghanta chalne ke bad boower motor chalta hi compressor aue fan bad hojata hi p c b me Jo 4 light 🚨 error batata hai
Hi
2 phas me lagao k to 440 batayega na
Fully ajusted belt loos ok se size ok adjusted fullseting key and triead loose or juseted solveing konizok solvingok
Motor.besh.se.kam..karna.💪
सर सेम मशीन है प्रॉब्लम ये है की रीस्टार्ट करने पर सबकुछ सही चल रहा है लेकिन् फिर दूसरे दिन सब बंद पड़ जाता है। अंदर मे जो स्क्रीन है उसमे कुछ भी सो नहीं करता है क्या प्रॉब्लम हो सकती है।
Sabse से phale Standing and actual
Pressure kya hai and rated and actual ampere ketna hai and room
Temperature ketna हैं
ठीक है सर जी क्या आपका whatsapp number ya facebook account मिल सकता है, जिससे की आपको direct message kr saku please
Bowler is normally working how to chak c and g don't have 24 not come bat r and c came 24 what the problem
First of all, check the wire of the thermostat, if the wire is correct then check R C&G in thermostat 24 voltage if c,g 24 voltage does not come, then replace the thermostat..