ความคิดเห็น •

  • @surendrakverma555
    @surendrakverma555 2 ปีที่แล้ว +1

    Very good. Thanks 🙏🙏🙏🙏

  • @chintanvaria2238
    @chintanvaria2238 2 ปีที่แล้ว +2

    Majority of Motor Manufacturers do not provide Negative sequence withstand characteristics in Motor Datasheet. How we can derive it when it is not available!?

  • @thakurprakashk
    @thakurprakashk 3 หลายเดือนก่อน

    what's logic of 58 percent and 33 percent settings. clarify

  • @ShubhamMishra-ef6op
    @ShubhamMishra-ef6op 2 ปีที่แล้ว +1

    Please share locked rotor motor protection

  • @wongsabarchannel1335
    @wongsabarchannel1335 11 หลายเดือนก่อน

    Nice Video, For Line to Ground Fault, 33% is mean 33% x I Nominal? For Example Generator with FLA is 1000 A, it mean during L-G Fault is around 0.33x1000=330 Ampere?
    Some generator has Maximum a Continuous Negative Sequence is 15 %. If Negative sequence is flow up to 33% of Nominal, it means shall be clear by 46 to Circuit Breaker.

  • @RajeshSharma-ge8ui
    @RajeshSharma-ge8ui 2 ปีที่แล้ว +2

    Sir why during L-L fault current in 3rd phase will be zero

  • @bhaveshprajapati998
    @bhaveshprajapati998 2 ปีที่แล้ว +1

    Hello Sir,
    This video is very useful for me.
    I request you to prepare a video on how to read the control scheme of HV and LV Switchboard.
    Thanks and regards
    Bhavesh Prajapati

  • @parvezpathan6509
    @parvezpathan6509 10 หลายเดือนก่อน

    Thaks sir....,. Happy to see the easy explanation ....... really it's highly appreciated

  • @thakurprakashk
    @thakurprakashk 3 หลายเดือนก่อน

    confusing concept 😮😮😮