Nice experience shared 🙏 Ek question hai sirji Delta to star distribution transformer me neutral grounded kiya jata hai to neutral me zero potential panekliye.but neutral me for bhi kuch value tak voltage hoti hai tester bhi jalti hai. Neutral ground kiya hai to load unbalance hone pe bhi koi voltage nhi rehna chiye. Pls batayiye.
@@BuildingSanchalan thanks sir, ap kisi ko nirash nhi karte. Video dekh liya but Mera sawal ye hai ki jab neural ko grounding kiya hua hai fir bhi neural me kuch voltage reh jata hai unbalance load ke karan. Ye voltage bhi zero hona chiye na ground k through?
Sir jo invertor wala generator ata hai usko chalu kar ke invertor ko charged kar ke, aur phir jab invertor charged hojaye toh generator ko band kar ke invertor use kar sakte hai kya?
Oil temperature nahi engine ka temperature jab as per engine system se uper jata hai tab bo jo thermostet valve 45 temperature ke asps valve open hota hai or engine me water circulation krata hai engine ko thanda krata hai ke btaiye sir ,,toffic bahut lamba hai ,,, But sahi guide kijiye sabhi ko ,,adha adhuraa gyan kisi kam ka nahi hota hai
Sir oil ke liye separate oil temp sensor lagaya jata hai Aur rahi baat thermostat ki to wo ja coolent out let temp 85 degree ho jata hai tab thermostat valve open ho jata hai tab engine me coolent corculation chalu ho jata hai.
Sir, in an interview interviewer asked me how much excitation voltage is given to dg to start and from where they get excitation voltage. Will you please make video on it and explain the topic. Also he said if pmg is not there and becuase of some reasons your residual voltage become zero then how will you start the dg. As on a name plate of dg excitation voltage is diffrent for diffrent dg's then how well will do that.
Sir yah no.4 wala thermostat wala ans h vah Galt h yah D.g ki body par laga rhta h or body ya knopi ka temp. Over hone par sat off valve ki supply ko Kat deta h
Sir double starter wale DG m dono starter ek sath kam karte h ya ek stand by m rehta h plz ans aur kise clear kare ke dono starter ek sath kam kar rehe h?
Load badhega RPM kam honge, tab governer fuel supply badha dega or RPM maintain ho jayenge. Han RPM fix hote ha jab design kiya jaata ha isliye hi governer fuel supply badhata h jisse RPM maintain ho sake
The subject explained in Very simple way .... just Superb ... 👌
Hats off you sir ... 🙏
Beautiful and very informative video must watch.
Bhai aap kya krte ho
बहुत बढ़िया समझाया सर जी आपने आज तक नहीं किसी ने नहीं बताया ऐसा
Thanks Bhai
Bhut ache sir good explain.. 🙏🙏
Very nicely explained. Good job
Thanks a lot
Sir aap ko Bahut 2 Dhanbad jamane ke liye
Thanks
Nice experience shared 🙏
Ek question hai sirji
Delta to star distribution transformer me neutral grounded kiya jata hai to neutral me zero potential panekliye.but neutral me for bhi kuch value tak voltage hoti hai tester bhi jalti hai.
Neutral ground kiya hai to load unbalance hone pe bhi koi voltage nhi rehna chiye.
Pls batayiye.
watch it th-cam.com/video/lFSEduHhlrU/w-d-xo.htmlsi=A4SUras_PRmFMXEF
everything you will found
@@BuildingSanchalan thanks sir, ap kisi ko nirash nhi karte. Video dekh liya but Mera sawal ye hai ki jab neural ko grounding kiya hua hai fir bhi neural me kuch voltage reh jata hai unbalance load ke karan. Ye voltage bhi zero hona chiye na ground k through?
Apne kafi achi information di hai thanks sir
thanks
Bahut achha sir ji explain.kiya.
VERY simple method....... Very interesting
Thanks
Sir Transformer pe video banaye
Nuce points learningvji 🙏🙏
Teaching style is excellent
Thanks but i am engineer. keep watching.
Excellent sir 👏
So nice of you
Sir ek video bano
1. Building ka electrical load kaise nikale
2. Lux meter kaise use karte hain.
Jarur,
@@BuildingSanchalan sir app ki video se bhaut fayda hota hai, God bless you.
Good
Banao sir.
Veri usefull video sir ji
Thanks sir explain
Sir jo invertor wala generator ata hai usko chalu kar ke invertor ko charged kar ke,
aur phir jab invertor charged hojaye toh generator ko band kar ke invertor use kar sakte hai kya?
Invertor seperate ha use use kar sakte ha parantu battery discharge hogi.
V good helpful video👍
So nice of you
Great work 👏
Thank you so much 😀
thanx you gave a very good suggestion
Sir please seperate detailed video on Turbo charger
Super video sir ...thank you
Best zabardast
Thanks
Dear sir
Please dg self kaise Kam karta hai detail me video banaye
Nice explaination Sir🙏
Keep watching
Oil temperature nahi engine ka temperature jab as per engine system se uper jata hai tab bo jo thermostet valve 45 temperature ke asps valve open hota hai or engine me water circulation krata hai engine ko thanda krata hai ke btaiye sir ,,toffic bahut lamba hai ,,,
But sahi guide kijiye sabhi ko ,,adha adhuraa gyan kisi kam ka nahi hota hai
Thank you sharma ji for correct us. Engine ka temperature thermostate oil ke thru hi to maapti hogi. please reply.
Sir oil ke liye separate oil temp sensor lagaya jata hai
Aur rahi baat thermostat ki to wo ja coolent out let temp 85 degree ho jata hai tab thermostat valve open ho jata hai tab engine me coolent corculation chalu ho jata hai.
Self starter :- 1 battery 12 volts
2 batteries 24 volts
yes bur i could not what you want to say/ask.
GCP means generator control panel or governor control panel?
generator control panel
Great information
Glad it was helpful!
Lovely
Exeelent sir ji 🌹🌹🌹🌹🌹🌹
Very very thanks sir for assam
Welcome
Nice 👏👏👏👏👏
Thanks
Nice video 👍
Thanks 👍
Very nice 👌 Sir
Thanks and welcome
Nice.....👆
Thanks
सादर प्रणाम सर जी
Dhanyabad.
DC shunt motor have a maximum torque, to provide the force to fly wheel.
But brushed dc motor is used in DG
Thanks for good answers .
Very nice video
Thanks
Sir lube oil and coolent temp kitna max and min hone pr dg auto off ho jata h
Auto off on Lube oil pressure 3 - 7 Kg/cm2 and normal temp range 45 degree to 80 degree C. Coolant temp Max-95 degree C. DG will be auto trip.
@@BuildingSanchalan Thanku dear sir for support
Good video sir thanks
So nice of you
Excellent sir...
🙂
🙏
Thank You Sir
Priming pump se fuel ko injector tak pahunchate hai.. ya bole to if there is any air buble in fuel line, usko nikalne ke kam ata hai..
Rght ans
Ye banda priming pump ko oil ka application bata raha hai
Single phase genset me nutrat ko ground karte hai kya?
Nahi
DG ka rpm to constant raheta hai na ? Ya to 1500 ya to 1800
Kiya jaata ha AVR ke thru for same voltage.
Sir D g me oil Kitna Jata Hai oil Cup change karte hai kitne ghante ke bad oil check chainj hai aur sab video banaaiye.
KOn se dg ke baare janana chahte ho.
Sir RPM Kam Jada karane SE frequency change vogi kya
Yes.
Very nice 👍
thanks
❤❤
Sir, in an interview interviewer asked me how much excitation voltage is given to dg to start and from where they get excitation voltage. Will you please make video on it and explain the topic. Also he said if pmg is not there and becuase of some reasons your residual voltage become zero then how will you start the dg. As on a name plate of dg excitation voltage is diffrent for diffrent dg's then how well will do that.
th-cam.com/video/Kwfkgn-_yT4/w-d-xo.htmlsi=gU7YOrmFYZxPNsxf
It's depends on the kva of the DG.
It may be 48volt /63volt
Thermostat is link with hot water
Thermostate does link both chilled and hot water.
Priming pump air cooled generator m b lgi hoti h kya
Jaruri ni ha DG ki capacity ke anusaar hota ha. han 500 KVA air cooled me hota ha
Sir yah no.4 wala thermostat wala ans h vah Galt h yah D.g ki body par laga rhta h or body ya knopi ka temp. Over hone par sat off valve ki supply ko Kat deta h
Good sir
Thanks and welcome
Very Good
Thanks
Sir battery series connect mein hoti ya parallel me
In DG, series connection
Amazing sir
Thanks and welcome
Super 👍
Thank you
Sir ji...
AVR ..GCP ko order deta hai
..aur GCP ... EFC ko order deta..??
Mutlab AVR, GCP, EFC connection kaise hota hai.??
Friend, Trully i don't have actual Idea.
AVR.. GCP ko order deta hai.???
Wiring harness through ye sab Contrl box ya to ECM se connect hote hai bhai.
Nice
Thanks
Tq sir 🙏🙏
Hi
Q8 mei battery type pucha hei toh type puchiye na....konsi battery puchne se toh 12/24V hi answer rahega
U R right.
Good brefing
Sir 24v pe ku nahi self lega. Kitne voltage hoga to chlega 10%5 % chalta he kya nhi sir jra btaye _,+
26 to 27 volt, bcoz at the time of self voltage will be drop.
@@BuildingSanchalan sir jb battry 24 volt ki lagi hai to wo 26-27 volt current kaise degi.?
Explain how to synchronizing DG..??
OK, For synchronizing Frequency,Phase sequence and voltage should be same.
Very good sir
Good sar
❤❤❤❤❤
Thanks sir g
Sir g ,dol feder and star and delta ka video banadijiea na sir
Request sir
Welcome
th-cam.com/video/I-WeJ5OC2qs/w-d-xo.htmlsi=kXau3CUJK3hvIYIK
Thankq dear sir 🙏
Most welcome
Thanku sir
Welcome
DG self starter per ek seperate detailed video bana den please
OK
Thank you sir
Sir double starter wale DG m dono starter ek sath kam karte h ya ek stand by m rehta h plz ans aur kise clear kare ke dono starter ek sath kam kar rehe h?
Starter, me samjha ni
Sir jab ek DG m double self starter ho to Kya wo dono self starter ek Sath operate hote h ?
Kidr ho job pe mumbai me kya
Self starter dono ek saath challenge ha
@@rahulkamble5943 NCR
Sir g load increase hona RPM pr kya effect padega kyu alternator ke RPM toh fix hota jitna voh design kiya h
Load badhega RPM kam honge, tab governer fuel supply badha dega or RPM maintain ho jayenge. Han RPM fix hote ha jab design kiya jaata ha isliye hi governer fuel supply badhata h jisse RPM maintain ho sake
@@BuildingSanchalan thanks sir g
Great
Great
Sir dg ke chember me filter kis side me hota hai
Dono side me hote h
Thanks sir
sir load ke hisab se dg ka selection kaise krte hai ye bta dijye
connected load ka 80 % or what you want to run on DG
Super
Dg me kon sa lube oil dala jata hai
Volvoline 15 W 40 grade. Make can be changed.
Sir shift engineer ware video banao
soon
Lead acid battery kyu lagate h?
Now yeh battery hi sasti ha aur maintenance free bhi,
Dg ko kva me hi kiyo measuring krte hai
Kya kva please ans sir
yeh power factor ko impact ni karta isliye.
Q 6 priming pump fuel se related hai sir
Oil ke liye oil pump hota hai
God job
Thanks
good sir
Keep watching
Online corse hai kya dg oprator
Yes ITI Diesel mechanic
Agar battery 24 volt Ki Hai To vah 26 27 voltage Kaisa Degi
24 volt battery 27 volt tak charge ho jaati ha.
D. G me lead acid Battary hi kiu lagate h sir
Sasti hoti ha aur pick up( initial current) achha hota h
Sir mee plant ka video banao
Dear never write the short form please
Sir ager battery 24 volt ka h toh woh 26 volt kese dikhayega
Full charge hone ke baad. ek baar check kar lo confirm ho jayega.
DG stat karte samay batric ka kitna volt Kam Karta hai
6 to 7
Sir DG se kitne cable nikalte hai
According to load.
Thank you sir ❤️
Most welcome
🙏🙏🙏🙏🙏🙏🙏
Per hours Lube oil consumption kitna hoga
Plz help
Lube oil per hour consumption ni hota