Sir jo invertor wala generator ata hai usko chalu kar ke invertor ko charged kar ke, aur phir jab invertor charged hojaye toh generator ko band kar ke invertor use kar sakte hai kya?
Nice experience shared 🙏 Ek question hai sirji Delta to star distribution transformer me neutral grounded kiya jata hai to neutral me zero potential panekliye.but neutral me for bhi kuch value tak voltage hoti hai tester bhi jalti hai. Neutral ground kiya hai to load unbalance hone pe bhi koi voltage nhi rehna chiye. Pls batayiye.
@@BuildingSanchalan thanks sir, ap kisi ko nirash nhi karte. Video dekh liya but Mera sawal ye hai ki jab neural ko grounding kiya hua hai fir bhi neural me kuch voltage reh jata hai unbalance load ke karan. Ye voltage bhi zero hona chiye na ground k through?
Sir yah no.4 wala thermostat wala ans h vah Galt h yah D.g ki body par laga rhta h or body ya knopi ka temp. Over hone par sat off valve ki supply ko Kat deta h
Sir double starter wale DG m dono starter ek sath kam karte h ya ek stand by m rehta h plz ans aur kise clear kare ke dono starter ek sath kam kar rehe h?
Oil temperature nahi engine ka temperature jab as per engine system se uper jata hai tab bo jo thermostet valve 45 temperature ke asps valve open hota hai or engine me water circulation krata hai engine ko thanda krata hai ke btaiye sir ,,toffic bahut lamba hai ,,, But sahi guide kijiye sabhi ko ,,adha adhuraa gyan kisi kam ka nahi hota hai
Sir oil ke liye separate oil temp sensor lagaya jata hai Aur rahi baat thermostat ki to wo ja coolent out let temp 85 degree ho jata hai tab thermostat valve open ho jata hai tab engine me coolent corculation chalu ho jata hai.
Sir, in an interview interviewer asked me how much excitation voltage is given to dg to start and from where they get excitation voltage. Will you please make video on it and explain the topic. Also he said if pmg is not there and becuase of some reasons your residual voltage become zero then how will you start the dg. As on a name plate of dg excitation voltage is diffrent for diffrent dg's then how well will do that.
Load badhega RPM kam honge, tab governer fuel supply badha dega or RPM maintain ho jayenge. Han RPM fix hote ha jab design kiya jaata ha isliye hi governer fuel supply badhata h jisse RPM maintain ho sake
Bro yaha pr engine start hona jaruri h.. Ek dg operator battey ki voltage or gravity check krta h jaha pe electrisian ka topic hoga vaha fit baithega apka ye question
The subject explained in Very simple way .... just Superb ... 👌
Hats off you sir ... 🙏
Beautiful and very informative video must watch.
Bhai aap kya krte ho
बहुत बढ़िया समझाया सर जी आपने आज तक नहीं किसी ने नहीं बताया ऐसा
Thanks Bhai
Bhut ache sir good explain.. 🙏🙏
Very nicely explained. Good job
Thanks a lot
Sir jo invertor wala generator ata hai usko chalu kar ke invertor ko charged kar ke,
aur phir jab invertor charged hojaye toh generator ko band kar ke invertor use kar sakte hai kya?
Invertor seperate ha use use kar sakte ha parantu battery discharge hogi.
Bahut achha sir ji explain.kiya.
Sir aap ko Bahut 2 Dhanbad jamane ke liye
Thanks
Apne kafi achi information di hai thanks sir
thanks
Nice experience shared 🙏
Ek question hai sirji
Delta to star distribution transformer me neutral grounded kiya jata hai to neutral me zero potential panekliye.but neutral me for bhi kuch value tak voltage hoti hai tester bhi jalti hai.
Neutral ground kiya hai to load unbalance hone pe bhi koi voltage nhi rehna chiye.
Pls batayiye.
watch it th-cam.com/video/lFSEduHhlrU/w-d-xo.htmlsi=A4SUras_PRmFMXEF
everything you will found
@@BuildingSanchalan thanks sir, ap kisi ko nirash nhi karte. Video dekh liya but Mera sawal ye hai ki jab neural ko grounding kiya hua hai fir bhi neural me kuch voltage reh jata hai unbalance load ke karan. Ye voltage bhi zero hona chiye na ground k through?
Sir lube oil and coolent temp kitna max and min hone pr dg auto off ho jata h
Auto off on Lube oil pressure 3 - 7 Kg/cm2 and normal temp range 45 degree to 80 degree C. Coolant temp Max-95 degree C. DG will be auto trip.
@@BuildingSanchalan Thanku dear sir for support
GCP means generator control panel or governor control panel?
generator control panel
Great work 👏
Thank you so much 😀
V good helpful video👍
So nice of you
Sir yah no.4 wala thermostat wala ans h vah Galt h yah D.g ki body par laga rhta h or body ya knopi ka temp. Over hone par sat off valve ki supply ko Kat deta h
Excellent sir 👏
So nice of you
Single phase genset me nutrat ko ground karte hai kya?
Nahi
Veri usefull video sir ji
Sir good morning power factor kam hone se kya problem ho sakta hai aur jyada hone se kya problem ho sakta hai
th-cam.com/video/S0yZ7X0vwfs/w-d-xo.htmlsi=fnXVlzdj4V3i79n8 ise dekho sab pata chal jaayega
Nuce points learningvji 🙏🙏
Thanks sir explain
Super video sir ...thank you
Priming pump air cooled generator m b lgi hoti h kya
Jaruri ni ha DG ki capacity ke anusaar hota ha. han 500 KVA air cooled me hota ha
Sir ji...
AVR ..GCP ko order deta hai
..aur GCP ... EFC ko order deta..??
Mutlab AVR, GCP, EFC connection kaise hota hai.??
Friend, Trully i don't have actual Idea.
AVR.. GCP ko order deta hai.???
Wiring harness through ye sab Contrl box ya to ECM se connect hote hai bhai.
VERY simple method....... Very interesting
Thanks
Sir Transformer pe video banaye
Teaching style is excellent
Thanks but i am engineer. keep watching.
thanx you gave a very good suggestion
Sir D g me oil Kitna Jata Hai oil Cup change karte hai kitne ghante ke bad oil check chainj hai aur sab video banaaiye.
KOn se dg ke baare janana chahte ho.
Dg me kon sa lube oil dala jata hai
Volvoline 15 W 40 grade. Make can be changed.
Sir double starter wale DG m dono starter ek sath kam karte h ya ek stand by m rehta h plz ans aur kise clear kare ke dono starter ek sath kam kar rehe h?
Starter, me samjha ni
Sir jab ek DG m double self starter ho to Kya wo dono self starter ek Sath operate hote h ?
Kidr ho job pe mumbai me kya
Self starter dono ek saath challenge ha
@@rahulkamble5943 NCR
Nice explaination Sir🙏
Keep watching
Oil temperature nahi engine ka temperature jab as per engine system se uper jata hai tab bo jo thermostet valve 45 temperature ke asps valve open hota hai or engine me water circulation krata hai engine ko thanda krata hai ke btaiye sir ,,toffic bahut lamba hai ,,,
But sahi guide kijiye sabhi ko ,,adha adhuraa gyan kisi kam ka nahi hota hai
Thank you sharma ji for correct us. Engine ka temperature thermostate oil ke thru hi to maapti hogi. please reply.
Sir oil ke liye separate oil temp sensor lagaya jata hai
Aur rahi baat thermostat ki to wo ja coolent out let temp 85 degree ho jata hai tab thermostat valve open ho jata hai tab engine me coolent corculation chalu ho jata hai.
Sir dg ke chember me filter kis side me hota hai
Dono side me hote h
Sir 24v pe ku nahi self lega. Kitne voltage hoga to chlega 10%5 % chalta he kya nhi sir jra btaye _,+
26 to 27 volt, bcoz at the time of self voltage will be drop.
@@BuildingSanchalan sir jb battry 24 volt ki lagi hai to wo 26-27 volt current kaise degi.?
Exeelent sir ji 🌹🌹🌹🌹🌹🌹
Nice.....👆
Thanks
Nice 👏👏👏👏👏
Thanks
Sir ji DG me Jo Dainemo jo laga rahta hai uska kiya kam hota hai
Battery charge karna
Sir ji battery charger karne ke liye to panel se wire dalte hai na sir ji
@@hengineeringmind9871 han, jab engine band hota h tab k liye
Nice video 👍
Thanks 👍
Great information
Glad it was helpful!
Sir please dg ka efficiency ky kw me kaise nikalte hai
Total unit generated/ total fuel consumption
DG ka rpm to constant raheta hai na ? Ya to 1500 ya to 1800
Kiya jaata ha AVR ke thru for same voltage.
Sir, in an interview interviewer asked me how much excitation voltage is given to dg to start and from where they get excitation voltage. Will you please make video on it and explain the topic. Also he said if pmg is not there and becuase of some reasons your residual voltage become zero then how will you start the dg. As on a name plate of dg excitation voltage is diffrent for diffrent dg's then how well will do that.
th-cam.com/video/Kwfkgn-_yT4/w-d-xo.htmlsi=gU7YOrmFYZxPNsxf
It's depends on the kva of the DG.
It may be 48volt /63volt
Sir battery series connect mein hoti ya parallel me
In DG, series connection
Sir RPM Kam Jada karane SE frequency change vogi kya
Yes.
Dg ko kva me hi kiyo measuring krte hai
Kya kva please ans sir
yeh power factor ko impact ni karta isliye.
DG stat karte samay batric ka kitna volt Kam Karta hai
6 to 7
Sir ek video bano
1. Building ka electrical load kaise nikale
2. Lux meter kaise use karte hain.
Jarur,
@@BuildingSanchalan sir app ki video se bhaut fayda hota hai, God bless you.
Good
Banao sir.
D. G me lead acid Battary hi kiu lagate h sir
Sasti hoti ha aur pick up( initial current) achha hota h
Sir ager battery 24 volt ka h toh woh 26 volt kese dikhayega
Full charge hone ke baad. ek baar check kar lo confirm ho jayega.
Excellent sir...
DG me Self ke time battery voltage kya rht hai
Self ke time battry voltage 26 volt se 17 volt tak jaati ha
sir load ke hisab se dg ka selection kaise krte hai ye bta dijye
connected load ka 80 % or what you want to run on DG
Sir g load increase hona RPM pr kya effect padega kyu alternator ke RPM toh fix hota jitna voh design kiya h
Load badhega RPM kam honge, tab governer fuel supply badha dega or RPM maintain ho jayenge. Han RPM fix hote ha jab design kiya jaata ha isliye hi governer fuel supply badhata h jisse RPM maintain ho sake
@@BuildingSanchalan thanks sir g
Lead acid battery kyu lagate h?
Now yeh battery hi sasti ha aur maintenance free bhi,
Dear sir
Please dg self kaise Kam karta hai detail me video banaye
Sir D G kitne bhi kva ka ho usko 1500 RPM pe hi kyu set kiya jata hai
Due to get 50 Hz frequency.
Lovely
Explain how to synchronizing DG..??
OK, For synchronizing Frequency,Phase sequence and voltage should be same.
Best zabardast
Thanks
main diploma mu car service center me work karta to mai industry me maintenance department me ja sakta hu ke nhi
तुमने डिप्लोमा किस ब्रांच में किया है
तुमने डिप्लोमा किस ब्रांच में किया है तुम किसी भी इंडस्ट्री में जा सकते हो
@@BuildingSanchalan electrical
Dg se voltage kaisa banta hai...
th-cam.com/video/Kwfkgn-_yT4/w-d-xo.html please watch it for same
sir aapne btaya coil ko ghumaya jata pr ye sahi nahi hi
Sahi kya ha batao please.
Sir please seperate detailed video on Turbo charger
Thanks for good answers .
🙂
🙏
Thank You Sir
Very very thanks sir for assam
Welcome
Agar battery 24 volt Ki Hai To vah 26 27 voltage Kaisa Degi
24 volt battery 27 volt tak charge ho jaati ha.
Very nice 👌 Sir
Thanks and welcome
Sir DG se kitne cable nikalte hai
According to load.
Very nice 👍
thanks
Very nice video
Thanks
Priming pump se fuel ko injector tak pahunchate hai.. ya bole to if there is any air buble in fuel line, usko nikalne ke kam ata hai..
Rght ans
Ye banda priming pump ko oil ka application bata raha hai
Good video sir thanks
So nice of you
Sir kya dg rectifier se chalu kr sakte hai kya
Rectifiers AC ko DC me convert karte h
How much current does the self motor carry?
Bro yaha pr engine start hona jaruri h.. Ek dg operator battey ki voltage or gravity check krta h jaha pe electrisian ka topic hoga vaha fit baithega apka ye question
Sir ji Tharmostate kaha lagate hai
Jahan kahin ka bhi temperature measure karna hota h,
Ex. Radiator, PHE, coolant tank,lube oil sump pit ......
Sir fuel ka pressure kitna rahata hai
अलग-अलग पॉइंट पर अलग-अलग प्रेशर होता है इजेक्टर में अलग होता है pt पंप के बाद अलग होता है सीआरडीआई में अलग होता है
सादर प्रणाम सर जी
Dhanyabad.
Per hours Lube oil consumption kitna hoga
Plz help
Lube oil per hour consumption ni hota
Super 👍
Thank you
Amazing sir
Thanks and welcome
Sir, please tell about PUC pollution under control certificate for Dg set.
It is called stack emission, soon will upload video
Online corse hai kya dg oprator
Yes ITI Diesel mechanic
Jb battery 24 volt ki hai to 26 kahn se milega
Check practically. Will get definately.
DC shunt motor have a maximum torque, to provide the force to fly wheel.
But brushed dc motor is used in DG
Thankq dear sir 🙏
Most welcome
Tq sir 🙏🙏
Hi
24 volt ki battery 26 volt kaise dikhaygi
check and reply please.
Very Good
Thanks
❤❤
Q8 mei battery type pucha hei toh type puchiye na....konsi battery puchne se toh 12/24V hi answer rahega
U R right.
Good sir
Thanks and welcome
❤❤❤❤❤
Sir En sabh ka PDF kaha se mile pliss batao
Thanks sir g
Sir g ,dol feder and star and delta ka video banadijiea na sir
Request sir
Welcome
th-cam.com/video/I-WeJ5OC2qs/w-d-xo.htmlsi=kXau3CUJK3hvIYIK
750 kva ka dg battery voltage 25.30 pa start ho jata hai
ho sakta ha.
Very good sir
Aur fuel kya hota hai sir
Diesel
DG self starter per ek seperate detailed video bana den please
OK