Bagus om, suatu hari nanti Inhsa Allah akan saya praketakan untuk rumah anak saya tapi spek down lah, pompa transfer dan pompa booster yang pakai pompa sumur dangkal atau pompa semi jetpump, sekarang ini dirumah, instalasi listrik pompa saya pakai kontaktor, tiap hari mendengar suara jedak jedek walau pompa sumur dangkal. Mungkin 1 RT/RW di kampung saya, hanya saya yang pasang pompa 200 watt pakai kontaktor hehehehe WLC saya pakai tapi bukan pakai omron berkatoda om, tapi radar tapi seting konek B1 dan B2 (SUMP). saya suka otomatisasi, karena saya punya mesin dryer laundry buatan Bantul, otomatissinya isinya, selenoid gas, temperatur control, relay, timer H3CR, igniter, sensor flame, MCB, pilot lamp, sekering gelas .....seneng nambah ilmu sama
Terima kasih sudah berbagi,mantap sekali ilmunya, profesional engineer. Minta sarannya dimana posisi terbaik dari pressure tank dan pressure switch, bila instalasi plumbing tidak standard, sehingga di bagian terjauh dari pompa terjadi penurunan tekanan yang cukup besar.
Untuk menghindari drop pressure yg besar pada jaringan pipa tentu saja harus ada keseimbangan antara head dan kapasitas pompa dengan jaringan plumbing. Pressure tank dan pressure switch di posisi terbaik pun tidak akan banyak berpengaruh jika jaringan plumbingnya buruk karena loses nya pada pipa jaringan, bukan pada pompa. Contohnya ada di video test commisioning pompa booster, hasilnya jauh dari harapan.
Wiring diagram nya sdh pernah saya upload , silahkan di cek playlist pompa booster untuk video dan link download nya saya cantumkan di deskripsi masing² video.
Terima kasih banyak Pak, peneranagan yang sunguh jelas, bagaimana saya bisa menghubugi bapak untuk mempelajarai nya dengan lebih lanjut, saya dari malaysia.
@@HSPOMPA Hello! Sir, good morning Thank you for your reply. May i request you to know if you are a manufacturing company for the booster systems, if yes how do you control the panel for the moment? We are a manufacturing company in India and for last 10 years we are manufacturing panels for booster and hydro-pneumatic systems. we also manufacture dedicated controllers for this application, if you find it interesting i will be happy to share the details of the controller-HMI. Thank you, hear you soon. Regards Abhijit siddhaielectsys@hotmail.com
@@abhijitrashinkar Glad to know your interest ...but unfortunately my company is a small company and i'm just a technician who not familiar with HMI. My control panel is a conventional one with push button and pilot lamp for indicator. So..thank you for your offered..
@@HSPOMPA No no Sir you got me wrong, the controller we manufacture are beyond your imagination and are very very cost effective, I request your email address only to share the details if you think interesting then you can think of the commercials, and to be honest the controller is of interest to a technical person, so it is my humble request to share your email address.
Sebenar nya hampir gak ada beda nya , hanya secara pribadi saya lebih suka di buat terpisah. Lebih mudah memilih mana yg difungsikan ketika di posisi manual.
@@HSPOMPA baik Pak, karena di lapangan banyak juga saya lihat selektor switch auto manual nya disatukan, terimakasih atas balasan nya, Salam sehat dan sukses selalu
Download aja...wiring diagram nya sdh pernah saya upload video nya. Cari di playlist video wiring diagram , link download pdf nya ada di deskripsi video.
How could you said this tutorial is excellent if you can't understand not a single word of indonesian language...Hahaha...by the way, may i know where are you from?
@@HSPOMPA From philippines... i understand when you said the word contactor pressure switch, and i know you explained it what is the used and purposes of each parts
@@arielcunanan4994 I'd put english subtittle on this video...i hope it will help you a little bit to understand about how booster pump controller is work...
Mantab Mohon arahannya Misalkan kita setting boster pump menggunakan 3 buah pompa boster Setelah sekian lama pemakaian ada trouble, yaitu 1.pompa nyalanya gak mau berhenti 2.pompa nyalanya cuma 1 pompa, saat mati dan hidup lagi cuma pompa no 1 trus, mati lagi dan hidup lagi, tp hanya pompa no 1 lagi yg hidup 3.settingan 3 pompa, akan tetapi mau kita rubah sementara menjadi 2 pompa yg kerja karena ada perbaikan pompa no. 3 , itu gmn pak 4.mohon share wiringnya pak Mohon masukannya, Terima kasih semoga dilancarkan segala urusannya, dan semakin sukses
1. Pompa nyala gak mau berhenti itu sebabnya hanya karena titik setting Off gak tercapai. Sebabnya kapasitas pompa gak mencukupi dari banyaknya pemakaian. 2. Alternate pompa nya gak jalan , jadi gak bisa gantian. 3 & 4 . Cek playlist wiring diagram
1.titik setting pompa sudah mencapai titik setting max, tp tetep nyala terus menerus sampai mentok di preasure gauge masih gak mau mati??? 2.alternative maksdnya gmn pak??? Atau hsrnya udah error??
@@davidprakoso7619 1. Oh klo itu pressure switch nya yg bermasalah , sdh sampai titik pressure tp gak mau lepas switch nya. 2. Bisa dari HSR , bisa juga dari komponen pendukung. HSR yg bagus itu tiap 10 menit pindah sendiri
Bang mau nanya pompa kan ad 2 pompa 1 sama pompa 2 setiap keran di nyalakan kluar airnya kdang keras kadang ngk setelah di teliti ternyata setiap giliran pompa 2 ngk mau saya pikir pompanya yg bermasalah setelah saya cek manual pompa 2 normal saya bingung apnya Kira2 bermaslah?
Pak klau pke ITL bsa kerja bergantian bgtu yah. Cra seting pressure switch gmna pak. Apa kah off nya set dua bar bgtu pla sett off nya misalnya di 1 bar
Mantabs, Pak. Namun saya ada pertanyaan, Pak. Untuk pompa booster kan wajib pakai pressure tank untuk menghindari cetak cetok, nah tipe pressure tank-nya itu jenisnya apakah sama dengan fire pump, Pak ? & bagaimana pemilihan kapasitas dan pressure dari pressure tank tsb ? serta mungkin bisa dibuatkan tutorial menggunakan 3 pompa, Pak agar diketahui settingan di pressure switchnya. Terima ksh.
Hal² yang di tanyakan sdh saya pernah saya jelaskan, silahkan di cek : th-cam.com/video/NTg6L5lsYz4/w-d-xo.html th-cam.com/video/rCUZxL6uR7k/w-d-xo.html
@@hanunmamat7985 Klo perlu nya hanya bergantian kerja pompa , bisa pakai rangkaian 3 buah relay LY4 atau MY4. Bisa di lihat di video berikut : 👉 th-cam.com/video/EUhjMXDlCp0/w-d-xo.html
Belum kah..? Secara singkat saya sebutkan fungsi kerja WLC hanya sebagai Safety ketersediaan air, hubungan nya dengan sistem hanya sebagai proteksi ada atau tidak ada nya air yang tersedia untuk pompa bisa berfungsi dengan aman..Semoga bermanfaat..!
Parallel alternate tanpa HSR bisa saja , pakai komponen alternate yg lain semisal impulse relay atau latching relay dengan tambahan relay dan sistem wiring.
Workshopnya di mana pak.maksud sya jakarta mana?? Sya baru terjumpa chanel youtube bpk.bole bagi whatsupp bpk ngak.ada pt tempat sya bekerja suruh buat pump panel hydrant.dia paksa sya kuasai.padahal itu bukan bidang sya.terpaksa sya pelajari pump panel yg dia beli sya bongkar dan pelajari.sya bilang kalau mau mcm ini fotocopy seperti china bisa aja kita buat asal jgn component lain.relay pun seperti ini juga sya bilang.sya ini awam dgn relay.tq pak
Maaf, Pak. Bagaimana panel pompa booster paralel alternate ini mengetahui jika pompa 1 bekerja namun tidak kapasitas yang diingin tidak dipenuhi sehingga pompa 2 diperintahkan untuk jalan ? Sensor apa yang mendeteksi kekurangan kapasitas air yang dihasilkan pompa 1 ? Selain itu apa sebenarnya fungsi HSR 2 maupun G4Q tsb, apakah tidak cukup menggunakan timer model H3CR saat pindah ke pompa berikutnya ? Mohon pencerahannya ya, Pak. Terima Kasih.
Sensor deteksi sebenarnya lebih ke pressure, pressure drop berarti kapasitas drop juga dan ini tugas nya pressure switch untuk deteksi nya. Fungsi HSR dan G4Q lebih kepada kontrol starting kontaktor berdasarkan signal dari pressure switch. Klo H3CR itu TDR, jadi hidup nya pompa berdasarkan setting timer nya.
Pak mau tanya apakah bisa pompa booster memakai relay G4Q dengan disistem kerjanya pararel alternate. Sedangkan yg saya tahu relay G4Q bekerja secara bergantian sebagai kontrol kontak pada kontraktor, sebelum dan sesudah nya saya ucapkan Terima kasih.
Bisa...tambah relay biar lebih safety. Video berikut contoh sederhana penggunaan G4Q untuk sistem parallel alternate : th-cam.com/video/Uzc6ssHnT4s/w-d-xo.html
@@HSPOMPA Waduh,,,berarti saya salah hitung, Pak. Tadinya saya pikir bisa untuk motor 3kW atau 4kW. Apa karena saya belum tambahkan besarnya MCB 1 phase yang 2A (rangkaian kontrol) ya, Pak ?
@@GERAND.Flowmeter.Distributor Nah...klo pake rumus cari Ampere, seharusnya 10 Ampere cukup buat 4 kw. Yang gak di perhitungkan itu lonjakan arus nya. Saya pakai 16 A untuk 4 kw karena MCB yg saya pakai itu type Domae, untuk pemakaian arus hubung singkat max. 4,5 kA. Untuk proteksi beban lebih kan ada TOR, lagi pula harga nya lebih murah..😁
Beda box panel doang...klo box panel ini pesanan orang. Ketebalan plat sama , beda warna cat dan kunci. Untuk info harga bisa hubungi : 👉 Tyo +6282123466269 👉 Yudi +6282112913886
Mohon maaf sblmnya, banyak yang minta saya share wiring diagram nya. Bukan saya gak mau tapi gak bisa karena saya terikat regulasi perusahaaan tempat saya bekerja. Mohon maaf ya..🙏
@@saalila7395 On dan Off pompa 1 dan pompa 2 berdasarkan perubahan tekanan air yg dibaca oleh pressure switch , pergantiannya di atur oleh HSR dengan delay On dan Off selama 1 detik. Lamanya waktu delay tdk bisa dirubah / di setting karena sdh termasuk setting pabrikasi.
Walaupun ga bisa cara buatnya ini vidio yng paling sya suka dan selalu sya putar diselah kesibukan
Sukses trus abngq
Terima kasih untuk Support nya mas Ari..Semoga di lancarkan dan di permudah segala sesuatu nya buat mas Ari...Aamiin..!
Bagus om, suatu hari nanti Inhsa Allah akan saya praketakan untuk rumah anak saya tapi spek down lah, pompa transfer dan pompa booster yang pakai pompa sumur dangkal atau pompa semi jetpump, sekarang ini dirumah, instalasi listrik pompa saya pakai kontaktor, tiap hari mendengar suara jedak jedek walau pompa sumur dangkal. Mungkin 1 RT/RW di kampung saya, hanya saya yang pasang pompa 200 watt pakai kontaktor hehehehe WLC saya pakai tapi bukan pakai omron berkatoda om, tapi radar tapi seting konek B1 dan B2 (SUMP). saya suka otomatisasi, karena saya punya mesin dryer laundry buatan Bantul, otomatissinya isinya, selenoid gas, temperatur control, relay, timer H3CR, igniter, sensor flame, MCB, pilot lamp, sekering gelas .....seneng nambah ilmu sama
Wah..semoga nantinya bisa jadi inspirasi buat tetangga² anda ya pak..Ilmu pengetahuan itu mempermudah hidup..hehehe
Terima kasih pak penerangan nya ringkas tapi padat dengan ilmu.salam dari malaysia
Alhamdulillah...Semoga bermanfaat, salam untuk teman² dari Malaysia..!
Terima kasih sudah berbagi,mantap sekali ilmunya, profesional engineer.
Minta sarannya dimana posisi terbaik dari pressure tank dan pressure switch, bila instalasi plumbing tidak standard, sehingga di bagian terjauh dari pompa terjadi penurunan tekanan yang cukup besar.
Untuk menghindari drop pressure yg besar pada jaringan pipa tentu saja harus ada keseimbangan antara head dan kapasitas pompa dengan jaringan plumbing. Pressure tank dan pressure switch di posisi terbaik pun tidak akan banyak berpengaruh jika jaringan plumbingnya buruk karena loses nya pada pipa jaringan, bukan pada pompa. Contohnya ada di video test commisioning pompa booster, hasilnya jauh dari harapan.
@@HSPOMPA matur nuwun sekali, jelas dan gamblang penjelasannya 🙏
mantap master...trims ilmunya
Semoga bermanfaat...!
Mantap mas
Bagus pe nyampaianya , ada kah skema panel booster pump ini, kalau ada bolehkan bebagi untuk saya.
Wiring diagram nya sdh pernah saya upload , silahkan di cek playlist pompa booster untuk video dan link download nya saya cantumkan di deskripsi masing² video.
Terima kasih.
Alhamdulillah...Semoga Allah lancarkan dan luaskan rezeki nya...Aamiin..!
Mantap pak
Trimakasih ilmunya...boleh di buatkan wiring pake kontrol nya pak
Siap..! Ditunggu ya..
Terima kasih banyak Pak, peneranagan yang sunguh jelas, bagaimana saya bisa menghubugi bapak untuk mempelajarai nya dengan lebih lanjut, saya dari malaysia.
@@HSPOMPA salam pak ,saya dah cuba Whatsap tapi tak boleh, jika tak keberatan boleh bagi email pak', saya sangat meninati tutorial bapak ni.
@@AbuKassimMohdSaleh
Email : hspump75@gmail.com
IG : @herman270175
@@HSPOMPA terima kasih banyak pak.
@@AbuKassimMohdSaleh sama sama
Hello! Sir
Nice explanation.
Hello...thank you for your visit..!
@@HSPOMPA
Hello! Sir,
good morning
Thank you for your reply.
May i request you to know if you are a manufacturing company for the booster systems, if yes how do you control the panel for the moment?
We are a manufacturing company in India and for last 10 years we are manufacturing panels for booster and hydro-pneumatic systems.
we also manufacture dedicated controllers for this application, if you find it interesting i will be happy to share the details of the controller-HMI.
Thank you, hear you soon.
Regards
Abhijit
siddhaielectsys@hotmail.com
@@abhijitrashinkar Glad to know your interest ...but unfortunately my company is a small company and i'm just a technician who not familiar with HMI. My control panel is a conventional one with push button and pilot lamp for indicator. So..thank you for your offered..
@@HSPOMPA
No no Sir you got me wrong, the controller we manufacture are beyond your imagination and are very very cost effective, I request your email address only to share the details if you think interesting then you can think of the commercials, and to be honest the controller is of interest to a technical person, so it is my humble request to share your email address.
@@abhijitrashinkar Alright sir..here is my email.. hspump75@gmail.com
Izin tanya Pak, klo selektor switch auto manual di satukan dan di pisahkah kira2 dimana kelebihan dan kekurangan nya, Terimakasih
Sebenar nya hampir gak ada beda nya , hanya secara pribadi saya lebih suka di buat terpisah. Lebih mudah memilih mana yg difungsikan ketika di posisi manual.
@@HSPOMPA baik Pak, karena di lapangan banyak juga saya lihat selektor switch auto manual nya disatukan, terimakasih atas balasan nya, Salam sehat dan sukses selalu
@@syahdewanpurba Aamiin...
mau tanya pak . apakah bisa panel inventer boster di rubah tidak pakai inventer
Lebih baik buat baru pak..mau rubah juga hrs ada penambahan kontaktor, overload dan pressure switch.
bang bisa liaaat weringny tdk,skema panelny bang,saya mau coba buay
Download aja...wiring diagram nya sdh pernah saya upload video nya. Cari di playlist video wiring diagram , link download pdf nya ada di deskripsi video.
Is that indonesian language hope i can understand but not a single word,anyway its excellent Tutorials God bless
How could you said this tutorial is excellent if you can't understand not a single word of indonesian language...Hahaha...by the way, may i know where are you from?
@@HSPOMPA From philippines... i understand when you said the word contactor pressure switch, and i know you explained it what is the used and purposes of each parts
@@arielcunanan4994 I'd put english subtittle on this video...i hope it will help you a little bit to understand about how booster pump controller is work...
Mantab
Mohon arahannya
Misalkan kita setting boster pump menggunakan 3 buah pompa boster
Setelah sekian lama pemakaian ada trouble, yaitu
1.pompa nyalanya gak mau berhenti
2.pompa nyalanya cuma 1 pompa, saat mati dan hidup lagi cuma pompa no 1 trus, mati lagi dan hidup lagi, tp hanya pompa no 1 lagi yg hidup
3.settingan 3 pompa, akan tetapi mau kita rubah sementara menjadi 2 pompa yg kerja karena ada perbaikan pompa no. 3 , itu gmn pak
4.mohon share wiringnya pak
Mohon masukannya, Terima kasih semoga dilancarkan segala urusannya, dan semakin sukses
1. Pompa nyala gak mau berhenti itu sebabnya hanya karena titik setting Off gak tercapai. Sebabnya kapasitas pompa gak mencukupi dari banyaknya pemakaian.
2. Alternate pompa nya gak jalan , jadi gak bisa gantian.
3 & 4 . Cek playlist wiring diagram
1.titik setting pompa sudah mencapai titik setting max, tp tetep nyala terus menerus sampai mentok di preasure gauge masih gak mau mati???
2.alternative maksdnya gmn pak??? Atau hsrnya udah error??
@@davidprakoso7619 1. Oh klo itu pressure switch nya yg bermasalah , sdh sampai titik pressure tp gak mau lepas switch nya.
2. Bisa dari HSR , bisa juga dari komponen pendukung. HSR yg bagus itu tiap 10 menit pindah sendiri
Bang mau nanya pompa kan ad 2 pompa 1 sama pompa 2 setiap keran di nyalakan kluar airnya kdang keras kadang ngk setelah di teliti ternyata setiap giliran pompa 2 ngk mau saya pikir pompanya yg bermasalah setelah saya cek manual pompa 2 normal saya bingung apnya Kira2 bermaslah?
Pak klau pke ITL bsa kerja bergantian bgtu yah. Cra seting pressure switch gmna pak. Apa kah off nya set dua bar bgtu pla sett off nya misalnya di 1 bar
Mngkn bsa mnta wirringnya jga pak
Nggaknpakai plc atau smart relay pak?
Gak pake PLC pake nya HSR , konvensional tapi efektif.
@@HSPOMPA makasih pak atas penjelasannya soalnya temen saya yang lks soalnya tentang alternite juga
Om, mau tanya itu HSR2 yang tiger ke pompa?, yang HSR2 trigernya pressure swicth yang terpasang di pipa discharge kan? gitu om?
Iya benar..!
I need Booster pump electrical Diagram Wirning
Kalau mau pesan dibuatkan panel control booster pump seperti ini bisa ya?
Bisa..untuk info dan harga bisa hubungi :
👉 Tyo +6282123466269
👉 Yudi +6282112913886
Baik, terima kasih
Mantabs, Pak. Namun saya ada pertanyaan, Pak. Untuk pompa booster kan wajib pakai pressure tank untuk menghindari cetak cetok, nah tipe pressure tank-nya itu jenisnya apakah sama dengan fire pump, Pak ? & bagaimana pemilihan kapasitas dan pressure dari pressure tank tsb ? serta mungkin bisa dibuatkan tutorial menggunakan 3 pompa, Pak agar diketahui settingan di pressure switchnya. Terima ksh.
Hal² yang di tanyakan sdh saya pernah saya jelaskan, silahkan di cek :
th-cam.com/video/NTg6L5lsYz4/w-d-xo.html
th-cam.com/video/rCUZxL6uR7k/w-d-xo.html
@@HSPOMPA Ok. Tq, Pak
👍
Mas.. Klu bisa di sertai dgn wiring diagramnya... Terima ksh...
Cek playlist wiring diagram
Kalau ditambah inverter bisa gak?
Bisa
Om HSR CARA kerjanya seperti apa..?dan perlu di seting ga...?
Gak perlu setting..cara kerja nya liat video ini :
👉 th-cam.com/video/q9yKAGJi0Ag/w-d-xo.html
adakah penganti HSR yang sama cara kerjanya..? karna HSR mahal...trimakasih om...
@@hanunmamat7985 Klo perlu nya hanya bergantian kerja pompa , bisa pakai rangkaian 3 buah relay LY4 atau MY4. Bisa di lihat di video berikut :
👉 th-cam.com/video/EUhjMXDlCp0/w-d-xo.html
Boleh share system wiring control nya pak
Cek playlist wiring diagram
Wlc blum dikaitkn penjelasny dgn hss td pak..secara sistem .trimakasih.
Belum kah..? Secara singkat saya sebutkan fungsi kerja WLC hanya sebagai Safety ketersediaan air, hubungan nya dengan sistem hanya sebagai proteksi ada atau tidak ada nya air yang tersedia untuk pompa bisa berfungsi dengan aman..Semoga bermanfaat..!
Maaf bang pemula, mintakdiagram instalasinyapanel pompa boster ini bang🙏
Cek di playlist wiring diagram
Kalo tanpa HSR bisa gk om?
Parallel alternate tanpa HSR bisa saja , pakai komponen alternate yg lain semisal impulse relay atau latching relay dengan tambahan relay dan sistem wiring.
Bisa belajar wiring panel pump sama om gak???
Boleh...main aja ke workshop!
Workshopnya di mana pak.maksud sya jakarta mana?? Sya baru terjumpa chanel youtube bpk.bole bagi whatsupp bpk ngak.ada pt tempat sya bekerja suruh buat pump panel hydrant.dia paksa sya kuasai.padahal itu bukan bidang sya.terpaksa sya pelajari pump panel yg dia beli sya bongkar dan pelajari.sya bilang kalau mau mcm ini fotocopy seperti china bisa aja kita buat asal jgn component lain.relay pun seperti ini juga sya bilang.sya ini awam dgn relay.tq pak
@@sentosazr9084 workshop di Tambun Bekasi...cantumkan WA kamu, nanti saya hubungi.
Maaf, Pak. Bagaimana panel pompa booster paralel alternate ini mengetahui jika pompa 1 bekerja namun tidak kapasitas yang diingin tidak dipenuhi sehingga pompa 2 diperintahkan untuk jalan ? Sensor apa yang mendeteksi kekurangan kapasitas air yang dihasilkan pompa 1 ? Selain itu apa sebenarnya fungsi HSR 2 maupun G4Q tsb, apakah tidak cukup menggunakan timer model H3CR saat pindah ke pompa berikutnya ? Mohon pencerahannya ya, Pak. Terima Kasih.
Sensor deteksi sebenarnya lebih ke pressure, pressure drop berarti kapasitas drop juga dan ini tugas nya pressure switch untuk deteksi nya. Fungsi HSR dan G4Q lebih kepada kontrol starting kontaktor berdasarkan signal dari pressure switch. Klo H3CR itu TDR, jadi hidup nya pompa berdasarkan setting timer nya.
@@HSPOMPA Yes setuju, Pak. Yang pasti HSR maupun G4Q itu mempunyai KELEBIHAN lebih ketimbang H3CR yang hanya sebagai TDR. Tq, Pak.
@@GERAND.Flowmeter.Distributor sama sama
Kalau box panel booster ini sizenya brp, Pak ?
500 x 400 x 200 mm
Pak mau tanya apakah bisa pompa booster memakai relay G4Q dengan disistem kerjanya pararel alternate. Sedangkan yg saya tahu relay G4Q bekerja secara bergantian sebagai kontrol kontak pada kontraktor, sebelum dan sesudah nya saya ucapkan Terima kasih.
Bisa...tambah relay biar lebih safety. Video berikut contoh sederhana penggunaan G4Q untuk sistem parallel alternate : th-cam.com/video/Uzc6ssHnT4s/w-d-xo.html
Izin, Pak. Jika menggunakan MCB utama adalah 20A & MCB pompa I =10A & MCB pompa II = 10A juga masalah tidak ya, Pak ?
Gak masalah...20 A itu bisa untuk 5,5 kw , sedangkan 10 A untuk 2,2 kw.
@@HSPOMPA Waduh,,,berarti saya salah hitung, Pak. Tadinya saya pikir bisa untuk motor 3kW atau 4kW. Apa karena saya belum tambahkan besarnya MCB 1 phase yang 2A (rangkaian kontrol) ya, Pak ?
@@GERAND.Flowmeter.Distributor Nah...klo pake rumus cari Ampere, seharusnya 10 Ampere cukup buat 4 kw. Yang gak di perhitungkan itu lonjakan arus nya. Saya pakai 16 A untuk 4 kw karena MCB yg saya pakai itu type Domae, untuk pemakaian arus hubung singkat max. 4,5 kA. Untuk proteksi beban lebih kan ada TOR, lagi pula harga nya lebih murah..😁
@@HSPOMPA Hehe...A siaaap. Tq, Pak
@@GERAND.Flowmeter.Distributor sama sama
Jual gk om, yg speknya seperti ini,Klu Jual brapa om?🙏
Beda box panel doang...klo box panel ini pesanan orang. Ketebalan plat sama , beda warna cat dan kunci. Untuk info harga bisa hubungi :
👉 Tyo +6282123466269
👉 Yudi +6282112913886
Bang ada skema nya bagi dong
Sdh ada skema nya , cari di playlist wiring diagram. Link download pdf nya ada di deskripsi video.
Om, klo itu sistem itu dipakai untuk pompa celup/submersible bisa ga, dgn 3 unit pompa, 3phase
Sdh pasti bisa...tinggal ganti pressure switch dengan floating switch ( pelampung ).
@@HSPOMPA yup,,, Om bekasi ya,, panel maker bukan?
@@caturwahyudi1284 Workshop di Bekasi, saya cuma bisa rakit beberapa panel buat pompa...berlebihan klo di sebut panel maker :)
@@HSPOMPA hehe,, sama aja itu mah om, merakit panel juga panel maker
@@caturwahyudi1284 hehehe...
Hsr type itu kalau buat alternate 3 pompa bisa gak pak ...? Thank's
Bisa...HSR ada dua type HSR2 untuk 2 pompa dan HSR3 untuk 3 pompa
3 pompa berarti pressure switch nya harus tiga juga ya
@@harianggi8022 iya benar..
Ok pak terima kasih infonya, kalau dekat saya mau main ke work shop bapak. sayangnya saya jauh di Kalimantan.
@@harianggi8022 terima kasih ya sdh mau mampir..Semoga bermanfaat..!
Please sir gave me???
You can find it in wiring diagram playlist in this channel.
Ada contact person nya pa? 🙏
Ke IG aja ya..@Herman270175
Minta gambar wiring kabelnya bos
Wiring diagram sdh bisa di dowload, link nya ada di deskripsi.
Boleh izn share instalasinya pak
Saya ngin cba instal pak🙏
Mohon maaf sblmnya, banyak yang minta saya share wiring diagram nya. Bukan saya gak mau tapi gak bisa karena saya terikat regulasi perusahaaan tempat saya bekerja. Mohon maaf ya..🙏
@@HSPOMPA siap pak 86
terimakasih
Hsr hargax kisaran brp pak?
Harganya kisaran 500 - 600 ribuan
@@HSPOMPA hrs ni tinggal pakai ja sesuai wiringx, apa ada juga yg d setting?
@@saalila7395 tinggal pakai saja sesuai wiring.
@@HSPOMPA dalam pergantian nyala pompa 1 ke 2 dan sebalikx apa kaya sistem setelan timer at gmn ?
@@saalila7395 On dan Off pompa 1 dan pompa 2 berdasarkan perubahan tekanan air yg dibaca oleh pressure switch , pergantiannya di atur oleh HSR dengan delay On dan Off selama 1 detik. Lamanya waktu delay tdk bisa dirubah / di setting karena sdh termasuk setting pabrikasi.
Bang bagi wa nya dong biar bisa konsultasi kita
Bisa minta no CSnya ya
Tyo +6282123466269
Yudi +6282112913886
Pak,pliss wiringnya🙏
Ada kok....tapi berbayar 🙏
Cek playlist wiring diagram
Otomatis nya nama/seri apa bos?
Ke HSR2 dari Kael
Minta wiring diagram bisa bos? Saya pusing... Bukan ahli pompa, disuruh benerin pompa cetak cetek... 3phase 2pompa vertical di roof
@@KhAn-rj5bb periksa pressure tank nya...masalahnya di situ aja. Lihat video saya yg lain , sdh saya jelaskan..
Brother digram show viedo give
Check playlist wiring diagram
Brother give me your whatsup number . Im from Bangladesh .
@@HSPOMPA Don't have digram