How did we know when to reduce our duct size? ACCA Manual D

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 ส.ค. 2024
  • Understanding the procedure of reducing the size of an air duct based on sound principles, not rules of thumb. Proper Duct sizing, no rules of thumb.

ความคิดเห็น • 25

  • @thecurious6721
    @thecurious6721 หลายเดือนก่อน +1

    Thanks for the video, but if you posted a link to a video about branch run sizing it would be more helpful for us and your channel exposure.

  • @millenialmemoirs
    @millenialmemoirs 21 วันที่ผ่านมา

    I’m new to system/duct design, I’ve done a few dozen manual Ds over the last year, none of them I followed the book perfectly. There’s a lot of grey area in duct design. But I typically reduce when my calculated trunk velocity drops down about 30-40% and I’ve not had any major supply airflow or total static issues yet.

    • @edwardjanowiak
      @edwardjanowiak  20 วันที่ผ่านมา +1

      I believe the video follows what is in the manual. You can reduce (or never reduce for that matter) but your goal will always be to keep the velocity less then 900 FPM in the supply and 700 FPM in the return.

  • @gund89123
    @gund89123 3 หลายเดือนก่อน

    I am adding 800 sqft to my home (1,400 existing + 800 new).
    Got quotes from 5 contractors so far. They are telling I need to upgrade my furnace and AC.
    The recommendations range from 3 ton to 5 ton.

    • @tekjunkie28
      @tekjunkie28 หลายเดือนก่อน

      Are they doing a actual load calc? If not dont pick them.. Also Dont pick 1 unit to do it all. No house can use 5 Tons. Maybe 2 2 ton units but never 5 tons out of 1 unit

    • @millenialmemoirs
      @millenialmemoirs 21 วันที่ผ่านมา

      If you’re adding 800 square feet you’ll need an extra 1-2 tons depending on a variety of factors like age of the home, quality/r factor of insulation across the entire home and new space, etc. the comment above me saying “don’t go with someone who doesn’t do a load calc” is kind of ignorant. In my state, nobody is going a full load calc for residential changeouts unless it’s a 5000 sq foot mansion or new construction project. It’s too expensive and rules of thumb get us by just fine for small homes.

  • @ATeamAdam
    @ATeamAdam 3 ปีที่แล้ว +1

    Great video

  • @ParamountVideoTakes
    @ParamountVideoTakes 3 หลายเดือนก่อน

    Shouldn’t the size reduction be installed immediately after the 5th takeoff? I know that the sketch is not to scale, but the sketch shows it midway between the 5th and 6th takeoffs. It might be helpful to illustrate, or mention, that the transition can be placed a short distance after the 5th takeoff to save materials.

  • @SubZero-st3ct
    @SubZero-st3ct 10 หลายเดือนก่อน +1

    Hi Ed I have a few questions for you.
    1. After you reduced in the example.. won’t your last few runs “run out of velocity” on the end? (Just like when you took off your velocity dropped in the beginning?).
    2. Is it acceptable when using round pipe to reduce 4 sizes if need be? I.E. let’s just say that I started with a 16” round pipe and at half my velocity I needed to reduce to a 12” pipe. Would it be acceptable to put 2 reducers together and go from a 16” to a 12”? Thank you

    • @edwardjanowiak
      @edwardjanowiak  10 หลายเดือนก่อน +2

      Question 1. No. Velocity can not be to low in a branch run if you follow the guidance of Manual D. If CFM is correct the velocity if air going through the terminal box and grille is what we care about.
      Question 2. Yes. Manual D is about having enough fan pressure to overcome all pressure drops, having ducts large enough to not allow velocities to go above maximum values and using dampers to get the proper volume through branch runs. There are a few more but thay are my top 3.

    • @SubZero-st3ct
      @SubZero-st3ct 10 หลายเดือนก่อน

      @@edwardjanowiak thank you for your clarification.

  • @eduardkhachaturyan1189
    @eduardkhachaturyan1189 3 ปีที่แล้ว +1

    Question. Is it ok to reduce the duct work (let’s use your example) after we take first 3 branches, when the duct work is in unconditioned space to reduce the use of the materials and reduce the surface area of the duct work. So we can save few dollars on insulation and metal and also few BTUs?

    • @edwardjanowiak
      @edwardjanowiak  3 ปีที่แล้ว +2

      Eduard Khachaturyan yes, you can reduce the size as much as you want. Just make sure you keep your velocity under the maximum limit. My observations have been when people use rules of thumb to size ducts, they ignore velocity limits and we end up with an undesirable increase in static pressure.

  • @user-pd4jb7gv7n
    @user-pd4jb7gv7n 8 หลายเดือนก่อน

    Havent heard this stuff since Occ
    college..😅

  • @larryhoward4562
    @larryhoward4562 9 หลายเดือนก่อน

    Question: I have 17 feet of 6 inch duct supply to a room. After 17 feet, it elbows down and to the right, travels 2 feet straight, then elbows up and into a transition piece that feeds the room. Do I need to reduce the 6 inch to 4 inch OR simply get rid of the elbows and install a 45 set about 4 feet before the transition piece into the room?

  • @neoferatus
    @neoferatus ปีที่แล้ว

    Where can i downlad this paper calculator?

  • @nathanrothenberg8442
    @nathanrothenberg8442 3 ปีที่แล้ว

    Ed, what is it that we are supposed to calculate?

    • @edwardjanowiak
      @edwardjanowiak  3 ปีที่แล้ว

      When are we supposed to change the size of our ducts? I explained what the processes is based on the guidance of Manual D

  • @HVAC1116
    @HVAC1116 2 ปีที่แล้ว

    Should I reduce my return in size as well? Or keep it the same size the entire length

    • @edwardjanowiak
      @edwardjanowiak  2 ปีที่แล้ว +2

      It's your choice. The #1 rule to follow is whatever CFM volume you are moving through the duct (in that section) should not exceed the velocity limit as per table N3-1 Page N13 of ACCA Manual D (it says 700 FPM for a return duct). Lower velocity will never hurt your perforce, but it can impact your cost. I size my ducts following the conservative path listed in the table mentioned above. Check out ACCA.org, click on the education & events tab to see where I'm doing my next virtual or live training event.

  • @oscaro.rodriguez3217
    @oscaro.rodriguez3217 2 ปีที่แล้ว

    Hey if I put supply grills straight into duct 24x10 does the grill size let say 10x6 have the same cfm as say a 10x6 square duct not sure on how to size with grills going straight into trunk line thanks for any response

  • @stevendunnivant4048
    @stevendunnivant4048 2 ปีที่แล้ว

    What about a double plenum?
    Would it be:
    •@12’ on each side

    • @edwardjanowiak
      @edwardjanowiak  2 ปีที่แล้ว

      Nope

    • @joeybrazda364
      @joeybrazda364 หลายเดือนก่อน

      Friction rate would change since you’re likely changing the location of the furnace at that point.