I'm really sorry for my mistake🙏🙏🙏 ۔۔۔dear frainds is vidio me hamne .last me 16000 CFM ko 20 tr bataya hai...jo ki 40 tr hota hai...qki 400 CFM = 1 tr and 16000 CFM =40 tr ....🙏
But thank you so much to make such deep efforts to understand easily.... Please make more videos..... media used in ahu filters and their relevance . Plus make videos on dust collector, hydraulic filters, air compressed filters etc
Ji bilkul .. jaha tak hame knowledge hai ham wHa tak to bata sakte hai sabko ... Ye mera instagram id hai aap kabhi bhi questions kar sakte hai yaha par 👉 kgufran195
@@c4chiller9984 sir aap kaha the utna दिनों से मैंने आपको.बहुत याद kiya😢😢me ईस्ट.nhi chalata था aapke liye hi me Instagram chalu किया h par wo kisi our की id मिल रहीं h
This practical math formula goes a long way when you're considering air ventilation improvement in an indoor space: In air handling unit how to measure cfm... CFM = (fpm * area), where fpm is the feet per minute To find the cubic feet per minute, substitute the FPM value with the area after the area is squared. We have measured the cfm readings using anemometer.
you are right ...Ashutosh ji but it's simple way to calculate CFM other HVAC technician because it's Directly understanding in practically ...here I not use long furmula to mathematics
लास्ट में तो आप गलत बता दिए ना 20 टी आर गलत है 16000 सीएफएम है, 400 सीएफएम बराबर 1 टन 16000÷400=40 टी आर हुआ ना✓ आपका बताने का तरीका बहुत पसंद आया उसके लिए धन्यवाद
Agar man lijiye fcu unit ya kisi grill ka ka cfm lena hay sirji, toh uha pe agar inch may measurements aate hay, feet may nehi toh kaise nikalenge ek example deke bata denge toh achha hogi🙏 same rule rahegi ka?
Sir Cfm me average meter factor kya hota h total cfm ko plus kr k divide krne k bad average meter factors se multiple krenge kya Confused hu sir thoda btayea
Check kar sakte hai jii waha se bhi But hame return air Jo hamare ahu ya filter ke pass aati hai waha se hame poori proper air ki velocity milegi Yani ki poora CFM ham Le sakte hai ...
Ji ha bilkul ....TR ya phir CFM ek size ki tarah hota hai to har company ko size yani TR ko to dena hi padega ...ye ek masurment hai aor ha 400 CFM = 1 tr hota hai ....sukriya koi aor question ho to jarur batana
Wo depend karta hai ki apne ahu kitna use kiya hai.. Mtlb ki agar ek hi ahu use kareneg to 60 tr ka ahu hoga aor 3 ahu use karenge to 20 tr ke 3 ahu honge 60 tr ke ahu me around 12 filter tak hote hai 20 tr ke ahu me 4 ya Filter tak hote hai
iska matlab ye hai ki ek cubic feet me kitni air flow .. ho rahi hai ..jisse ki ham pata karte hai ki hamara ahu theek tarah se run ho raha hai ya nahi ya phir kahi duct me leak to nahi hai ....👉 aor hamne vidio me area nikalna bataya hua hai .....aap ek baar phir se chek kariye
Ji behtar tareeka ye hai ..ki agar Aap ke pass diploma ya iti hai to aap kisi facilities compani me 3 month tak as a assistant work kariye ..jisse ki apka develop hoga .. aor uske baad aap koi post le sakte hai ..👍
I see ur all vdo related to hvac systems and I am able to define all parts of its different different working in that system....sir u define each and every part by great understanding for others ...easily anybody can understand....thanks for ur helping in hvac field......actually I get interested after watching ur vdo ...... Sir how can find job .....
I'm really sorry for my mistake🙏🙏🙏 ۔۔۔dear frainds is vidio me hamne .last me 16000 CFM ko 20 tr bataya hai...jo ki 40 tr hota hai...qki 400 CFM = 1 tr and 16000 CFM =40 tr ....🙏
Koi baat nhi sir galti insan se hi hoti hai
Sir Diffuser Se Bhi CFM Nikalte Hai Na
Okk
@@mdarman8564 ji ha bilkul nikalte hai
To sir diffuser se cfm kaise nikalte hai
Bahut jyadaa pasand aayi video ❤️❤️❤️ love you bro
Awesome way to calculate the cfm , Great brother
Bahoot sukriya ji apka ..💐💐🙏
Great sir bahut bahtareen explanations ..
Bahoot sukriya apka
Very helpful vedio
Sach kahu to bhai aapka bataya hua ek baccha bhi samajh jaega. I mean your explanations way is too good. Thank bro.
Jald hi aapke 1k subscribe honge.
Bahoot sukriya ji apka ...ye sab apka hi support hai ji 🙏💐💐
V. Good ❤
Thank you 👍
Sir very easy badhiya samjhaya
Good job bhai gufran ...
Regards.
Ashutosh Sharma
thank you very much Ashutosh jii 🙏
Great 👍
Bhut ache se smjaya aapne sir thank u so much
Sukriya ji apka 💐🙏💐
You very great sir 👌🏻👍🏻👏
I very cherish you 👍🏻
bahoot Sukriya ji apka 🤗
Nice explanation
Very Good video Bhai..
Bahoot sukriya ji apka 💐🙏
Sir you have a good knowledge..and thanks for this video
Sukriya ji 💐
Good job sir
For best explain, thank you very much 😊.
🤗🤗
But thank you so much to make such deep efforts to understand easily....
Please make more videos..... media used in ahu filters and their relevance .
Plus make videos on dust collector, hydraulic filters, air compressed filters etc
i have already uploaded ahu filter and ...CO2 vidio 👍
link in description you can see
Aapke video se Hamen bahut Sikha .👍🏻💯
ji sukriya...🤗👍
Keep this thinking continue
Ji jrur sukriya apka
Sir ji aap ki video very useful hoti hai thanks 🙏🙏🙏
hamari taraf se bhi thanks 🤗👍
Nice 👍 videos sir aap ki videos good
thank you 👍
Excellently explained 👌
thank you 🤗....you are continue watching my vidio ... thank you very much 👍
Appreciate👍
sukriya ..ji apka 🙏
Sir bhut acha sa smja h sir ji m Puri raat aap ki hi video dekh reya ho nid bi nhi basa 1 phase ka Kam h mera phir bi bhut noliz mili
Ji bahoot sukriya apka 🤗
Thanks Bro you explain very well (Eng-Ahmed)
thank you for compliment 👍
Aapki video bahut kàam ki hoti hai bhai . Samjh me aa jaata hai
Ji sukriya apka 🙏💐
Very very nice 👍
Thanks brother nailed it keep it up
Sukriya ji apka 🤗
Outstanding
Sukriya ji apka 💐💐🙏
Very nice👍👏 sir ji sach me hamare jaise bacho ke liye mahan hai 🙏🙏🙏🙏 jaise aap ham bachi ka help kar rhe hai ji
Ji bilkul .. jaha tak hame knowledge hai ham wHa tak to bata sakte hai sabko ... Ye mera instagram id hai aap kabhi bhi questions kar sakte hai yaha par 👉 kgufran195
@@c4chiller9984 sir aap kaha the utna दिनों से मैंने आपको.बहुत याद kiya😢😢me ईस्ट.nhi chalata था aapke liye hi me Instagram chalu किया h par wo kisi our की id मिल रहीं h
Thank you sir
This practical math formula goes a long way when you're considering air ventilation improvement in an indoor space:
In air handling unit how to measure cfm...
CFM = (fpm * area), where fpm is the feet per minute
To find the cubic feet per minute, substitute the FPM value with the area after the area is squared.
We have measured the cfm readings using anemometer.
you are right ...Ashutosh ji
but it's simple way to calculate CFM other HVAC technician because it's Directly understanding in practically ...here I not use long furmula to mathematics
Bhai Dil jeet liya
thank you for supporting and loving 🤗🤗
I am also happy with this topic...
Thank you 👍
Ti wari now lucky whreanow???
VERY GOOD EXPLANATION.....EXCEPTIONAL EFFORT TO EXPLAIN THANKS
Thank you for compliment 💐
Ok bhaiyaji thanks
🤗👍
Nice video
Thank you
Keep making more videos
off cours...soon 👍
👍👍👍👍👍👍👍👍👍❤️❤️❤️
❤️❤️
Super bhai
Bahoot sukriya apka
Good 👍
Last me aapne tr Galt Kiya hai 40 tr hona chahiye
Very good explanation god bless you
Bahoot sukriya ji apka
Good morning do you have WhatsApp number
make one video on microprocessor how to operator how to troubleshoot in that
@@mubasheerahmed8227 its my instagram id 👍 kgufran195
@@mubasheerahmed8227 already maked your topic vidio please check on link
Good
👍
thanks ❤❤❤
Koi bat nahi prosee to seem he hy na sir😊
Jii ha process same hai 👍
Sukriya sir
Thank you so much sir
👍👍
लास्ट में तो आप गलत बता दिए ना 20 टी आर गलत है 16000 सीएफएम है,
400 सीएफएम बराबर 1 टन
16000÷400=40 टी आर हुआ ना✓
आपका बताने का तरीका बहुत पसंद आया उसके लिए धन्यवाद
ji ha wo calculation me hamse mistake Hui thi ....but hamne phir first comment me clear Kiya tha ...but thank you apka ki apne focus se vidio dekha 🙏🙏
🌹🌹🌹❤️❤️🌹🌹🌹
can you please explain about IKW & COP for chiller with examlpe,
Asalamo Alekum sir aap ye videos bahut acha tha per sir aap ne 16000 ko 1600 bola mistakes sir butsir aap ka ye videos very good sir
ji walaikum assalaam...
yes boss calculation me mistake Hui thi 🙏
Agar man lijiye fcu unit ya kisi grill ka ka cfm lena hay sirji, toh uha pe agar inch may measurements aate hay, feet may nehi toh kaise nikalenge ek example deke bata denge toh achha hogi🙏 same rule rahegi ka?
Sir
Please.
Condenser water pump, chilled water pump aur chiller ka changeover ka sop ke upar ek video banaye.
dost .
hamne SOP ke topic pe ek seperate video upload kiya hua hai description me link hai aap dekh sakte hai...👍
Indoor Package unit ke all electric part ke baare me bata dijiye
Ji time milega to ham jarur add kar denge sukriya
Samgh gaye sir🙏🏻🙏🏻
Ok jii 👍
I am also a BMS technician sir
good
Good bro ❤40 tr
Thanks ✌️
❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤
Thank you dost 👍👍
Great bro but hm ahu ko running condition me check Krna safe rahega kya 😒😒
ji ....CFM always running condition me hi nikala jata hai .....off condition me flow kaha se milega 🤗
Ok sir koi baat nhai ham sahi nikale the ❤
very good 👍
Sir air colled chiller ka video banaye
ji hamne banaya hai discription me link hai aap dekh sakte hai
Agar hum area ko inch me ya mm me lenge to koun sa formula lgega
Sir ap Kitna veido digiye ha a Dekker Mera bohot experience huya
thank you
Sir filter ke 5 jahag se air jaruri lena hai?
ji ha ...tabhi calculation proper ayegi
Bhai chiller me kaun sa expansion volve use hota hai
Maximum autometic expention valve ya centryfugal typ me orifes use hota hai jo gas ko nozeling karta hai
Bhai franite to centigred or centigred to franite nikal ne ka tarika dikho
Ji hamne already vidio upload ki hui hai hamne vidio ke neeche link diya hua hai aaap dekh lijiye
Sir Cfm me average meter factor kya hota h total cfm ko plus kr k divide krne k bad average meter factors se multiple krenge kya
Confused hu sir thoda btayea
ji ha dost ...jaisa apne bola approx vahi hai ....baki jaisa apne vidio me dekHa ...ye bilkul symple way hai CFM nikalne ka 👍
16000 ÷ 400 =40 Ton
Ji bilkul ...sahi hai apka
..hamse vidio me mistake se 20 tr bol diya tha uske liye sorry 🙏💐
Direct ham supply duct m laga kr chqu nahe kr saktey ..
Check kar sakte hai jii waha se bhi
But hame return air Jo hamare ahu ya filter ke pass aati hai waha se hame poori proper air ki velocity milegi Yani ki poora CFM ham Le sakte hai ...
Last Mai 16000 ki jaga 1600 bola sir g
sabhi company ke AHU ka TR seme hi hota h kya
Ji ha bilkul ....TR ya phir CFM ek size ki tarah hota hai to har company ko size yani TR ko to dena hi padega ...ye ek masurment hai aor ha 400 CFM = 1 tr hota hai ....sukriya koi aor question ho to jarur batana
By brother cfm 16000 divided by400 will be40 if im not wrong
you are right dear .....👍 its my mistake calculation time ....🙏
Sir ye to bata diya magar duct se kaise milayege pura video dikhaiye
CFM calculation ke bad kya Sare system ka tonage malum hota hai ya fir only AHU ka
Only ahu ka
@@c4chiller9984 Sar FIR compresser ka tanishk Kaise Pata Karenge ki kitne tan ka compresser hai
Cooling capacity se
3.5 kW= 1 tr
Sir cfm nikal ne ke total kitne tariqe h hum log dusre tariqe se nikalte h
Thnks for explain but end time calculate mistake 40 tr is answer 🙂
Ji you are right ... 👍
Wo meri mistake thi .. 40 tr is right
Air ki speed kitni honi chahiye sir. Or kita CFM ayega k hm samjhenge k sab thik hai
dost ...jitne CFM ka apka ahu hoga usse thoda sa jyada CFM ana chaiyye to ..
samjh jaao air flow sahi hai 👍
Sab Samaj Aya Lakin 16000 k bad ni Samaj I 😢😢😢
ahu tr calculation/formula sir ???
Bhai meter me velosity set krni hoti h jese 10 15 20 usse bhi to multiply krna hota h wo to aapne kiya hi nahi
Ji ha 10 karni padti hai qki kuch anemometer alag alag hote hai .. subme setting rahti hai .. but apko
F/m me check karna hoga
20tr kaise hoga ,40 tr hoga n, division krne pr 400 se 16000 ko
Mai bhi usi confusion me hoo
Pura area ka secore se multiple karenge
jii ha ...har filter ka square nikalna hai apko 👍
Agr ek room me cooling jyda ho rha hai aur fcu lga huwa hai to kaise sahi krenge
thermostat se kam kardo ....
Air balancing kaise nikalte hai
VAV ko adjust karke 👍
Chiller to secondry&primary pump control show me
Bhai 400 cfm 1tr 16000 se divide karege to 40 tr a raha hai bro ek video bnaye kitne tr ahu ka kitna cfm hona chaheye
ji Ha dost apka calculation right hai 40 tr hi ayega....maine mistake se 16 tr bataya tha ..but wo 40 tr hoga 👍
Sir 16000 dive by 400 is equal to 40 Tr. Please check. And you are saying 20 Tr.
ji ha you are right 👍
I'm already checked....and clear that in first comment
Cfm ka full form cubic feet mint hoga sir
Very good 👍
Sir eska koi farmula hota hai CFM nikalne ka
Sir 70tr ke cooling tower me kitne number of filter rahta hai???
Ji Cooling tower me filter nahi hote
Aapka questions kya hai ??
@@c4chiller9984 sir chiller agar 60tr ka hai to AHU me kitne number of filter lga hota hai
Wo depend karta hai ki apne ahu kitna use kiya hai..
Mtlb ki agar ek hi ahu use kareneg to 60 tr ka ahu hoga aor 3 ahu use karenge to 20 tr ke 3 ahu honge
60 tr ke ahu me around 12 filter tak hote hai
20 tr ke ahu me 4 ya Filter tak hote hai
40TR
ji ha 40 tr hoga ... by mistake se hamne 20 tr bataya sorry
Some time ahu size is small and we don't have more space to entering ahu .then how will get
check the CFM from near return air grill in cooling area or supply air grill ..
@@c4chiller9984 its not possible bro. its in open area height is 6 meters .and there are using fabric duct
Sir Ahu par dps switch lage hote h uske upar video banou please
Aapka video 5 bar dekha confiuse tha ki kaise 20 tr aaya
Really sorry ji
Ji hamne is vidio me 40 tr ko 20 tr mistake se bata diya tha but description me hamne add kar diya tha ji ....
Cfm फुल फॉर्म क्यूबिक फीत पर मिनट है तो इसका मतलब बताएं और एरिया कैसे निकाला जाता है इसके बारे में बताएं
iska matlab ye hai ki ek cubic feet me kitni air flow .. ho rahi hai ..jisse ki ham pata karte hai ki hamara ahu theek tarah se run ho raha hai ya nahi ya phir kahi duct me leak to nahi hai ....👉 aor hamne vidio me area nikalna bataya hua hai .....aap ek baar phir se chek kariye
Agr CFM kam aega to kya krenge sir🤔ya jyada bhi aa skta h kya?
1.Moter aor blower ki speed check karo
2. Duct chcek karo kahi se leak to nahi hai ..
Jyada aaye cfm aaye to koi problem nahi
@@c4chiller9984 thnx sir for reply 👌
Bro chilar DC se chalta hai ya Ac
Ac to dc to ac ...pahe ac ko dc banata hai aor phir use dc ko ac banata hai ....chalta ac me hi but dc hone ke baad
Jaise apka inverter kaam karta hai ..usi tarah chiller me VSD drive hoti hai jo kaam karti hai ..
Sab din reading hi leta tha aur harame supervisor CFM nikalte the lekin ab hum bhi nikal lengey
bilkul nikaloge aap🤗 ... aor jo doubts ho wo pooch lena 👍
@@c4chiller9984 jii bilkul
Koi accha training institute ka pta btyega jaha practical krwaya jata hai aur placement bhi
Ji behtar tareeka ye hai ..ki agar
Aap ke pass diploma ya iti hai to aap kisi facilities compani me 3 month tak as a assistant work kariye ..jisse ki apka develop hoga .. aor uske baad aap koi post le sakte hai ..👍
@@c4chiller9984 B.tech from Mechanical.....I have just completed but not able to get any job as yet ......please help if u can ....
I see ur all vdo related to hvac systems and I am able to define all parts of its different different working in that system....sir u define each and every part by great understanding for others ...easily anybody can understand....thanks for ur helping in hvac field......actually I get interested after watching ur vdo ......
Sir how can find job .....