1 hp 20 stage sumbersible ke liye kitne mm ka wire lena padega sir 400 feet gehrai tak le jana hai
Sir mera 10 hp ka masala pisne wala machine hai or 3 phase ka connection hai main usme kitne mm ka wire use kar sakta hu
Sir hamara u
7.5hp ka agro ka motor he to usko konsi motor cable use kare light 3 phase he
Agar acha or paisa lga hi rahe hai sir to 6 mm warna 4 mm bhi aap use kar sakte hai
@@Easy_fit2 hp water pump ke liye best wire copper or Aluminium??
Distance 100 metar from electric connection.
Reply
Sir, Mere Yha 2Hp ki submersible moter hai( Oil filled), or 3 Phase ka Light connection Liya huva hai, Toh uske liye Muje kitne mm ka wire Lena hoga ? Please Reply sir
Meko , keval boring se Main light Tak ki cabel ki jankari chahiye hai sir ji( boring se Ghar ki main switch ki duri 50 feet h) ? Mere Ghar pr sir ji , unhone , Boring ki cabel na dalte huve , unhone Ghar ki light fitting k wire dal diye h , jisse proper current nhi mil pa rha h ,or uski Distance 50 feet h, Toh uska solution kya ho skta hai sir .... please bataiye kuch
खंबा से लेकर खेत तक 1000 फीट है तो 2 एफी मोटर को कितना एमएम तार लगेगा
Mera 3 hp ka motor hai jo 100 feet me laga hai (three phase) mujhe kitne mm ka cable use krna chahiye?
1 hp submersible hai 250 feet se pani uthana hai kitna mm ka cable lagayenge??
Bhai 3hp motor hai aur 25 ka pump hai ,, borewell ki gahrai 400 feet hai uska bar bar tar jl jata hai usme 2.5 mm ki cable hai devidayal ki,,,,,koi solution btao bhai
Galat taar nagaya hai bhai aapne
Aapko 4 mm ka taar use karna hota hai 3 hp me or koi acha ka company wala hi use kijiye ga par 4 mm hona to ekdum jaruri hai
Comment ke liye thank you 🙏
1 hp moter lagi hai new summersable lagwaya hai 5 din pahle 2.5 mm crompton ki cable lagi hai moter pani to full de rhi hai par cable heat ho rhi hai kya karan ho sakta hai.
Sahi gauge ka wire nahi hoga warna 1 hp ka submersible me 2.5 mm ka wire aaram chalta hai
Sir meri three fase ki kab ki motor hai 17.5 ki konsi wire Li Jaye Jo best ho quality achi ho
Thank you for comment 🙏
Falcon ka ya cri ya kiran or poin yeah sab maine use kiya hai best kab hai
Sir mera motor 18hp ki he usme dp se bor tak kitne mm ka tar lagega taki bo acha pani de 550fit pe motor he
Vai 3inch borwell ma konsa motor lagaga 50 fit ha bor
Agar 3/4 hp ka submersible mile to thik warna V3 1 hp 10 stage aaram se mil jayega aaap lagwa sakte hai
@@Easy_fit 2 hp water pump ke liye best wire copper or Aluminium??
Distance 100 metar from electric connection.
Reply
भाई मेरे घर में 1 hp का सबमर्सिबल पंप है एंकर का 1.5 mm का तार लगा है दो दो बार तार जल गई जबकि जॉइंट्स हर जगह टाइट है तार की दूरी मैं बोर्ड से 40 45 फीट है कुछ बताओ
@@Easy_fit अभी आज ही जल गया है अब 2.5 या 4 mm का डालूंगा
सर एक बात और बताओ मेरे इधर के दुकानदार HPL कंपनी का वायर को अच्छा बता कर बेच रहे है क्या HPL वायर सच में अच्छी होती है?
Sorry for late reply
Brand hpl ho ya ipl
Cable ko aapko khud se cheak karna hoga or brand list me nhi hai
Cheak karne liye aap cable ko chil ke uska gauge ka quality and quantity dono dhyaan se samjh ke le sakte hai or agar cable cri ka ho ya falcon ya kiran cable ya point cable to aap le sakte hai yeah sab achi company he
5 hp 3 face ka hai 130 fit me laga hai har sal moter jal jata hai, mujhe bhi laga wire change kar de, please bataye wire kitna mm ka lagaye
Kam se kam 6 mm to aapko use karna hi chahie
Phir bhi jal jaa raha hai kya ??
Mera single phase 1.5hp submersible pump hai, wire 1.5mm ka laga hai ,amp. 11-13 show karta hai sahi hai ya galat hai.please suggest me
सर जी, हमारा बोअरवेल 510 फीट हैं, ओर मोटर 450 फीट पर है, 5.25 की मोटर हैं, केबल 2.5 mm का हैं, पर पाणी कम मार रही है... प्लीज सर इलाज बताओ
Sir mere paas 3 hp v6 submrcibul ka motor hai 80-90 fit gaharai hai to konsa kebal sahi rahega
Agar local wire use kar rhe hai to 6 mm aur branded me 4 mm use kar sakte hai
3,h p ki motar ki kedal honi chaiye
Aapka sawal hai ache se samjh nhi paye phir bhi jawab de rahe hai hum aapko
Ki 3 hp motor ke liye 4 mm ka cable lagega chahiye
Sir , Meko Borwell se Ghar tak k liye Kitne Mm ka wire lena hoga ( borwell s ghar tak ki distance 50 feet hai? Mere Yaha borwell s Ghar k main switch tak Ghar k light fitting k wire dal rakhe hai , jo Boring load nhi le pa rahi h toh ,me borwell s ghar tak k liye wire change krna chatta hu , or me vahi wire use krne ki soch rha hu , jo mene Borwell ki machine k sath fit kiye hai...toh sir aapse suggestions chahiye hai , ki is situation m muje kya krna chahiye???? Please Reply sir , badi samasya m hu
AAP kitne hp ka submersible use kar rahe hai ??
Or poll se ghar ke liye kitna mm ka service wire kiye hai avi ???
@@Easy_fit sir, 2Hp ki Moter use kr rha hu or 3 Phase ka connection le rakha hai Ghar m, 5kv ki capacity hai Ghar ki...
3 hp summer subal kitna 7 mm ka tar chal ja ga
350 feet borwell ke liye kon see pump lena chahiye
Sorry sir for late reply 1.5 hp ka cri company ka aaap le sakte ho warna texmo ka ka machine
2.5 Hp ke submersible pump me 120 ft gehrai par kitne mm ki wire use karein
@@aaravaggarwal3283 mujhe lga tha aap 2hp ko 2.5 hp bol rahe hai kyuki 2.5 hp nahi aata hai
1.5 hp ke liye 2.5 mm use kijiye
@@Easy_fit sir paras company ki wire kaisi rahegi.. hardware wala bol raha hai 4Mm laga lo
Sir mere ghar me 6.5 inch ka bor hai jo 400 feet par pani hai or total 480hai to sir hum kitne hp or kitne stage ki moter lu batao
400 feet niche se suru hai or total bor 480 feet Mtlb sirf 80 feet bor me pani hai ???
Sir, 15 HP k liye best cable konsi rahegi.
@@Easy_fit Sir, hmara pump 200mtr below ground hai. Can you give best quality cable name, Please🙏
Sir Mera submersible motor 1hp ka hain .....par motor chalanepe panel board mai 220 volt 7 ampere dikhata hai toh ye lagbhag 2hp show Kar Rahe Hai....kiya load lenepe wattage jyada khati hai ya motor mai problem hai ....motor 1hp ka hai 3 inch .....bore well bhi 3 inch ka hai .....100 feet niche motor set hai ....total head motor ka 160 feet hain ....aur wire 2.5 mm ka laga huwa hai ....lekin 1hp motor hai toh 2 hp kiyu bijli khata hai ...lagbhag 1500 watts tak chala jata hai .....kiya ye common problem hain ....
Thank you for your comment
Sir sirf motor Ko Bina lord ke chaiye ga to 4 amp leta hai ok jab boring me dal dijiye ga to motor ke sath pump ka lord or Pani ka lord se 6.5 ya 7 amp bta Raha hoga jo 100% thik hai don't worry 🙂
3 hp सम्बलसिबल चलाने के लिए कितनी mm ki केबल लगे गा,, Tc connection se lena hai 400 meter duri hai पोल की ,,Tc connection ke liye chahiye केबल
@@VikasKumar-zd9zotransformer se aapke borewell takk 3 phase line pahuch huwa ??
Sir 1hp ki मोटर समर में कितने केवल लगानी चाहिए
Sir Samar ke bahar jo cell hota h vha se wire ke taar pighal jate h 8/10 days ke baad
@@Easy_fit 4mm ka kr rkha h tab bhi taar pighal jaate h cell pas se
Sir aap kis cell ki baat kar rahe hai aap please ache se bataiye takki mai aapki help kar saku
300 feet andar 1.5 hp 19 stage cri pump me kitna mm tar or kis company ka lagana chahiye
खंबा से लेकर खेत तक 1000 फीट है तो 2 एचपी मोटर चलाने के लिए कितना एमएम तार लगेगा
Sir 3 hp borewell ke liye kitna mm ka wire lagega 700 miter duri ke liye
370 feet borewell aur 1hp motor ke liye kitna mm ki wire konsi wire sahi rahega
@@Easy_fit knoledge nhi hai aapko bekar me video banaye ho 3 mm ka wire laga hai phir bhi Pani thoda thoda de Raha hai
3mm ka kon si wire laga liye h jo pani nhi de raha aluminium wire h kya motor voltage aur ampere kitna bata raha h ?
@@CgExam-xr9no 3 mm ka wire aata to nahi hai bhaiya aap 10 mm lga dijiye meri na maniye apna maan ke 10 mm ya 20 mm lga dijiye
Sir namaskar. 260 ft ke liye kitne hp ki motor chahiye ghar ke liye aur isme kitne mm ka wire chahiye
Namaste 🙏 1 hp 13 stage ya 1.5 hp 15 stage dono me se kisi ko lga sakte hai 2.5 mm wire aap use kar sakte hai aaram se
Sir 2 hp ka submersible lena h uske liye 4mm ka wire lagaye ya 6 mm ka
15 hp me kitne ki cable lgegi
Mujhe main line se 250 meter dur 1.5hp ka samarsewal pump chalana hai kon kitna mm ka wire jaruri padega?
Best