  • @senaidklokicc9944
    @senaidklokicc9944 10 หลายเดือนก่อน

    Do this valve need instrumental air suply ?

  • @TonyStarkSpearfishing
    @TonyStarkSpearfishing 4 ปีที่แล้ว

    Please make upload a video tutorial for PRV with DOROT 31-310 pilot.

    • @rizzimatheu
      @rizzimatheu 3 ปีที่แล้ว

      Hi Wilfredo. Pilot used in demonstration is 3 way, similar 31-310; (both 3w). Is the same procedure.

  • @ceversonaspen
    @ceversonaspen 9 ปีที่แล้ว

    Q: The step about verifying a minimal downstream demand which occurs at 1:50, is this done to prevent chatter or flutter at low flow? I have a situation where my team is being told we need to install low flow bypass in numerous valves (which happen to not be Dorot valves), and I am wondering if making sure this step is performed in commissioning might help avoid the need to do so?

    • @izharbahir8485
      @izharbahir8485 9 ปีที่แล้ว

      +c_e , the purpose for this step is to calibrate the set point. once the set point achieved, downstream isolation valve can be opened.
      there is no need of a bypass in dorot valves as they work close to zero flow without chattering (as declared on dorot's catalogue - please check with S300 electronic catalogue that can be downloaded for free from dorot website.

    • @rizzimatheu
      @rizzimatheu 3 ปีที่แล้ว

      I'm not sure to understand your question.
      Anyway, all S300 Dorot valves (model 30 - 31 - 32) has sealing disc with LTP (r) system.
      It´s allow regulate with very low flow, near 0 (zero flow).
      It´s one of Dorot´s valve strenghts.
      Pressure reducing station installed with VRP S300 Dorot doesn´t need by-pass to low flow.
      Eventually, by-pass is installed with mechanical valve (butterfly , gate, etc), used just during pipeline filling or maintenance period.

  • @fernandovergara3119
    @fernandovergara3119 ปีที่แล้ว