  • @wat3rdog25
    @wat3rdog25 5 ปีที่แล้ว +1

    I really love having braided hose vs a hard stainless tube that can be a pain to deal with.

  • @v6cosworth167
    @v6cosworth167 5 ปีที่แล้ว

    What would you do if your outlet preasure is the same as the inlet (fully open) what would cause that?

    • @dieterfunkhauser6319
      @dieterfunkhauser6319  5 ปีที่แล้ว +1

      V6 Cosworth, outlet pressure = inlet pressure usually means there is no flow across the valve. These valves are meant to work only whole flowing. If there is flow and the valve is not regulating, then check the pilot set point, check for pilot system leakage, or the main valve itself could have an issue. I’d recommend contacting your local rep for troubleshooting.

  • @hiwaabdulrazaq7920
    @hiwaabdulrazaq7920 4 ปีที่แล้ว

    Thanks

  • @Davidsavage8008
    @Davidsavage8008 ปีที่แล้ว

    To many chanses to break the system installing so many 1/4 " apendages that when flaking out the hoses in the catwalk catch on.