  • How to reset parameters of ASDA-B2 Delta AC-Servo Drive, back to Factory default.

ความคิดเห็น • 15

  • @qutubkhan8113
    @qutubkhan8113 ปีที่แล้ว

    Do you Know Drive Working Speed setings

  • @sanjeevsai1332
    @sanjeevsai1332 ปีที่แล้ว

    Please send position mode wiring details

  • @eduardoflores5945
    @eduardoflores5945 ปีที่แล้ว

    AL025?

  • @bouhlelaymen3885
    @bouhlelaymen3885 2 ปีที่แล้ว

    please Do you know the solution for alarm 009?

    • @yapselectro2946
      @yapselectro2946  2 ปีที่แล้ว

      Sorry for late reply,
      AL009: Excessive deviation of Position Command
      Causes Checking Method Corrective Actions
      Parameter P2-35 is set too small
      Check the setting value of parameter
      P2-35 (The warning condition of excessive position deviation).
      Increase the setting value of P2-35 (The warning condition of excessive position deviation).
      The setting of the gain value is too small.
      Check if the setting value is appropriate.
      Correctly adjust the gain value.
      The torque limit is too low. Check the torque limit value. Correctly adjust the torque limit value.
      Excessive external load Check the external load.
      Reduce the external load or evaluate the motor capacity again.

  • @hamara4457
    @hamara4457 3 ปีที่แล้ว

    Do you know the solution for alarm 009?

    • @yapselectro2946
      @yapselectro2946  2 ปีที่แล้ว

      Sorry for late reply,
      AL009: Excessive deviation of Position Command
      Causes Checking Method Corrective Actions
      Parameter P2-35 is set too small
      Check the setting value of parameter
      P2-35 (The warning condition of excessive position deviation).
      Increase the setting value of P2-35 (The warning condition of excessive position deviation).
      The setting of the gain value is too small.
      Check if the setting value is appropriate.
      Correctly adjust the gain value.
      The torque limit is too low. Check the torque limit value. Correctly adjust the torque limit value.
      Excessive external load Check the external load.
      Reduce the external load or evaluate the motor capacity again.

    • @qutubkhan8113
      @qutubkhan8113 ปีที่แล้ว

      Please AL.009 Discuss and Connecting Wiring Image

  • @kostasvasiliou8290
    @kostasvasiliou8290 2 ปีที่แล้ว

    Do you know the solution for al022?

    • @yapselectro2946
      @yapselectro2946  2 ปีที่แล้ว

      Sorry for late reply,
      AL022 Main circuit power lack phase:
      Check if RST power cable is loose or does not connect to the power. This alarm occurs when no power connects to single phase servo drive.

    • @qutubkhan8113
      @qutubkhan8113 ปีที่แล้ว

      Please Contact CN1 Wiring Image

  • @juanlezama7930
    @juanlezama7930 2 ปีที่แล้ว

    Please solution Al009

  • @atulram3111
    @atulram3111 3 ปีที่แล้ว

    Al.o11 ka alarms kese remove hoga

  • @leandrootavio1409
    @leandrootavio1409 2 ปีที่แล้ว

    P2 - 08 = 10