Measuring Total External Static Pressure

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ต.ค. 2024

ความคิดเห็น • 97

  • @jonwiersig5800
    @jonwiersig5800 8 หลายเดือนก่อน

    Great video. Clear detailed explanation and example of where to measure static pressure. As an engineer, I was impressed with your use of fan laws for pressure drop. Great job!

  • @robertstinnett4266
    @robertstinnett4266 11 หลายเดือนก่อน

    Thank you sir! I train service and start up techs. I am going to make this video a requirement. Most techs do not even consider or think of static pressure. This definitely shows how important it is.

  • @dissociativecat7495
    @dissociativecat7495 ปีที่แล้ว

    this is one of the best videos I've found about this subject

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว +1

    They are perfect for that as long as the hole in the inner wall is sealed with high temperature RTV. You can easily remove the plug the following year for testing. When you say "rated" however, there are no ratings for any type of sealant for b-vent that I know of. We do however have copies of letters from all of the major b-vent manufacturers on how the hole is to be sealed. You can email us or call us and we can get them to you via email if you need them.

  • @garysmith10449
    @garysmith10449 11 ปีที่แล้ว +2

    You have a great way of explaining things you need to keep adding more videos ASAP

  • @hvac5646
    @hvac5646 11 ปีที่แล้ว +4

    Thanks. That was very informative.
    You put the static tip pointing up (with air flow) in blower section.
    In the diagram it is in blower section, reversed, pointing AGAINST air flow.
    Please clarify.

  • @karlxmas
    @karlxmas 5 ปีที่แล้ว +16

    11:42 - "Awwww Shit"- Pause..... then carries on. AWESOME!

  • @HBSuccess
    @HBSuccess 4 ปีที่แล้ว +3

    One nice thing you can do is use a perm magnet on the cabinet or plenum just below where you’re drilling to catch the drill filings when making the test holes.

  • @chrissipple1018
    @chrissipple1018 ปีที่แล้ว +1

    One thing that might help is to cut a small piece of sheet metal and drill a hole in it and then tape it over the limit opening. you will have a removable port for static pressure readings. Also you can not suck or draw pressure you can only push it by the pressure difference.

  • @BouncyThrone
    @BouncyThrone 5 ปีที่แล้ว

    I may be missing something, but aren't y'all in the business of actually selling meters, devices, tools, and equipment to tradesmen and the like? If so, I'm impressed. I can't tell you how often I've attempted to consult and extract info from a seller only to find they are completely clueless of the products they're selling. So this is refreshing..
    Not sure what happened at the 11:40 mark, but this was a great tutorial..
    I recently grabbed that Testo 510 to upgrade from my analog. It seems very accurate and stable, but I can't help wonder how durable it's going to be. It literally reminded me of one of those child's play plastic cell phones when I first handled it.. perhaps I just equate weight with quality, and next to my fluke with that big yellow cover, it just doesn't feel quite as durable, but perhaps and hopefully I'm missing something, and it will prove to be a great asset..
    With all the choices you have a hand, I'm guessing you like it if it's the one you chose for this video..

  • @HVACShopTalk
    @HVACShopTalk 11 ปีที่แล้ว +1

    Very good instructional video. Most of the systems I check are well above the recommended static pressure. I like the steel plugs- I am headed to trutech now for those. Good job.

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว +1

    The static pressure tip minimizes the impact of velocity pressure and turbulence in the duct providing a more accurate measurement. In a perfect world you could hold the tube at the face and read static, in actual application a static pressure tip is always recommended.

  • @munawarsoomro6207
    @munawarsoomro6207 4 ปีที่แล้ว

    Very nice video thanks. I haven't found a video where one can make airflow measurements with hot wire given supply taps generally come few inches off of the duct connection to evaporator coil.

  • @willpartin622
    @willpartin622 ปีที่แล้ว

    Thank you for all your great vids.
    I was wondering if you can ever have too much return ducting.
    After watching your videos, I checked my external static and found 3.5 and 3.5 for a total of 7 in WC .
    Filter drop is .18 INWC ( 5 inch air bear) and a\c coil drop is .21INWC. ( 2.5 ton N coil.)
    The temp rise is 70 degrees in heat mode. Rheem says 40-70 rise is okay , so I'm at the high end of acceptable . Shooting for 55 degree rise.
    I'm thinking I might need more returns and supplies but don't want to over duct it. Any help or advice? Also, when is was installed they added one 10' and one 8 inch flexible return duct.
    this is a 70,000 BTU Rheem 95% that replaced a 115,000 Ruud 95% furnace. Thank you
    Reply
    Thank you for this vid
    I was wondering if you can ever have too much return ducting.
    After watching your videos, I checked my external static and found 3.5 and 3.5 for a total of 7 in WC .
    Filter drop is .18 INWC ( 5 inch air bear) and a\c coil drop is .21INWC. ( 2.5 ton N coil.)
    The temp rise is 70 degrees in heat mode. Rheem says 40-70 rise is okay , so I'm at the high end of acceptable . Shooting for 55 degree rise.
    I'm thinking I might need more returns and supplies but don't want to over duct it. Any help or advice? Also, when is was installed they added one 10' and one 8 inch flexible return duct.
    this is a 70,000 BTU Rheem 95% that replaced a 115,000 Ruud 95% furnace. Thank you
    Reply

  • @gwengreer3633
    @gwengreer3633 10 ปีที่แล้ว

    Very good teaching on The Measuring Total Estatic Pressure. Gwendolyn Greer

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว +4

    Your installer should verify that the actual static pressures fall within the design range of the appliance and follow all of the manufacturer start up instructions/requirements included with the furnace.

    • @xposed11
      @xposed11 4 ปีที่แล้ว

      th-cam.com/video/k5GcI6cbL-U/w-d-xo.html Fucking lul my dudes...fucking lul.

  • @sam111880
    @sam111880 8 ปีที่แล้ว

    great video on the understanding of how to uses digital anemometer to determine in-WC or in-Hg for you ac and heating system. But curious do you ever measure combustion chamber pressure to determine clogs or other obstructions in the combustion chamber not just for the return /supply vents. I would imagine you never want to drill into combustion because now you have CO possible issues in the future for aging systems. However maybe pulling off and using where the pressure switch goes into is one way.

  • @soloch69
    @soloch69 ปีที่แล้ว +1

    Love the video thank you for all the great helpful information keep them great videos coming 👍🏻

  • @dpeagles
    @dpeagles 11 ปีที่แล้ว

    One of the best explanations I have seen.

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว

    You could, I am not a big fan of operating the furnace even temporarily without the limit, but I am a little conservative in that manner. However you make the measurement thought remember to test the appliance with the highest airflow requirement.

  • @ChrisHVACguy
    @ChrisHVACguy 10 ปีที่แล้ว +2

    Do the heat exchangers have a pressure drop? If so I would imagine that pressure drop is counted for in the max esp on data plate? Now most limit switches are in between the heat exchangers not downstream, so if you measure esp there, aren't you going to get a reading that's a little higher because your not counting for 100% of heat exchanger pressure drop?

  • @NoneFB
    @NoneFB 2 ปีที่แล้ว +1

    I liked that 3D sketch of thee pitot tube. I’ve never seen that before.

  • @biblebloopers946
    @biblebloopers946 2 ปีที่แล้ว

    Your tip is supposed to go in the direction against the air flow. So if the airflow is flowing up then you want to point your tip down.
    Am i wrong?

  • @goosecouple
    @goosecouple 11 ปีที่แล้ว +1

    Hi, why is it necessary to do measure external static pressures? Is it a usual required measurement to be made in new installations? I have new system being installed, should I tell the installer to make these measurements? Thx.

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว

    It does not matter what way the tip points (up or down) as long as the shaft is parallel to the flow. What you do not want is the velocity pressure to influence the reading by impacting the pressure sensing ports.

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว +1

    Thank-you all for the positive comments.

  • @804PMatt
    @804PMatt 11 ปีที่แล้ว

    Jim. Love your videos. Question. My company will not supply steel caps. Only plastic. Is it ok to remove the limit and just use some tape around your pitot tubes temporarily to get the readings? Then remove tape and reinstall limit? Just curious as to what your thoughts are. I am not comfortable with installing a plastic cap in that location. Keep the videos coming!

  • @HVACShopTalk
    @HVACShopTalk 11 ปีที่แล้ว +1

    Are the steel plugs rated for testing b vent?

  • @enricoricci4692
    @enricoricci4692 2 ปีที่แล้ว

    Change That Dull Drill Bit !! Great Video !!

  • @DayClanTribe
    @DayClanTribe 7 ปีที่แล้ว +1

    Great video presentation! I've got a question about your final comment that "static pressure is not a good way to quantify airflow". So even based against mfg specific-unit calculation charts you're saying those figures are not accurate enough?

    • @ArcheryRuleZ
      @ArcheryRuleZ 3 ปีที่แล้ว

      Good question, idk why the guy ignored u

    • @milotorres6894
      @milotorres6894 3 ปีที่แล้ว +1

      Staying within spec design keeps you from robbing Peter to pay Paul and have a balanced , quiet flow of air ...

    • @markhoffmann5941
      @markhoffmann5941 2 ปีที่แล้ว +1

      one reason i can think of is lets say a motor is not running proper speed for what ever reason. If the air flow charts are based on a known motor performance/speed and that motor is only @ 50% the measured pressures produced will be lower.

  • @martinwoods6716
    @martinwoods6716 4 ปีที่แล้ว

    Very Good Video,That’s for Explaining and being detailed about Static Pressure on Furnace..... Could you do the Hot Wire Anemometer Test Also plz....?

  • @quangnguyen-hq1bc
    @quangnguyen-hq1bc 9 ปีที่แล้ว

    Your explanation is very clear .Thanks

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว +1

    Thanks a lot for your feedback. I am trying to get more done. It takes a lot of time. I am glad that you find them useful. Let me know if there are topics of interest that you would like us to cover.

    • @imposterimpossible1580
      @imposterimpossible1580 4 ปีที่แล้ว

      TruTech Tools, LTD very helpful and well explained. Thanks for posting this stuff!

  • @pdavis8945
    @pdavis8945 9 ปีที่แล้ว

    Hi Jim, Great video, thanks. I may have room behind my furnace for drilling a hole, have close supply and return like yours, very tight. The high limit on my new Trane XT95 does not look like an easy pull out. How do I avoid drilling through something important on the back? Thanks, Paul

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว

    Static pressure tips provide a much more accurate reading as they are not subject to as much influence of velocity pressure in the duct system.

  • @RobHVAC
    @RobHVAC 11 ปีที่แล้ว

    Great video Jim. Very informative.

  • @sleepnessuk1476
    @sleepnessuk1476 9 ปีที่แล้ว +1

    Hey, I've a cross flow over finned tube heat exchanger inside duct, which type of pressure should I measure static or dynamic.

  • @langsbr
    @langsbr 11 ปีที่แล้ว +1

    Does the same testing rules apply for a heat pump system? I would presume so, but most of the information I see online refers only to furnaces.

    • @jimbergmann3499
      @jimbergmann3499 11 ปีที่แล้ว

      Yes, all of the same rules apply.

    • @Barracuda48082
      @Barracuda48082 6 ปีที่แล้ว

      Heatpumps are calculated for ac airflow..single stage..then cfm increases if additional btus or stages are added.

  • @celtichongy
    @celtichongy 7 ปีที่แล้ว

    Excellent training

  • @pawelkoper
    @pawelkoper 7 ปีที่แล้ว

    I'm confused, were you first using static pressure probes on the furnace (the ones with the closed tips)? And then you're describing a pitot tube (open tip) later in the video. I thought a pitot tube is used to figure out velocity pressure.

    • @BryanOrr36
      @BryanOrr36 7 ปีที่แล้ว +2

      pawelkoper Correct, he is just explaining both

  • @jbmoxley59
    @jbmoxley59 11 ปีที่แล้ว

    great tutorial. fantastic job on presentation!

  • @awsom70
    @awsom70 11 ปีที่แล้ว

    very good presentation! lots of useable info. thanks

  • @donsnow4564
    @donsnow4564 10 ปีที่แล้ว

    great video. thanks for upload. im here in canada and having a hard time finding these pitot tubes. i found one supplier that can get them in for me but sound expensive. 8" or 12" set for 120 dollars. any suggestions?

  • @mikemalone6103
    @mikemalone6103 8 ปีที่แล้ว +1

    Have an airflow problem. 1.08 Tesp measured across RTU but, this 2 ton unit is just dribbling out air in the registers. Using a magnehelic, how do I identify where the obvious blockage is, or why air isn't screaming out the registers, not concerned with noise only the output throw of warm air.

    • @BryanOrr36
      @BryanOrr36 7 ปีที่แล้ว +3

      Mike Malone you would need to start at the unit and take measurements periodically down the line until you see a big drop. In this case I would suspect a possible closed fire damper.

    • @hvac01453
      @hvac01453 7 ปีที่แล้ว

      thanks for your input...

  • @tyl8ter
    @tyl8ter 10 ปีที่แล้ว

    Honestly, What's the difference if you use a capture hood at SA or RA or Vane when CFMs and balancing is the concern............what is more accurate in you opinion..

    • @tyl8ter
      @tyl8ter 10 ปีที่แล้ว

      Thank you so much.

  • @garybonacci2031
    @garybonacci2031 5 ปีที่แล้ว

    @7:40, why do you say to put the tip in the direction of the airflow? I was told by more than one source to put the tip opposite the direction of airflow.

    • @TruTechTools
      @TruTechTools  5 ปีที่แล้ว +1

      Gary Bonacci It does not matter what way the tip points as long as the shaft is parallel to the flow. What you do not want is the velocity pressure to influence the reading by impacting the pressure sensing ports.

    • @TruTechTools
      @TruTechTools  5 ปีที่แล้ว

      Gary Bonacci we also have a short illustration at the following link under the “Resources” tab : www.trutechtools.com/SPTK

  • @jamesmartin5970
    @jamesmartin5970 2 ปีที่แล้ว

    I do not understand your calculating on you static pressure that you have it does not figure up right to me. 86,000-1.08x40=1990, or I am missing something. what I get 86,000-by 1.08x40=3185 help me under understand math.

  • @alanstephen7218
    @alanstephen7218 7 ปีที่แล้ว

    Very informative, thanks for posting.

  • @rocker8692
    @rocker8692 6 ปีที่แล้ว +8

    I thought the tube is pointed into the airflow.

    • @derrickgarcia303
      @derrickgarcia303 4 ปีที่แล้ว

      Yeah that’s what I thought too. You want the air to hit the tube.

    • @hangngoaigiare
      @hangngoaigiare 4 ปีที่แล้ว

      for static pressure no

  • @aaronharkness3599
    @aaronharkness3599 3 ปีที่แล้ว

    Much easier to drill a hole in the duct between the filter and the furnace. I won't drill into an appliance if I don't have to. Obviously, no choice between evaporator and the furnace. Generally, an installation manual will call for a 6" riser between the furnace and the evaporator. When these are installed, taking measurements is a breeze.

  • @wmhvac-r2826
    @wmhvac-r2826 7 ปีที่แล้ว

    wow great vid right off the batt!

  • @Scott4139
    @Scott4139 5 ปีที่แล้ว

    Is there any downside of having unequal positive and negative pressures, even if they sum to 0.5? Seems 0.1 on supply and 0.4 on return would cause other issues.

    • @TruTechTools
      @TruTechTools  5 ปีที่แล้ว

      That would indicate an imbalance in restriction, indicating more return flow is needed.

  • @ComfortTechNJ
    @ComfortTechNJ 11 ปีที่แล้ว

    Great video as always. Thank you.

  • @fitz2180
    @fitz2180 8 ปีที่แล้ว

    Very informative, Thank you!

  • @jjmoffo
    @jjmoffo 11 ปีที่แล้ว

    Great video keep them coming

  • @WoundedEgo
    @WoundedEgo 9 ปีที่แล้ว

    Would it be a helpful measurement to merely put your hand in front of the farthest vent to see if the air is flowing freely? I would think that only if you were not satisfied with that air flow that you would want to go to the trouble and expense to measure upstream, no?

  • @spartans2288622886
    @spartans2288622886 5 ปีที่แล้ว +3

    11:38 lmao! That's the good stuff!

  • @ruslan2s42
    @ruslan2s42 5 ปีที่แล้ว

    Thanks so much.

  • @deathk26
    @deathk26 9 ปีที่แล้ว

    I was laughing out loud after 11:38 .... Great video by the way

  • @dehrlich28
    @dehrlich28 8 ปีที่แล้ว +9

    11:30 - 11:45 cracks me up! lol

    • @Mikecianfrocco
      @Mikecianfrocco 7 ปีที่แล้ว

      DUSTIN EHRLICH that's funny lol

    • @Barracuda48082
      @Barracuda48082 6 ปีที่แล้ว

      Was Brian O behind camera? Lol

  • @bobbydigital8
    @bobbydigital8 11 ปีที่แล้ว

    Very helpful.

  • @TruTechTools
    @TruTechTools  11 ปีที่แล้ว

    Thanks

  • @ericthered3321
    @ericthered3321 9 ปีที่แล้ว +2

    Nice video kind of misleading at the end with the comment made about not wanting to use tesp as an airflow measurement tool, this can be done just fine as long as you have the fan chart from the manufacure which uses these measurement figures to rate the airflow at different tesp's.

  • @HVACShopTalk
    @HVACShopTalk 11 ปีที่แล้ว +1

    Thanks, I will send you an email at trutech. Thanks for the quick reply.

  • @doncocorote1
    @doncocorote1 6 ปีที่แล้ว

    Thanks 🙏🏼 nice 👍

  • @thomashuxley2959
    @thomashuxley2959 5 ปีที่แล้ว

    Don't think he'll get any manufacturer to agree that static pressure does not give you an accurate airflow. It tell you all you need to know about volume and velocity when you speak it's language, so to speak.

  • @Anton-du-Fleur
    @Anton-du-Fleur 7 ปีที่แล้ว

    11.45 oh yesss

  • @rocker8692
    @rocker8692 8 ปีที่แล้ว +2

    Oh sh#t lol

  • @noxloz1700
    @noxloz1700 4 ปีที่แล้ว

    нужен перевод на русский

  • @thomashuxley2959
    @thomashuxley2959 5 ปีที่แล้ว +1

    He put his tips the wrong way. ALWAYS point the "bullet" tip point toward the air.

    • @hangngoaigiare
      @hangngoaigiare 4 ปีที่แล้ว

      no hes right. he only want to find out static pressure so doesnt matter which way it point. other way for reading static and total velocity