tranfor potecia minuto 9:00 partes minuto 9:50 pruebas de mantenimineto 11:45 (vida útl 25 - 30 años) esquemas para realizacion de pruebas 14:45 medio de refrigeracion 15:45, prueba de aislamiento 18:00, relacion de transformacion 24:40, factor de potencia 30:14, resistencia de devanados 34:24, rigidez dielectrica del aceite 38:14, concluciones 48:38
🎯 Key points for quick navigation: 00:18 *🏭 Main content: Introduction to electrical tests for transformers.* - Overview of transformers and their significance in electrical systems. - Explanation of how transformers function based on electromagnetic induction. - Characteristics and types of transformers used in different settings. 03:17 *🌐 Main content: Types of transformers and their components.* - Description of auto-protected transformers for rural areas. - Explanation of pedestal transformers and their applications. - Overview of submersible transformers and their installation. 07:45 *🔬 Main content: Transformer applications in renewable energy.* - Use of transformers in solar energy generation. - Role of transformers in wind farms. - Importance of power transformers in industrial facilities. 09:48 *🛠️ Main content: Importance of transformer maintenance and components.* - Overview of key components in a transformer system. - Significance of regular maintenance for transformer longevity. - Common maintenance tests such as winding resistance and insulation resistance tests. 11:35 *⚡ Main content: Purpose and types of electrical maintenance tests for transformers.* - Importance of maintenance tests to prevent failures and ensure operational efficiency. - Different types of electrical tests including insulation resistance, power factor, and oil analysis. - Discussion on the typical lifespan and maintenance procedures for transformers. 21:59 *🔍 Electrical Testing for Transformers: Resistance Testing* - Evaluation of resistance between different coil and tank components - Connection schemes for resistance testing in different types of transformers - Minimum acceptable resistance values for insulation resistance testing 24:31 *🔌 Transformer Transformation Ratio Testing* - Definition and importance of the transformer transformation ratio test - Calculation of theoretical and measured transformation ratios - Interpretation of acceptable differences in transformation ratios 30:24 *⚡ Power Factor Testing for Transformers* - Purpose and significance of power factor testing - Detection of insulation issues and material aging through power factor measurements - Interpretation of power factor values for transformer diagnostics 42:43 *🧪 Gas Analysis Sampling Recommendations* - Recommendations for gas sampling and analysis procedures, 43:38 *🔍 Key Gases for Transformer Diagnosis* - Importance of analyzing key gases such as hydrogen, ethylene, and acetylene, - Threshold levels indicating overheating or dangerous conditions in transformers. 44:34 *🛠️ Methods of Gas Diagnosis* - Different gas diagnosis methods using tools like Delong's triangle and Roger's code, - How gas levels and patterns help technicians identify specific issues in transformers. 46:13 *⚠️ Interpreting Laboratory Reports* - Interpretation of laboratory reports based on gas concentrations and recommendations for maintenance, - Understanding gas concentrations as indicators of transformer health and potential failures. 49:12 *💡 Importance of Monitoring and Maintenance* - Significance of regular monitoring and maintenance of transformers, - Correlation between electrical test results, diagnostic interpretation, and proactive maintenance practices. 50:53 *📝 Final Recommendations for Transformer Maintenance* - Importance of transformer insulation and controllable factors in extending transformer life, - Emphasis on thorough maintenance practices, documentation, training, and safety protocols for maintenance technicians. Made with HARPA AI
Hice pruebas de aislamiento en un transf seco de 30 kv 480 a 220 le.metimos 500 Volts y se fue a OL no me da medición y luego le metimos 1000 Volts u solo me dio 15 y 30 seg.... Y otra vez OL a qué se debera
Hola, quisiera realizar una pregunta, en el apartado de resistencia de aislamiento con el megger, si nos encontramos con un trafo donde para realizar la prueba donde el trafo se encuentra puesto a tierra, entiendo que para hacerla prueba además de quitar las tierras y desconectar también la tierra del neutro y acá va la duda, es necesario cortocircuitar si el trafo trifasico ya se encuentra con los devanados unidos entre sí por medio de los puentes siendo delta en primario y estrella en el secundario ?
Muy buenos días Ing. comento sobre los transformadores que se utilizan para bancos de módulos solares, son especiales o cualquier transformador puede recibir el voltaje que suministran los módulos mencionados a través de el inversor que como ya comenta ud. convierte de DC a AC.
Muy buen video, soy estudiante de ingeniera electromecánica y me gustaría aprender más del tema, ¿alguna recomendación de un libro sobre este tema de transformadores?
Disculpe en mi casa el voltaje es de 258 voltios y mi mini Split arranca y y pasado 10 minutos se apaga se protege y la CFE me dice el voltaje está bien y yo les digo que no pero quién los saca de ahí ellos son los que según mandan saludos
En la prueba de resistencia de devanado a transformadores tipo sumergido en aceite, ¿Cómo evitar lectura errónea si el calentamiento del devanado se debe a que el transformador ha estado en funcionamiento? Gracias
Medi el voltaje de lado secundario y una línea meda 486 a 487 . Esto a qué se debe. Esta medición la hice desconectado todo y realice la prueba a la salidas de transformador
He participado en 2 mantenimientos, al hacer la prueba de Aislamiento (Meggeo) se tuvo problemas cuando se le aplicaba está prueba a Transformadores Secos, el equipo dejaba de medir a qué puede deberse?
Buen dìa, me gusto mucho el video, es excelente pero tengo una duda. ¿Còmo se hace la prueba de resistencia de aislamiento a un transformador Estrella-Estrella?.
Para un transformador Estrella-Estrella con neutros interconectados, la única medición de resistencia de aislamiento posible a realizar sería; Primario + Secundario vs Tierra o Tanque. (porque los neutros de ambos devanados están interconectados y por ello no hay un aislamiento que se pueda medir) Si para el mismo ejemplo, adicionalmente a que los neutros están interconectados, también están referidos al tanque, entonces no es posible realizar NINGUNA prueba de aislamiento.
En el tema de medición de Aislamiento, me causa duda si esta correcta la tabla de Índice de Absorción (DAR) y el Índice de Polarización (PI) debido a que esa tabla es para maquinas Rotativas según la IEEE y según el Manual de Aislamiento Megger y no es aplicable para transformadores. ¿Si alguien tiene alguna otra información seria bueno para salir de la duda?
IEEE62-2005 Guide for Diagnostic Field Testing Part1 Transformers (clause 6.1.5.2): For small transformers the polarization index will be equal to 1 or slightly higher. Larger transformers may exhibit a polarization index of 1.1-1.3. In general, a high value of polarization index indicates that the insulation system is in good condition. A polarization index of
Hice pruebas de aislamiento en un transf seco de 30 kv 480 a 220 le.metimos 500 Volts y se fue a OL no me da medición y luego le metimos 1000 Volts u solo me dio 15 y 30 seg.... Y otra vez OL a qué se debera
OL significa que el medidor de aislamiento esta fuera del rango de medicion del transformador, necesita un probador de aislameiento con un buen rango de medicion, ¿cual modelo de equipo tienes?
@@xcoff2000 pero debe de tener un rango máximo de medición, como 100 Gigaohms, 200 Gigahoms, 1 Teraohm, 10 Teraohms, 30 Teraohms... revisa tu ficha técnica, debe indicar su rango máximo de medición..
Gracias por su buena esplicacion es un orgullo escuchar su buena intencion de prebencion de accidentes Dios lo bendiga
Chingón, mi buen amigo Ángel Marroquín. Felicidades, buen trabajo.
tranfor potecia minuto 9:00
partes minuto 9:50
pruebas de mantenimineto 11:45 (vida útl 25 - 30 años)
esquemas para realizacion de pruebas 14:45
medio de refrigeracion 15:45, prueba de aislamiento 18:00, relacion de transformacion 24:40, factor de potencia 30:14, resistencia de devanados 34:24, rigidez dielectrica del aceite 38:14, concluciones 48:38
Gracias por compartir Maestro, está muy eficaz y desarrollado el tema, saludos desde la DVMS CFE.
🎯 Key points for quick navigation:
00:18 *🏭 Main content: Introduction to electrical tests for transformers.*
- Overview of transformers and their significance in electrical systems.
- Explanation of how transformers function based on electromagnetic induction.
- Characteristics and types of transformers used in different settings.
03:17 *🌐 Main content: Types of transformers and their components.*
- Description of auto-protected transformers for rural areas.
- Explanation of pedestal transformers and their applications.
- Overview of submersible transformers and their installation.
07:45 *🔬 Main content: Transformer applications in renewable energy.*
- Use of transformers in solar energy generation.
- Role of transformers in wind farms.
- Importance of power transformers in industrial facilities.
09:48 *🛠️ Main content: Importance of transformer maintenance and components.*
- Overview of key components in a transformer system.
- Significance of regular maintenance for transformer longevity.
- Common maintenance tests such as winding resistance and insulation resistance tests.
11:35 *⚡ Main content: Purpose and types of electrical maintenance tests for transformers.*
- Importance of maintenance tests to prevent failures and ensure operational efficiency.
- Different types of electrical tests including insulation resistance, power factor, and oil analysis.
- Discussion on the typical lifespan and maintenance procedures for transformers.
21:59 *🔍 Electrical Testing for Transformers: Resistance Testing*
- Evaluation of resistance between different coil and tank components
- Connection schemes for resistance testing in different types of transformers
- Minimum acceptable resistance values for insulation resistance testing
24:31 *🔌 Transformer Transformation Ratio Testing*
- Definition and importance of the transformer transformation ratio test
- Calculation of theoretical and measured transformation ratios
- Interpretation of acceptable differences in transformation ratios
30:24 *⚡ Power Factor Testing for Transformers*
- Purpose and significance of power factor testing
- Detection of insulation issues and material aging through power factor measurements
- Interpretation of power factor values for transformer diagnostics
42:43 *🧪 Gas Analysis Sampling Recommendations*
- Recommendations for gas sampling and analysis procedures,
43:38 *🔍 Key Gases for Transformer Diagnosis*
- Importance of analyzing key gases such as hydrogen, ethylene, and acetylene,
- Threshold levels indicating overheating or dangerous conditions in transformers.
44:34 *🛠️ Methods of Gas Diagnosis*
- Different gas diagnosis methods using tools like Delong's triangle and Roger's code,
- How gas levels and patterns help technicians identify specific issues in transformers.
46:13 *⚠️ Interpreting Laboratory Reports*
- Interpretation of laboratory reports based on gas concentrations and recommendations for maintenance,
- Understanding gas concentrations as indicators of transformer health and potential failures.
49:12 *💡 Importance of Monitoring and Maintenance*
- Significance of regular monitoring and maintenance of transformers,
- Correlation between electrical test results, diagnostic interpretation, and proactive maintenance practices.
50:53 *📝 Final Recommendations for Transformer Maintenance*
- Importance of transformer insulation and controllable factors in extending transformer life,
- Emphasis on thorough maintenance practices, documentation, training, and safety protocols for maintenance technicians.
Made with HARPA AI
Gracias por compartir imformación valiosa un saludo desde Ecuador
Buenas noches y gracias por la excelente presentacion.
Muy bien detallado. Gracias por compartir los conocimientos.
Exelente. Soy Tecnólogo en automatización todo esto lo estudie y somos las prácticas y son muy exelentes estás pruebas.
Hice pruebas de aislamiento en un transf seco de 30 kv 480 a 220 le.metimos 500 Volts y se fue a OL no me da medición y luego le metimos 1000 Volts u solo me dio 15 y 30 seg.... Y otra vez OL a qué se debera
Excelente muy claras las notas, recomendaciones etc.
Información muy buena
Gracias ing. Por esta.clase. siempre con tecnologia por delante esplicaciones correctas
Excelente presentación
Imágenes muy ilustrativas
Muy buen video, saludos desde Querétaro, México
muchas gracias ing fue de mucha ayuda bendiciones ...
Muchísimas gracias por el aporte
Bastante ilustrativo y técnico
Ecelente informacion, Muy Agradecido por compartir
Excelente inge.. muy profesional
Excelente ⚡👷
Muchas gracias por el contenido, didáctico .. Saludos derde Perú.
Gracias por sus cursos
Hola, quisiera realizar una pregunta, en el apartado de resistencia de aislamiento con el megger, si nos encontramos con un trafo donde para realizar la prueba donde el trafo se encuentra puesto a tierra, entiendo que para hacerla prueba además de quitar las tierras y desconectar también la tierra del neutro y acá va la duda, es necesario cortocircuitar si el trafo trifasico ya se encuentra con los devanados unidos entre sí por medio de los puentes siendo delta en primario y estrella en el secundario ?
Muy buen vídeo, Gracias
Agradezco por la información proporcionada. Una pregunta, ¿Donde puedo conseguir la SOM 3531?
Saludos.
Muy buenos días Ing. comento sobre los transformadores que se utilizan para bancos de módulos solares, son especiales o cualquier transformador puede recibir el voltaje que suministran los módulos mencionados a través de el inversor que como ya comenta ud. convierte de DC a AC.
Buenísimo gran explicación
Muy buen video, soy estudiante de ingeniera electromecánica y me gustaría aprender más del tema, ¿alguna recomendación de un libro sobre este tema de transformadores?
compa, métase a trabajar a una empresa de la rama eléctrica, ahí va a agarrar mas experiencia
Muy util muchas Gracias
Es importante que todo Electricista
Debe estar capacitado y actualizado
gracias
Disculpe en mi casa el voltaje es de 258 voltios y mi mini Split arranca y y pasado 10 minutos se apaga se protege y la CFE me dice el voltaje está bien y yo les digo que no pero quién los saca de ahí ellos son los que según mandan saludos
En la prueba de resistencia de devanado a transformadores tipo sumergido en aceite, ¿Cómo evitar lectura errónea si el calentamiento del devanado se debe a que el transformador ha estado en funcionamiento?
Gracias
se debe esperar a que enfrié hasta que esté a temperatura ambiente para empezar la prueba
como sertificarse como mechanico de mantenimiento de trasnformadores
Medi el voltaje de lado secundario y una línea meda 486 a 487 . Esto a qué se debe. Esta medición la hice desconectado todo y realice la prueba a la salidas de transformador
He participado en 2 mantenimientos, al hacer la prueba de Aislamiento (Meggeo) se tuvo problemas cuando se le aplicaba está prueba a Transformadores Secos, el equipo dejaba de medir a qué puede deberse?
Exactamente me pasa lo mismo
Excelente información, muy didáctica y entendible. Se requiere libro de consultas o artículos científicos, muchas gracias.
Muy bueno me gustaría siempre
recibir información o pertenecer a su grupo para tener más información
Buen dìa, me gusto mucho el video, es excelente pero tengo una duda. ¿Còmo se hace la prueba de resistencia de aislamiento a un transformador Estrella-Estrella?.
Tengo esta misma duda, la pudiste resolver?
Para un transformador Estrella-Estrella con neutros interconectados, la única medición de resistencia de aislamiento posible a realizar sería; Primario + Secundario vs Tierra o Tanque. (porque los neutros de ambos devanados están interconectados y por ello no hay un aislamiento que se pueda medir)
Si para el mismo ejemplo, adicionalmente a que los neutros están interconectados, también están referidos al tanque, entonces no es posible realizar NINGUNA prueba de aislamiento.
En el tema de medición de Aislamiento, me causa duda si esta correcta la tabla de Índice de Absorción (DAR) y el Índice de Polarización (PI) debido a que esa tabla es para maquinas Rotativas según la IEEE y según el Manual de Aislamiento Megger y no es aplicable para transformadores. ¿Si alguien tiene alguna otra información seria bueno para salir de la duda?
IEEE62-2005 Guide for Diagnostic Field Testing Part1 Transformers (clause 6.1.5.2): For small transformers the polarization index will be equal to 1 or slightly higher. Larger transformers may exhibit a polarization index of 1.1-1.3. In general, a high value of polarization index indicates that the insulation system is in good condition. A polarization index of
Entonces la ieee 43 2000 para máquinas rotativas
Y la ieee 63 2005 para tr
Es el mismo principio?
Hice pruebas de aislamiento en un transf seco de 30 kv 480 a 220 le.metimos 500 Volts y se fue a OL no me da medición y luego le metimos 1000 Volts u solo me dio 15 y 30 seg.... Y otra vez OL a qué se debera
OL significa que el medidor de aislamiento esta fuera del rango de medicion del transformador, necesita un probador de aislameiento con un buen rango de medicion, ¿cual modelo de equipo tienes?
@@mariogomez3213 según es autorango
@@xcoff2000 pero debe de tener un rango máximo de medición, como 100 Gigaohms, 200 Gigahoms, 1 Teraohm, 10 Teraohms, 30 Teraohms... revisa tu ficha técnica, debe indicar su rango máximo de medición..
Usted se dedica a ese tipo de servicios
Mas para ingenieros este video que para gente que quiere aprender de a poco, pasoooo chauuu jajaja
Parece un correcaminos, lee sin parar, no detalla en casi nada, poco que rescatar
.
Habla.mucho y no.dice nada de lo que necesito
Gracias